Mechanical Trouble 

  Valve will not operate          1)    Try moving the valve with the Manual Handwheel  after  

 

                                                                 Pulling the declutch lever.  

                                                     2)  Watch mechanical position On top of actuator for movement    

                                                     3)  If Handwheel will not move, the valve is stuck. Valve needs to    

                                                                

disassembled and repaired. 

                           4)  If Handwheel moves well without interruption, check the        

                                                            adapter connecting the valve and actuator.                                       

                                                     5)  If Handwheel moves check electrical functioning. 

 

Electrical Trouble             

1)

  

Check Main Power Supply, relays,  fuses, lamps, switches 

Check Main                               2)  If the problem is the control panel- replace defective parts. 

 Control Panel 1

st

                           If  NO Control Panel problem Check Actuator 

Then Actuator                          3)  Check the Actuator Motor and replace if necessary. 

                                                    4)  Torq Switch Tripping-  turn main power off and follow  

                                                         Mechanical Trouble Shooting procedure  

                                                    5) Check for faulty Limit switch with circuit check, 

                                                        adjust or replace. 

                                                    6) All other electrical problems can be resolved by parts   

                                           Replacement. 

 

FCEL Actuators are designed for long life under normal operating conditions. It is 
Recommended to make an operational check 2X’s per year. 

Flomatic  warrants all products to be free of defects in workmanship and materials for 1 Year 

from date of shipment. 

 

 

 

15 Pruyn's Island Drive   Glens Falls, New York   12801 

Phone  (800) 833-2040       

www.flomatic.com

 

Fax (518) 761-9798       

Содержание FCEL

Страница 1: ... once electric power is energized If in manual mode when electric power is re energized actuator will automatically declutch and operate 2 2 Valve Position Indication Actuator Top mounted Visual position indication shows OPEN and CLOSED valve position 3 Wiring Connections 3 1 Top Housing Cover Removal Remove the 4 Socket head Housing Capscrews with a hex key wrench Lift housing cover from actuator...

Страница 2: ...n screw 4 2 Setting the Open Limit Switch Upper Cam and Upper Switch 1 Pull the declutch lever and turn Handwheel counter clockwise to move the valve to the fully Opened position 2 Using a hex key wrench loosen the upper cam screw Opened LS 3 Adjust the cam to trip the upper cam switch LS then tighten screw 4 3 Mechanical Travel Limit Stops TLS 1 Closed Travel Limit Stop is on Left and Open Travel...

Страница 3: ... removal 2 Machining The Drive bushing is machined to adapt to valve shaft or mounting coupler if actuator is not direct mounted to the valve If key keyway adaptation is used the directionof keyway should align with one of the drive busing screws 6 2 Reassembling the drive bushing 1 Check the relative position of valve and actuator Open Closed If not rotate the actuator to same position as valve 2...

Страница 4: ...rol panel replace defective parts Control Panel 1st If NO Control Panel problem Check Actuator Then Actuator 3 Check the Actuator Motor and replace if necessary 4 Torq Switch Tripping turn main power off and follow Mechanical Trouble Shooting procedure 5 Check for faulty Limit switch with circuit check adjust or replace 6 All other electrical problems can be resolved by parts Replacement FCEL Actu...

Отзывы: