3.3
Working principle
The automat is installed to the heating or air conditioning system as well as to a supply, e.g. drinking water net.
The automat compensates losses of system water automatically by the refill process. The refill process can be:
pressure controled;
•
level controled.
•
P
G
J
I
E
F
D
B
C
A
H
Types of control:
Pressure controled:
The system pressure is monitored by the pressure
sensor (B). When the pressure is below a certain
value the controller (F) switches ON the pump
(D). The pump wil refill the system with water
that is stored in a breaktank. The controller will
switch OFF the pump after an adjustable pressure
difference is reached. The refill time and -amount
is protected and can be adjusted as welI.
Level-controlled:
The breaktank uses a float switch to maintain its
capacity. The breaktank has a overflow protection
(G) and a run-dry sensor (E) to maintain a safe
water level of breaktank. The impuls water
counter gives information about the amount of
water that is refilled in total.
No.
Description
1
Control panel for the controller, graphical display,
LED for error display, selector switch (click and
roll)
2
Power switch, ON: flashes red
3
Internal fuse F1: T 16 A 250 V
4
Internal fuse F2: T 3,5 A 250 V
5
Hardware release, service menu E2
6
Terminal bars for
Electric supply;
•
sensors;
•
Impulse water counter;
•
External activation for refilling process;
•
Collective malfunction message;
•
Pump;
•
7
Interface RS485.