Air to water heat pump operation manual
P9
When retrun water temperature
≥
L6, return water valve close.
10.
10.
10.
10. Automatical
Automatical
Automatical
Automatical running:
running:
running:
running:
Under the condition of no control panel or control panel is damaged, system check about 1 minute, confirm
there is not control panel enter automatical controlling.
When run automatically:
Water tank preset temperature =55
℃
Preset outlet water temp of direct outlet water=50
℃
Deviation value of Water tank temprerature =0
Temp difference at which Compressor can restart after compressor stop = 5
℃
Period of defrosting=35minutes
Temperature at which system enter defrost state = -5
℃
Defrost runtime = 8 minutes
Temperature at which system quit defrost state =20
℃
Temperature at which electric heating startup=10
℃
Return water temperture=45
℃
Water supply temperature=40
℃
Degree of superheat=0
℃
Non check compressor current.
Ⅶ、
Protection
Protection
Protection
Protection illustration
illustration
illustration
illustration
1
、
Pretection of compressor postpones 3 minutes, both compressor turn on and off need 3 minutes. every time,
compressor needs 3 minutes to restart after it stoped.
2
、
Water flow switch protection (hydronic heating system use it ). After press
“
power
”
key, and cycle water pump
run, if water flow switch off,
then compressor and fan off.
3
、
High exhaust temperature pretection: when exhaust temperature
≥
115
℃
and last 30s, system consider
temperation is too high, close output, display error code, 3 minutes later system can restart.
4
、
High pressure protection
:
when high pressure switch disconnect 3 times within an hour, display panel show error
code and alarm. Then compressor off, fan off, cycle water pump off. After high pressure switch recover ,
postpone 3 minutes ,compressor restart, If high pressure switch disconnect over 3 times within an hour, control
panel lock the error, turn off all output signal, and will not restart whether pressure switch will recover or not.
5
、
Low pressure protection. when low pressure switch disconnect 3 times within an hour, display panel show error
code and alarm. Then compressor off, fan off, cycle water pump off. After low pressure switch recover, postpone
3 minutes, compressor restart. If low pressure switch disconnect over 3 times within an hour, control panel will
lock the error, close all output signal, and will not restart whether pressure switch will recover or
not..(Remarks:when defrosting, or within 5 minutes after compressor startup, system doesn’t test low pressure
switch)
6
、
Sensor error: if sensor occure error(broken circuit or short circuit), all output stop, and show error code. Sensor can
restart after erroe disappear.
7
、
Three phase protection
:
when dial switch 1 select number side, it has three phase test function, it will test three