 Installation Manual

Cable Kit Instructions

6). Installation of larger areas requiring 'add-on' cables. 
 

Illustrated is a 20 square metre conservatory requiring a type EK10 2950 cable kit to provide 
optimum heat. (18.4m² coverage allowing for edge clearance). 
 

MAIN HEATING

CABLE

ADDITIONAL CABLE

FLOOR PROBE

THERMOSTAT

50mm
EDGE
CLEARANCE

 

 

Firstly mark out the floor as previously described. 

 
Using the main kit cable (2000watts) run this out from  the termination point to the opposite 
end of the room and lay at 7cm spacings (12.5m2 c overage) back towards the control point. 
Check that remaining floor area will accommodate the additional 950watt cable (5.9m2 
coverage). Lay the additional cable and if necessary adjust the spacing to achieve full floor 
coverage. (The thermostat sensor m ust be positioned centrally between cable loops). 
 

Tiling the floor.  
 

Once the cables are laid suitable protection boards / old carpet must be provided to avoid 
damage during tiling. 
Tile adhesive can be laid in either a single or a two layer operation depending on the tiler’s 
preference to accommodate the 3m m cable thickness. The adhesive must be laid evenly in 
the same direction as the cables are running mak ing sure there are no air spaces. 
 

The following table of products are suitable for use with a Flexel Ecofloor underfloor 
heating system. Refer to the additional requ irements when using Depron underlay 
insulation and for further information and advice contact the Flexel technical 
department.

 

 

Содержание Ecofloor

Страница 1: ...d all permanent fixtures such as baths showers kitchen and bedroom units remember also that it is important to avoid thermally blocking the heated area as this will result in localised heat build up a...

Страница 2: ...0 8 1 9 3 10 5 11 8 13 0 41 EK 101700 1700 10 6 11 9 13 1 15 1 17 0 31 EK 102000 2000 12 5 14 4 16 2 18 1 20 0 26 EK 102300 EK1700 AD600 2300 14 3 15 9 17 7 20 0 23 0 23 EK102600 EK2000 AD600 2600 16...

Страница 3: ...marked and scaled drawing your supplier will calculate the appropriate kit required 2 Floor preparation Cable kits can be laid onto most existing floor surfaces that are sound and suitably prepared A...

Страница 4: ...quired and the electrical supply position form a channel in the floor adjacent to this point as illustrated THERMOSTAT SUPPLIED 45mm RECESSE D MOUNTING BOX REQUIRED FOR FLUSH MOUNTING 230VOLT SUPPLY F...

Страница 5: ...t again If you have ordered the wrong size of kit contact your supplier Now and referring to the tables on page 1 test the cable circuit for continuity resistance using an ohmeter Avoid traffic over t...

Страница 6: ...6 Flexel Installation Manual Cable Kit Instructions Finished Floor Diagrams Cross Section Flexible adhesive Tile finished with flexible grout...

Страница 7: ...att cable 5 9m2 coverage Lay the additional cable and if necessary adjust the spacing to achieve full floor coverage The thermostat sensor must be positioned centrally between cable loops Tiling the f...

Страница 8: ...440 multicoat for wet areas Mira 4800 antifire fluid primer Mira X Plan self Levelling acrylic and Fibre reinforced levelling compound Mira 3250 superplan Fix acrylic reinforced cement based quick cur...

Страница 9: ...tching on Before switching on the underfloor heating allow a minimum of 3 days for natural drying of the tile adhesive and grout Initially operate the system for 2 3 hours per day increasing to full c...

Отзывы: