background image

19

18

The HIU is equipped with an electric connection box that converts the 230VAC 

power supply to 24 VDC and powers the equipped SH pump and optional 

DHW pump. It also houses the fuse of the unit.

CAUTION!

The HIU uses electrical component (230VAC and 24VDC). Touching these 

components can result in an electrical shock, burn, or electrocution. The 

casing shall only be opened by authorised personnel when the power supply 

$.0/*Ȃѵ

1.  230VAC fuse (3A)

2.  230VAC connection to circuit breaker or power switch

3.  230VAC DHW circulation pump connection

4.  230VAC SH pump connection

5.  24VDC connection to electronic regulator PCB

6.  LED status indicator pump relay (ON = SH pump active)

7.  LED status indicator 24V (ON = 24V directed to regulator PCB) 

8.  WAGO connector, connecting all protective earth cables

7.4 Power supply

7. Service

1

2

3

4

5

6 7

8

insulated

230 V

230 V

Cable colours

The electronics housing is separated into a 230VAC area 

and a 24VDC area. By default the following cable colours 

are used:

CAUTION!

230VAC area 

  - Live 230VAC 

Brown 

 - 

Neutral 

Blue 

  - Protective earth Green/Yellow

24VDC area 

 - 

24VDC 

Black 

 - 

Ground 

Brown 

  - Signal wire 

Grey

7.5 Commissioning

Follow the steps shown below to commission the HIU. If leakage or other faults should occur, go to chapter “Troubleshoot”.

7. Service

CAUTION!

Parts and components may be hot or energized. 

Contact may lead to shock, burn or electrocution.

1.  Close all valves

2.  Check all nuts for leakage. (nuts may become loose 

during transport)

3.  Make sure the electronics are securely mounted to 

the frame and avoid cables from blocking the casing.

4.  Make sure that the power supply is switched 

*Ȃѵ*)) //# 0)$/ҁ.+*2 -' .җрҘ/*/#

power switch. 

  +/# +*2 -.2$/#*ȂѶ0)/$'

further notice below.

 The power switch must be 

permanently connected, suitably located and easily 

reached. Also see chapter “Installation requirements” 

Blue cable: 

N (neutral) 

Brown cable:  L (Live 230VAC) 

Green/yellow:  PE (protective earth)

5.  Open the domestic potable water valves (D&C) to 

pressurise the unit and check for leakage.

6.  Switch on the power to the unit. The LED should 

show a green blinking light (2).

7.  Open the DH valve (A) and check for leakage.

8.  Open the DH return valve (B) and check for leakage.

9.  Open the valve (E).

10. Open the SH return valve (F).

11. 

/-/'  $)"/#  $-0$/.//# /*+ޕ**-)

work the way down. (see also chapter “Bleeding the 

air”)

12. Check to see if the heating warms up.

13. It is possible to set the pump setting to optimise the 

SH system. See chapter “Pump settings”.

14. Completely open a DHW outlet (tap or shower). 

Check to see if the unit’s LED shows a blue blinking 

light (2). 

Leave it running for approximately 5 minutes.  

Check if the DHW temperature has reached its set 

point (default 55ºC) between 3 and 5 minutes.

15. Close all DHW outlets. The LED will now show a 

green blinking light (2).

1

2

Status Indicator LED

A

B

E

F

D

C

Содержание logoEco A2RXE

Страница 1: ...GB Technical information for installation and operation LogoEco Heat Interface Unit HIU A2RXE Instantaneous Hot Water Space Heating...

Страница 2: ...hoot technician 25 8 Appendix A 27 Appendix B 31 Appendix C 32 Contents Symbols and abbreviations Symbols Abbreviations CAUTION general safety remark CAUTION risk of shock CAUTION hot surfaces risk of...

Страница 3: ...ater temperature This may lead to a domestic hot water temperature that is higher or lower than its set point Hot water can cause burns 1 3 Priority switching 2 4 2 2 2 1 2 0 water If there is a power...

Страница 4: ...purpose it is advised to design the SH circuit in such a way that the SH return temperatures are as low as possible Keep following condition in mind during installation 4 2 0 0 4 2 General Plumbing R...

Страница 5: ...orrect current or overcurrent The circuit breaker must have a contact separation of at least 3mm in all poles and should isolate the appliance and all associated controls The HIU must at all times be...

Страница 6: ...P1 Description Type District heating station for indirect heating and instantaneous domestic hot water Mounting Wall mounted Dimensions 490 x 275 x 640 mm WxDxH height of the case Heating System 2 Con...

Страница 7: ...on make sure that there is a board installed e g plywood min 18mm to support the structure which is strong enough to hold the HIU Use a 4mm drill bit at least 40mm depth for the wall plugs If the wall...

Страница 8: ...may be hot or energized Contact may lead to shock burn or electrocution 1 Disconnect the HIU from the mains power 2 Open all space heating circuits in the property Turn the room thermostat and all ra...

Страница 9: ...un quietly without any air noise 5 0 0 its operating mode setting 0 4 0 the automatic air vent anti clockwise Turn on the circulation pump and let it run until all air 1 0 the pump setting and close t...

Страница 10: ...ice CAUTION Parts and components may be hot or energized Contact may lead to shock burn or electrocution 1 Close all valves 2 Check all nuts for leakage nuts may become loose during transport 3 Make s...

Страница 11: ...n the table below Settings You can choose between the performance view and settings view If you press the push button for 2 to 10 seconds the user interface switches to select selection if the user in...

Страница 12: ...procedure needs to be repeated Problem Cause Solution Pump not running Not connected or connected correctly Connect correctly Pump too hot dry operation or overheating protection active Allow pump to...

Страница 13: ...e electronics Contact your supplier 0 Tap is opened unit is in tapping operation Close Tap Sensor s are not connected or bad contact Check wire tree connections and connect the sensors properly then r...

Страница 14: ...e a light humming sound Rattling sound Flow sensor not installed correctly 2 4 Other defects Contact your supplier Guidelines for System Conditioning of Heating and Cooling Networks for Flamco Limited...

Страница 15: ...mendations and in accordance with BSRIA BG29 2012 0 0 0 1 4 0 0 for HIU must comply with EU norms DIN EN 12828 and current guidelines for heating systems In addition they should also be non hazardous...

Страница 16: ...tor of possible corrosion Chemical assessment PH value hardness precipitate composition and concentration of chemical treatment and type of treatment contained within the water A UKAS registered lab i...

Страница 17: ...8 Bleed point G 1 8 BT 19 Water hammer arrester G 3 4 WM x G 3 4 BT l 84 5 21 Flow sensor SIKA 22 Non return valve 24 circulation pump DHW Lowara 25 circulation pump space heating Grundfos UPM3 AUTO 1...

Страница 18: ...35 34 Contact Notes United Kingdom Flamco Limited Washway Lane St Helens Merseyside WA10 6PB United Kingdom 44 1744 744 744 0 222 0...

Страница 19: ...Flamco Limited Washway Lane WA10 6PB St Helens Merseyside United Kingdom T 44 17 447 447 44 F 44 17 447 447 00 E 0 222 0 0 0...

Отзывы: