1.3 FLUE TERMINAL POSITION

The minimum acceptable dimensions from the flue terminal to obstructions

and ventilation openings are shown below and listed in the table

It is important that the position of the flue allows the free passage of air

across it at all times. The minimum acceptable space from the flue terminal

to obstructions and ventilation openings are specified below (Fig. 2)

Fig. 2

DIMENSION TERMINAL POSITION

MINIMUM DIMENSION

A

Directly below an opening, air brick,

300mm (12in)

opening window

B

Above an opening, air brick,

300mm (12in)

opening window

C

Horizontally to an opening, air brick,

opening window etc.

D

Below gutters, soil pipes or drain pipes

300mm (12in)

E

Below eaves

300mm (12in)

F

Below balconies or car port roof

600mm (12in)

G

From a vertical drain pipe or soil pipe

300mm (12in)

H

From an internal or external corner

600mm (24in)

I

Above ground roof or balcony level

300mm (12in)

J

From a surface facing the terminal

600mm (24in)

K

From a terminal facing the terminal

600mm (24in)

L

From an opening in the car port

1200m (48in)

M

Vertically from a terminal on the same wall

1500mm(59in)

N

Horizontally from a terminal on the

300mm (12in)

same Wall

O

NOT APPLICABLE

N/A

P

NOT APPLICABLE

N/A

Q

NOT APPLICABLE

N/A

5

Содержание Raglan

Страница 1: ...BALANCED FLUE GAS FIRE Installation and Maintenance Instructions Hand these instructions to the user Model No KBFC MN for use on Natural Gas G20 at a supply pressure of 20 mbar in G B I E NB denotes...

Страница 2: ...nstallation of the gas supply 11 12 2 7 Securing of the firebox to the wall 12 14 2 8 Preparation for mounting the flue terminal 15 2 9 Fitting the terminal guard 16 2 10 Removal refitting of the glas...

Страница 3: ...60 NG Pilot Type S I T 140 Series NG size 27 Max Gross Heat Input 3 8 kW Min Gross Heat Input 2 5 kW Gas Rate 0 345 m3 hr Cold Pressure 20 0 1 0 mbar 8 0 0 4 in w g Ignition Push button Piezo Electrod...

Страница 4: ...re appropriate the Building Regulations Scotland Consolidation issued by the Scottish Development Department and all applicable requirements of the following British Standard Code of Practice 1 B S 58...

Страница 5: ...ve an opening air brick 300mm 12in opening window C Horizontally to an opening air brick opening window etc D Below gutters soil pipes or drain pipes 300mm 12in E Below eaves 300mm 12in F Below balcon...

Страница 6: ...ION 2 INSTALLATION OF FIRE 2 1 UNPACKING THE FIRE Carefully lift the fire out of the carton Remove the loose item packaging carefully from the the pack Check the contents as listed IMPORTANT THE CARDB...

Страница 7: ...ening Any surround must be suitably sealed to the fire place to prevent leakage See fig 3 below Fig 3 A min max sized opening with a flat rear face between the fire opening and flue outlet terminal is...

Страница 8: ...fitted or 125mm without black spacer fitted 2 3 PREPARATION OF THE WALL The appliance and flue pipes must be installed at right angles to the mounting wall The appliance itself should be installed ver...

Страница 9: ...ole To Hammer and chisel proceed as follows Mark the position of the centre of the flue pipe as specified in figure 5 Mark the position of the hole around this point Chisel out the area as marked on t...

Страница 10: ...or the inner flue pipe 87 5mm diameter add an additional 25mm to dimension A and cut the inner flue pipe squarely to length IMPORTANT DO NOT CUT FLANGED ENDS OF FLUE PIPE ENSURE THE PIPES ARE CUT SQUA...

Страница 11: ...er the firebox from the left right or rear and connect to the inlet elbow See below a If concealed pipe work is required plan the pipe run to enter the fire box through one of the openings in the side...

Страница 12: ...e installer to deal with any type of installation The preferred method of fixing the appliance is the cable fixing method which is described in detail in the following section If the standard firebox...

Страница 13: ...h the fixing eye at the bottom d Thread the cables through the rear of the firebox insert the flue pipes through the hole in the rear of the wall and offer the firebox up to the fireplace e Thread the...

Страница 14: ...on the main gas supply and carry out a gas tightness test l Depress the control knob and turn anti clockwise to the position marked pilot Hold in the control knob for a few seconds to purge the pipe...

Страница 15: ...terminal as a template Remove the flue terminal and drill the 2 off holes 6mm diameter into the wall Insert the raw plugs Replace the terminal onto the flue pipe and secure using the No 12 x 40mm scr...

Страница 16: ...er wall Remove the terminal guard and drill the 4 off 6 mm holes Insert the raw plugs into the drilled holes replace the terminal guard over the top of the flue terminal and attach to the wall using t...

Страница 17: ...at the bottom left hand corner of the firebox and advise the customer of the position of the allen key NOTE Always ensure that a consistent seal between the combustion cham ber and the glass frame is...

Страница 18: ...nce before and after working on the appliance When replacing these articles we recommend that the replaced items are not broken up but are sealed within heavy duty polythene bags clearly labelled as R...

Страница 19: ...l knob in the anti clockwise direction to the high position and the main burner will light e Turn the control knob clockwise to the low position and the gas input will be reduced to the minimum settin...

Страница 20: ...ff fixing screws which hold the pilot shield in place 4 1 3 Loosen the pilot pipe disconnect the ignition lead from the electrode and disconnect the thermocouple from the pilot assembly 4 1 4 Remove t...

Страница 21: ...he electrode and disconnect the thermocouple from the pilot assembly 4 3 5 Remove the 2 off fixing screws from the base of the control panel 4 3 6 Slide the control panel and gas train forwards to the...

Страница 22: ...uracy of illustrations and descriptions contained in this book cannot be guaranteed PARTS SHORTLIST Replacement of parts must be carried out by a competent person such as a CORGI registered gas instal...

Отзывы: