16
300
80
0
100
200
300
Pa
m
3
/h
200
0
100
400
W
0
20
40
60
0
40
80
l/s
60
20
230V
150V
190V
105V
85V
120V
170V
230V
150V
120V
85V
190V
170V
105V
60V
60dB(A) 65dB(A)
70dB(A)
60V
55dB(A)
50dB(A)
10 Capacity and sound data
10.1 Capacity diagram, sound data, specifications - K2 R AC
Supply air side (with F7 filter)
Data for supply air is measured in accordance with ISO 5136,
"In-duct method".
Radiated noise is measured in accordance with ISO 9614-2.
Bruel & Kjær measuring equipment, type 2260.
Air capacity at various capacity settings in Volt.
Supply air fan power consumption at various capacity settings.
Sound power level LwA, cf. correction table.
Sound data is given at sound power level LwA in the capacity diagrams
and is corrected with the table below for the various octave bands.
Radiated noise produces Lw in the various octave bands and total
LwA. This is read directly from the supply air table.
Correction factor for
Hz
63 125 250 500 1000 2000 4000 8000
LwA
Supply air 3
2
-2
-5
-5
-6
-13
-29
Extract air 18
14
1
-12
-14
-28
-37
-43
Radiated -46 -39 -29 -36
-40
-44
-54
-58
-33,5
Extract air side (with F7 filter)
P
ow
er c
on
su
m
pt
io
n i
n W
at
t
C
on
ta
ct r
es
is
ta
nc
e (
P
a)
Air flow rate, m
3
/h - Pressure correction factor
0
40
80
l/s
60
20
W
0
20
40
60
80
0
100
200
300
400
Pa
230V
150V
190V
85V
60V
170V
230V
150V
120V
85V
190V
170V
105V
60V
60dB(A)
64dB(A)
55dB(A)
45dB(A) 50dB(A)
120V
105V
m
3
/h
200
0
300
100
For fitter
P
ow
er c
on
su
m
pt
io
n i
n W
at
t
C
on
ta
ct r
es
is
ta
nc
e (
P
a)
Air flow rate, m
3
/h - Pressure correction factor
Yellow field: SFP < 1.0 per fan
Yellow field: SFP < 1.0 per fan