Fleck 7000 Скачать руководство пользователя страница 2

Clean Water Systems & Stores Inc 7000 Meter Greensand Filter Programming Guide 2010 

backwashes.  If your water hardness is 10 grains per gallon for example, set this to 10.   If your 
water test shows the hardness in PPM or mg/L, then divide this number by 17.1 to reach grains 
per gallon.  1 grain per gallon = 17.1 ppm or mg/L of hardness. 
 

6. 

Reserve Selection (Display Code RS):  Set to SF.

    

 

7. 

Safety Factory (Display Code SF):

  Set to 20.  This will allow the softener to regenerate 200 

gallons sooner to avoid having the softener resin get totally exhausted before it need s to 
regenerate. 

 

8. 

Day Override (Display Code DO): Set to 7 to 14 

. Use the Up or Down arrows to change the 

setting. This will allow the softener to regenerate once every 7 to 14 days no matter how much 
water is used.  This is optional (can be set to 0) but it can be useful if you have iron or other 
sediment to keep the softener clean. 

 

9. 

Regeneration Time: (Display Code RT):  Set to 2:00 am

 generally or sometime when no water 

is being used, and no other filter or softener is likely to be in a regeneration cycle. Press the Extra 
Cycle button. 

 

10. 

Regeneration Cycle Step Times: 

Use this display to set the various minutes of each cycle. 

Some of the cycles will be set to 0. 

Do not set any of the cycles to Off

. Use the Up or Down 

arrows to change the setting  to the desired setting.  Press the Extra Cycle button to accept the 
setting and move to the next parameter. 

a. 

B1 – Backwash: Set to 8 minutes. 

 

b. 

BD - Brine Draw: Set to 60

 

c. 

B2 - 2

nd

 Backwash: Set to 6 minutes.

 

d. 

RR -  Rapid Rinse:  Set to 6 minutes

 

e. 

BF - Brine Fill:  

30K grain softeners: set to 12  minutes.  48K grain softeners set to 20 

minutes.  80K grain softeners: set to 32 minutes. 

f. 

SV - Service (meaning it is in Service or filtering mode) no setting is needed for 

this. 

Press the Extra Cycle button 

 

 

11.  Flow Meter Type (Display Code FM):

 Set to t1.2 (which is standard Fleck 7000 meter). Press 

the Extra Cycle button.

 

 

Содержание 7000

Страница 1: ...Cubic Meters if out of the U S Press the Extra Cycle button to go to the next step 2 Valve Type Display code VT Set to DF2b This means it is set for standard Downflow mode Press the Extra Cycle button to go to the next step 3 Control Type Display Code CT Set to Fd This is the Meter Delayed option This tells the Fleck 7000 control to meter or keep track of the amount of water used but then wait unt...

Страница 2: ...er sediment to keep the softener clean 9 Regeneration Time Display Code RT Set to 2 00 am generally or sometime when no water is being used and no other filter or softener is likely to be in a regeneration cycle Press the Extra Cycle button 10 Regeneration Cycle Step Times Use this display to set the various minutes of each cycle Some of the cycles will be set to 0 Do not set any of the cycles to ...

Страница 3: ... to 2 00 am generally or sometime when no water is being used and no other filter or softener is likely to be in a regeneration cycle Press the Extra Cycle button 4 Feed Water Hardness Use this setting to adjust the feed water hardness Set for 20 for most applications Press the Extra Cycle button 5 Fixed Reserve Capacity Display Code RC This allows you some reserve in case the softener meter has c...

Страница 4: ... the system s reserve capacity calculated from system capacity feedwater hardness and safety factor SV Software Version Displays the software version installed on the controller Some items may not be shown depending on timer configuration The timer will exit Diagnostic Mode after 60 seconds if no buttons are pressed Press the Extra Cycle button to exit Diagnostic Mode at any time ...