FLAMCO-FILL PE INSTALLATION AND OPERATING INSTRUCTIONS
TP.04/02/09.EN
Edition 2009 / EXP
A:
Necessary, reset possible within normal use (control restarts after resetting).
B:
No duty, automatic reset within normal use.
Nr.
Message
Description
Reset
Possible cause
Troubleshooting
14
Filling amount
exceeded
Max. initial filling amount in filling
mode exceeded.
A
• Leakage in the system.
• System not sufficiently filled, yet.
• Solve leakage.
• Check adjusted value.
• Re-activate filling mode.
15
Filling time excee-
ded
Max. initial filling time in filling mode
exceeded.
A
• Leakage in the system.
• System not sufficiently filled, yet.
• Solve leakage.
• Check adjusted value.
• Re-activate filling mode.
16
Change module
Amount of the water treatment
module exceeded.
A
Module capacity of the water treatment
exhausted.
Change module.
17
Voltage sensor
Minimum sensor voltage below limit.
B
Blank defective.
Change controller when repetitive.
18
Short circuit of
pressure sensor
Short circuit current loop pressure
sensor.
A
Short circuit.
Check the electrical joints and cables.
19
Cable break of
pressure sensor
Interruption current loop pressure
sensor.
A
Cable break.
Check the electrical joints and cables.
20
No date/time
Real time clock has no valid time
information.
A
Time adjustment deleted after longer
dead-voltage condition.
Adjust time and date.
25
Maintenance date
Maintenance date reached.
A
Maintenance required.
Perform maintenance and confirm in
service menu.