STRA-14 Room controller. Installation and maintenance manual.

Fläkt Woods

8710 GB 2016.09.08

5 (12)

Specifications are subject of alteration without further notice.

Operating modes

STRA-14 has five different operating modes. Through

the Function button you are able to switch between three

of them. These are set through the parameter menu

(parameter 45) in the display. Occupied is the preset

mode.

Off

Operating mode Off means that the controller is switched

off, i.e. heating and cooling are disabled. However,

the temperature may not drop below the set minimum

temperature (parameter 6, FS = 8°C). If it does, the

controller will start heating. The background lighting

on the display is not lit, and only OFF is shown in the

display.
Nozzle setting for the airflow is according to Energy

Saving mode (Parameter 306).
Display: The background lighting is not lit, and only OFF

is shown in the display.

Unoccupied (Energy Saving Mode)

Operating mode Unoccupied is an energy saving mode. It

means that the room where the controller is placed is not

used for an extended period of time, for example during

evenings, nights or weekends. The controller is prepared

to change the operating mode to Occupied if someone

enters the room (presence). Both heating and cooling are

disabled within a temperature interval with configurable

min/max temperatures (parameter 4 respectively 5, FS

min = 19°C, max = 27°C).
Nozzle setting for the airflow is according to Energy

Saving mode (Parameter 306) but is increased step by step

if the cooling water valve is fully open and there is still a

need for increased cooling.
The background lighting on the display is not lit, but the

current room temperature (or setpoint value depending

on the configuration) is shown in the display. OFF is

shown in the display for this operating mode as well.

Standby (Energy Saving Mode) STELLA,

WEGA and NOVA

Operating mode Stand-by means that the room is in

an energy saving mode and is not used at the moment.

This can be during evenings, nights, weekends etc. The

room temperature is controlled around the applicable

heating and cooling setpoint values, with an extended

temperature interval (FS = +/-3°C).
Nozzle setting for the airflow is according to Energy

Saving mode (Parameter 306) but is increased step by step

if the cooling water valve is fully open and there is still a

need for increased cooling.
For example, if the heating setpoint value is 22°C and the

cooling setpoint value is 24°C, the controller will allow

the temperature in the room to be between 19°C and 27°C.

Local adjustment of setpoint value via the display on

STRA-14.
The background lighting on the display is lit (dimmed)

and STANDBY with the current room temperature (or

setpoint value depending on the configuration) are shown

in the display. Learn more in section Occupancy detector.

Occupied (Normal Mode)

Operating mode Occupied means that the room is in

use and is therefore in a comfort mode. The controller

regulates the room temperature around a heating

setpoint value and a cooling setpoint value (parameter 1

respectively 2, FI heating setpoint value = 22°C, cooling

setpoint value = 24°C). Nozzle setting for the airflow

is according to Normal mode (parameter 307) but is

increased step by step if the cooling water valve is fully

open and there is still a need for increased cooling. The

setpoint values can also be ad/-3°C locally via the

display, or via a central command.
The background lighting on the display is lit (dimmed),

and the occupancy indication is shown (see the Display

handling section). The current room temperature (or

setpoint value depending on the configuration) is shown

in the display.

Bypass (Boost Mode) STELLA, WEGA and

NOVA

Operating mode Bypass means that the controller controls

the room temperature in the same way as in operating

mode Occupied. For the chilled beam this activates the

output for forced ventilation and the air flow goes to a

predetermined maximum position (parameter 308). After

a configurable time (parameter 12, FS = 60 minutes) the

controller automatically returns to the preset operating

mode. Boost is normally activated when the Occupancy

button is pressed or a central command. The operating

mode is useful for example in conference rooms, where

many people are present at the same time during a

limited period of time.
The background lighting on the display is lit (dimmed).

The occupancy indication and the symbol for forced

ventilation are shown (see the Display handling section

on page 3). The current room temperature (or setpoint

value depending on the configuration) is shown in the

display.

Activation of operating modes

Preset operating mode

Occupied is the preset operating mode. Configuration of

desired operating mode is done in the parameter menu

on the display (parameter 45). The operating mode is

changed at following events:
• When the Occupancy button is pressed
• Activation/deactivation of an occupancy detector
• Via central control, for example central time control,

central booking system etc.

Содержание STRA-14

Страница 1: ...or no parity Communication speed 9600 bps not changeable Built in temperature sensor NTC type measuring range 0 50 C accuracy 0 5 C at 15 30 C Material casing Polycarbonate PC Weight 110 g This produ...

Страница 2: ...ecifications are subject of alteration without further notice Installation instructions Ensure that the installation complies with local safety regulations Information about commissioning of the produ...

Страница 3: ...cooling setpoints is done automatically in the controller depending on the heating and cooling requirement Display handling The display has the following indications Function button By pressing the Fu...

Страница 4: ...lve actuator max 5 mA The valve actuator s 0 10 V control signal terminal is connected to terminal 23 and its supply terminals to terminals 10 and 11 Make sure that the reference pole G0 is connected...

Страница 5: ...e is 22 C and the cooling setpoint value is 24 C the controller will allow the temperature in the room to be between 19 C and 27 C Local adjustment of setpoint value via the display on STRA 14 The bac...

Страница 6: ...ed operating mode to attain energy efficiency Control states The controllers can be configured for different control states control sequences Parameter 11 FI 4 Heating Cooling with VAV control with fo...

Страница 7: ...s air cooling and 51 100 is water cooling This is adjusted by changing the parameter 309 309 0 Free cooling off Water cooling 0 50 and 51 100 air cooling 309 1 Free cooling on Air cooling 0 50 and 51...

Страница 8: ...prevents the temperature from dropping below 8 C Return to normal fan speed and control occurs automatically when the room temperature exceeds 8 C Control the light with an occupancy sensor It s possi...

Страница 9: ...ng 1 2 3 4 5 6 STELLA 0 23 40 59 75 100 WEGA Standard 0 21 38 56 73 100 WEGA Power 0 23 23 23 23 100 NOVA 0 21 38 56 73 100 Nozzle selection for air flow in Energy Saving Mode and Boost Mode is adjust...

Страница 10: ...10v 1 2 10v 2 10 2v 3 10 0v 0 29 Heating Modulating Actuator Control 0 0 10v 1 2 10v 2 10 2v 3 10 0v 0 30 Cooling Modulating Actuator Control 0 0 10v 1 2 10v 2 10 2v 3 10 0v 0 31 Heating Thermal Actu...

Страница 11: ...or 1 For N O actuator 0 74 HMI Displacement View 0 The offset 1 The active setpoint offset 2 The heating setpoint offset 3 The cooling setpoint offset 4 Occupied Heating Setpoint Offset 5 Occupied Coo...

Страница 12: ...28 Branch Version 129 Revision 300 Voltage x 10 for nozzle 2 21 301 Voltage x 10 for nozzle 3 38 302 Voltage x 10 for nozzle 4 56 303 Voltage x 10 for nozzle 5 73 304 Max air level at 100 cooling 5 30...