TemplateA4_v20120211
6
3. Commissioning, use
The expansion module, in position on the fastened control unit cover, that allows the power supply and control unit to be switched
“On” in place, menu [11-3-8] gives access to the version view of the following extension:
Service menu [11] »
[11]
» Version information [11-3] »
[11-3]
» slot 3 [08.03.11] »
[11-3-8]
If the version number under [11-3-8] is missing, the module is not ready for operation (see page 6 - Internal and external error
messages). The initialized module (ready for operation) enables the signal output from Start in the start menu [9-9] (equipment
operational). Changes to the configuration that stop the control functions (in the menu navigation, confirming the question ‘Stop
system?’) interrupt the Capacity signal output, pressure analogue.
To maintain the signal output, it is essential that the power supply is available, the control unit is switched “On” and the equipment
sensors are functioning properly. To service the sensors, the requisite factory settings/initial conditions must be restored.
Note: Drawings of components may differ from actual parts supplied.
Commissioning, use
Location of data in menu:
Menu
Date, time
Menu
Language
Start-up
menu
Operation
menu
Service menu
Network
menu
Menu
Log-in
Configuration
menu
Menu
Data transfer
Equipment
information
Version
information
Error list
Hours of
operation
Top-up/
draining
Maintenance
Order
number
Terminal
Forward
Slot 1
Slot 2
Slot 3
Slot 4
Loader
Language
Controller
Main menu
Service
menu
Version
information
Internal messages; LED displays on the extension (nos. 1.3 and 1.4);
Status
Description
measures
Green "Off"
Extension not recognised, not available, no
access (version number under [11-3-8] not
available).
Control unit, power supply;
use indicated slot; clean contact surfaces of the
connector strip.
Green "On"
Extension recognised.
Function available.
Green "flashing"
Data transfer
-
Red "Off"
No errors.
-
Red "On"
Use of module blocked
(Exceeded Licensing).
Use extension on one of three previously used
control units.
Red "intermittent"
Last action resulted in error.
Carry out positioning under initial conditions (see
also: "External error message",
60 Extension).
External message; applicable error message after going to message display on terminal if error message shown:
Display
Description
measures
60
Extension
Last external extension action resulted in error
(identical to LED red, flashing intermittently;
no. 1.4).
Important: Error not saved, not contained in menu
[11-6]
(Error history, analysis).
Acknowledgement deactivates the error message
and the flashing red LED. (No consequences if
the error is not acknowledged). Check extension
positioning (extension may be removed).
Commis
sioning
Содержание SPC Extension Module