7.1.4 Modbus – properties 

Properties of Modbus RTU in the client-server network

Network topology

Linear bus with bus termination:  

Cable with 120 Ohm resistance at both ends

Transmission medium

For connecting the devices, bus cables suitable for the respective 

application must be used and laid professionally, the cross-section must 

be AWG 26 (0.129mm²) or more. To increase transmission reliability, it is 

recommended to use shielded bus cables twisted in pairs.

Cable lengths (without repeater)

A maximum cable length depends on the baud rate:
-at a baud rate of 9600 bits/s (factory setting), up to 1000m

physical interface

RS-485 with bus connector; connection can be mounted by the 

customer, 2-wire and has a 2-screw terminal

Addressings

1 ... 247; the following must be observed:  

32 devices in one segment, expandable to 247 with repeater, incl. 

client, where address 0 goes as broadcast message to all servers

.

Note: 

 

The respective applicable regulations and standards must be taken into account for laying bus cables 

inside buildings (inside/outside cabinets), laying cables outside buildings, potential equalisation, 

minimum distances (such as measures against interference voltages), shielding of cables (e.g. shield 

connection after expected interference) as well as installation of terminating resistors! 

When laying shielded cables, the shield may only be connected to ground at one point! 

Work on electrical equipment and connection work is only permitted for authorised and qualified 

electricians. The VDE guidelines and the provisions of the responsible energy utility company must 

be observed.

The LogoTronic Hub OTC operates with mains voltage. Therefore, always ensure the system is 

disconnected from the mains supply when carrying out any maintenance or repair work and secure 

it against unauthorised activation 

 

7.2  Modbus for LogoTronic Hub OTC and HIU controllers 

These chapters describe the Modbus communication via RS-485 interface with the LogoTronic 

controller for electronically controlled interface stations (HIU) that are prepared for communication 

via the Modbus RTU client/server protocol.

The Modbus interface offers the following possibilities:

 •

User interface with restricted data access to registers

 •

Client-server communication between HIU controllers (passing on temperature values), whereby 

they form a closed BUS system!

Содержание Logotherm LogoTronic Hub OTC

Страница 1: ...www flamcogroup com manuals Logotherm LogoT ronic Hub OTC ENG Operating instructions for communication with LogoTronic controllers for electronically controlled interface stations HIU...

Страница 2: ...eat Interface Unit interface station RL Heating circuit return line FL Heating circuit flow line FLA Flashing BT Wireless data transmission FW Firmware CW Domestic water cold RTU Remote Terminal Unit...

Страница 3: ...Keys A and B components 10 6 1 2 LED displays 1 5 11 7 LogoTronic Hub OTC functions 12 7 1 Modbus General overview 12 7 1 1 Remote Terminal Unit RTU mode 12 7 1 2 Protocol configuration 13 7 1 2 1 Uni...

Страница 4: ...scribed in the Technical data section You must also observe the relevant accident prevention regulations the regulations of the electrical engineering association and your local energy supply company...

Страница 5: ...t have read and understood the instructions The installer must explain all the relevant functions to the operator The housing must be intact and sealed prior to operation 1 3 Warranty and liability Th...

Страница 6: ...storage 0 C 70 C no condensation permitted Housing 3 part plastic polycarbonate ABS Dimensions 250 mm x 175 mm x 48 mm Display 5 LEDs Operation 2 buttons for service personnel 2 2 About the LogoTroni...

Страница 7: ...2 on the inner cover plate to the right of the fuse holder and the word FUSE a sticker with the inscription 2A T see figure 3 Installation The LogoTronic Hub OTC is supplied with a mains power cable...

Страница 8: ...adapters for flashing and configuring GND 24V DC RS485 B RS485 A Note The connectors are labelled on the cover plate The connection cables for this must be assembled on site for connecting the RS 485...

Страница 9: ...is Glass fuse 5x 20 mm Fuses may be changed only by specialist personnel once the equipment has been disconnected from mains power 6 LogoTronic Hub OTC operation 6 1 Configuration shown without front...

Страница 10: ...ress and let go All states not booting Launches saving of the transfer log onto a USB stick State Press and hold for a sustained period Run Test Activates test run mode Press and hold Test Launches wi...

Страница 11: ...atus of the LogoTronic controller in normal operating mode Status changes and LED indicators LEDs 1 2 3 4 5 Possible display Green On Off Flashing FLS FLF Green On Off Flashing FLS FLF Green On Off Fl...

Страница 12: ...pen protocol that can be used free of charge for commercial applications One client and up to 247 servers are possible in a Modbus network The protocol uses for example the RS 485 interface for data t...

Страница 13: ...t byte contains the device address Client and server devices continuously monitor the network even during a silent interval After the last transmitted byte a silent interval of at least 3 5 characters...

Страница 14: ...onal value is no longer required The scaling factor to be applied can be taken from a corresponding table 7 1 2 4 CRC The CRC is a 16 bit value that is appended to the message It is used to determine...

Страница 15: ...dings inside outside cabinets laying cables outside buildings potential equalisation minimum distances such as measures against interference voltages shielding of cables e g shield connection after ex...

Страница 16: ...ocols are available on the RS 485 interface Currently the HFC protocol manufacturer s own and the open Modbus protocol are available The protocol used on the RS 485 can be changed using the keys on th...

Страница 17: ...ality is ModbusClientX https sourceforge net projects modbusclientx modbus tool 7 2 3 RS 485 interface settings notes for system integrators The factory settings of the Modbus interface are set to 8 N...

Страница 18: ...0x02 Dates 2 Byte counter 6 0x08 Dates 2270 Value 22 7C 0xDE Dates 7 0x62 CRC check 25320 Checksum 0xE8 CRC check Received broadcast telegram Server Telegram Hex RTU structure Value Description 1 0x00...

Страница 19: ...ent server interconnection options in the Modbus network 1 2 Legend C Client LogoTronic Hub OTC S1 Sn Server LogoTronic controller for electronically controlled interface stations HIU AT Outside tempe...

Страница 20: ...oneywell AF10 B65 Operating range 40 70 C IP54 Art no M10560 53 for a spare parts case Warning The use of outside temperature sensors with other temperature characteristics such as PT1000 is not possi...

Страница 21: ...We reserve the right to change designs and technical specifications of our products 21 ENG...

Страница 22: ...Manual LogoTronic Hub OTC 22...

Страница 23: ...We reserve the right to change designs and technical specifications of our products 23 ENG...

Страница 24: ...No part of this publication may be reproduced or published in any way without explicit permission and mention of the source The data listed are solely applicable to Flamco products Flamco B V shall a...

Отзывы: