STRA-14 Room controller. Installation and maintenance manual.

Fläkt Woods

8710 GB 2016.09.08

4 (12)

Specifications are subject of alteration without further notice.

Wiring

STRA-14 has been constructed to be as compact as possible. Therefore, the controller’s communication input is not

galvanically separated from the supply voltage. This means that it is important to keep G and G0 in order, as well as the

communication input’s A and B.
All units that share the same transformer and communication loop must use the same transformer-pole for G (terminal

10) and G0 (terminal 11). On the communication loop the A-terminal (terminal 42) should only be connected to another

A-terminal and the B-terminal (terminal 43) to another B-terminal. Otherwise, there is great danger of short-circuit with

damaged components as a result.

Terminal

Designation

Operation

10

G

Supply voltage 24 V AC

11

G0

Supply voltage 0 V

12 - 14

No function.

20

GDO

24 V AC out common for DO. Internally connected to terminal 10, G.

21

G0

0 V common for UO. Internally connected to terminal 11, G0.

22

UO3

Control output ventilation.

3 put analog (FS). The valve actuator’s 0…10 V control signal terminal is connected to terminal 22 and its supply

terminals to terminals 10 and 11. Make sure that the reference pole G0 is connected to the correct terminal on

the actuator.

23

UO1

Control of heating.

For 0...10 V DC valve actuator, max 5 mA. The valve actuator’s 0…10 V control signal terminal is connected to

terminal 23 and its supply terminals to terminals 10 and 11. Make sure that the reference pole G0 is connected

to the correct terminal on the actuator.

alternative

For 24 V AC thermal actuator, max 2,0 A (FS). The thermal actuator is connected between terminals 23 and 20,

GDO.

24

UO2

Control output cooling.

For 0...10 V DC valve actuator, max 5 mA. The valve actuator’s 0…10 V control signal terminal is connected to

terminal 24 and its supply terminals to terminals 10 and 11. Make sure that the reference pole G0 is connected

to the correct terminal on the actuator.

alternative

For 24 V AC thermal actuator, max 2,0 A (FS). The thermal actuator is connected between terminals 24 and 20,

GDO.

30

AI1

For external room sensor, PT1000. Measuring range 0...50°C. Sensor is connected between terminals 30 and

41, AGnd.

31

AI2

For 0-10V CO 

2

 sensor input.

32

DI1

Occupancy detector. A potential-free contact is connected between terminals 32 and 40, +C. Closed contact

corresponds to occupancy.

See also section Occupancy detector in the chapter Operating modes.

33

DI2/CI

Fläkt Woods condensation detector STRZ-16 (FS). The sensor is connected between terminals 33 and 41, AGnd.

alternative

Window contact (DI). A potential-free contact is connected between terminals 33 and 40, +C. Closed contact

indicates closed window.

40

+C

24 V DC out common for DI and UI (with digital function)

41

AGnd

Analogue ground, reference for AI and UI (with analogue function)

42

A

RS485-communication A -

43

B

RS485-communication B +

Содержание STRA-14

Страница 1: ...or no parity Communication speed 9600 bps not changeable Built in temperature sensor NTC type measuring range 0 50 C accuracy 0 5 C at 15 30 C Material casing Polycarbonate PC Weight 110 g This produ...

Страница 2: ...ecifications are subject of alteration without further notice Installation instructions Ensure that the installation complies with local safety regulations Information about commissioning of the produ...

Страница 3: ...cooling setpoints is done automatically in the controller depending on the heating and cooling requirement Display handling The display has the following indications Function button By pressing the Fu...

Страница 4: ...lve actuator max 5 mA The valve actuator s 0 10 V control signal terminal is connected to terminal 23 and its supply terminals to terminals 10 and 11 Make sure that the reference pole G0 is connected...

Страница 5: ...e is 22 C and the cooling setpoint value is 24 C the controller will allow the temperature in the room to be between 19 C and 27 C Local adjustment of setpoint value via the display on STRA 14 The bac...

Страница 6: ...ed operating mode to attain energy efficiency Control states The controllers can be configured for different control states control sequences Parameter 11 FI 4 Heating Cooling with VAV control with fo...

Страница 7: ...s air cooling and 51 100 is water cooling This is adjusted by changing the parameter 309 309 0 Free cooling off Water cooling 0 50 and 51 100 air cooling 309 1 Free cooling on Air cooling 0 50 and 51...

Страница 8: ...prevents the temperature from dropping below 8 C Return to normal fan speed and control occurs automatically when the room temperature exceeds 8 C Control the light with an occupancy sensor It s possi...

Страница 9: ...ng 1 2 3 4 5 6 STELLA 0 23 40 59 75 100 WEGA Standard 0 21 38 56 73 100 WEGA Power 0 23 23 23 23 100 NOVA 0 21 38 56 73 100 Nozzle selection for air flow in Energy Saving Mode and Boost Mode is adjust...

Страница 10: ...10v 1 2 10v 2 10 2v 3 10 0v 0 29 Heating Modulating Actuator Control 0 0 10v 1 2 10v 2 10 2v 3 10 0v 0 30 Cooling Modulating Actuator Control 0 0 10v 1 2 10v 2 10 2v 3 10 0v 0 31 Heating Thermal Actu...

Страница 11: ...or 1 For N O actuator 0 74 HMI Displacement View 0 The offset 1 The active setpoint offset 2 The heating setpoint offset 3 The cooling setpoint offset 4 Occupied Heating Setpoint Offset 5 Occupied Coo...

Страница 12: ...28 Branch Version 129 Revision 300 Voltage x 10 for nozzle 2 21 301 Voltage x 10 for nozzle 3 38 302 Voltage x 10 for nozzle 4 56 303 Voltage x 10 for nozzle 5 73 304 Max air level at 100 cooling 5 30...

Отзывы: