Maintenance

FläktGroup 

DC_9202GB   20180403_R0

Specifications are subject to alteration without notice

0

LQLF-11

p

Pa

Pa

Pa

AIR FLOW MEASUREMENT WITH Q-DYSA

®

 AND ANALOGUE FLOW INDICATING INSTRUMENT

Filling screw

Level

Resetting screw

Flow indicating instrument

q-DYSA

®

 flow sensor

CHECKS

The zero setting of the manometer should be checked at regular 
intervals. To check the zero setting, remove the hoses connected 
to the pressure connections of the manometer. Whenever the need 
arises, use the resetting screw to adjust the zero setting. Top up with 
manometer liquid, if required. 

The measurement nozzle should be blown clean with compressed air 
once or twice a year depending on the quality of the air. This can easily 
be done by disconnecting the hoses from the instrument and blowing 
them with compressed air to free the air passages from impurities. 

Another type of pressure gauge may also be connected for use as an 
alternative meter or for checking the performance of the flow indicating 
instrument. In this case, fit T-nipples in the hoses to the indicating 
instrument and connect them to the pressure gauge. The air flow can 
be calculated by the expression:

q =   1  ·   

Δ

p  m

3

/s 

k

  

where the value of k is stated on the unit rating plate and 

Δ

p is the 

measurement pressure in Pa.

AIR FLOW MEASUREMENT WITH Q-DYSA

®

 AND ANALOGUE FLOW INDICATING INSTRUMENT

LQ-

size

1)

 size 2

2)

 size 1,

normal

2)

size 2,

normal

2)

 size 3,

normal

2)

 size 1, 

reinforced

2)

 size 2,

reinforced

2)

 size 3,

reinforced

K-factor m

3

/s at

500 Pa K-factor

m

3

/s at

500 Pa K-factor

m

3

/s at

500 Pa K-factor

m

3

/s at

500 Pa K-factor

m

3

/s at

500 Pa K-factor

m

3

/s at

500 Pa K-factor

m

3

/s at

500 Pa

60

1,4

16,0

1,99

11,24

1,50

14,91

1,35

16,56

2,23

10,03

1,75

12,78

1,35

16,56

62

1,09

20,5

1,50

14,91

1,35

16,56

1,08

20,70

1,75

12,78

1,35

16,56

1,08

20,70

64

0,85

26,3

1,35

16,56

1,08

20,70

0,80

27,95

1,35

16,56

1,08

20,70

0,80

27,95

71

0,85

26,3

1,35

16,56

1,08

20,70

0,80

27,95

1,35

16,56

1,08

20,70

0,80

27,95

73

1,08

20,70

0,80

27,95

0,68

32,88

1,08

20,70

0,80

27,95

0,68

32,88

80

0,85

26,3

1,35

16,56

1,08

20,70

0,80

27,95

1,35

16,56

1,08

20,70

0,80

27,95

82

1,08

20,70

0,80

27,95

0,68

32,88

1,08

20,70

0,80

27,95

0,68

32,88

84

0,80

27,95

0,68

32,88

0,52

43,00

0,80

27,95

0,68

32,88

0,52

43,00

Содержание LQLR

Страница 1: ...LS 3 INSTALLATION OF HABASIT FLAT BELT DRIVE 3 MOVING THE MOTOR TO ADJUST THE BELT TENSION 4 BELT PULLEYS 4 GROOVED BALL BEARINGS WITH TAPER SLEEVE 5 DISMANTLING THE PLUMMER BLOCK WITH BALL BEARING 7...

Страница 2: ...st content the unit should be serviced more frequently Check the belt tension every 6 months The fan is accessible through the inspection door panel IMPORTANT Isolate the power supply and wait until t...

Страница 3: ...easure the longest free measurement distance on the belt to the nearest 100 mm The belt must not be in contact with the pulleys along the measurement distance 6 Remove the belt place it on a flat surf...

Страница 4: ...ny anti corrosion agent and make certain that the surfaces are completely free from oil and dirt Fit the bush into the pulley 2 Oil the screws sparingly and loosely screw them into the tapped holes in...

Страница 5: ...ighten the nut by hand so that the shaft bearing and taper sleeve are firmly in contact with one another 4 Mark one of the tab washer tabs which is in line with a slot in the nut Then tighten the nut...

Страница 6: ...M t ut och markera lagrets l ge p axeln x ___ mm Steg 4 Lossa lagrets f stbultar och l t axeln b ras upp av lyftlinan Sp nn lyftlinan vid behov s att fl kthjulet inte r r inloppskonan Lagret r limmat...

Страница 7: ...toppskruv Steg 5 Lagermonteringen r nu klar Kontrollera att fl kthjulet roterar och utf r slutkontroll Fl kt M Nm Fl ktstorlek 080 090 100 27 27 27 5 3 Fl kthjul 5 3 1 Demontering av fl kthjul storlek...

Страница 8: ...e fit T nipples in the hoses to the indicating instrument and connect them to the pressure gauge The air flow can be calculated by the expression q 1 p m3 s k where the value of k is stated on the uni...

Страница 9: ...asing Screen Casing FREQUENCY CONVERTER Connection of the screening conductor shall be made via an EMC approved union in the frequency converter s casing or by using a clamp intended for this purpose...

Отзывы: