5.3.3 REGULATION T-box - ELIS A-W/N WIRING DIAGRAMS
Power supply 230V/50Hz (OMY 3x1mm
2
)
T-box (OMY 4x0,5mm
2
)
Door contact DCe/DCm (door closed
– contacts opened; door opened – contacts closed)
Valve with actuator SRSQ3d (OMY 3x0,5mm
2
) or SRQ (OMY 3x0,5mm
2
)
A
– Exchanger water supply
AB
– Valve water supply
B
– Return pipe water supply
5.3.4 REGULATION T-box - ELIS A-E WIRING DIAGRAMS
Power supply 3x400V/50Hz
ELiS A-E-100 (min. 5x4 mm
2
) (Overcurrent B16)
ELiS A-E-150 (min. 5x6 mm
2
) (Overcurrent B20)
ELiS A-E-200 (min. 5x6 mm
2
) (Overcurrent B25)
T-box (OMY 4x0,5mm
2
)
Door contact DCe/DCm (door closed
– contacts opened; door opened – contacts closed)
ATTENTION:
Switch 4 on SW3 to the position
“E” and then restart the system switching it off for 5 seconds. Each time the device is switched
off the heaters are being cooled for next 15 seconds.