Plug fan GMEC with EC-motor - Operating instructions

8

FläktGroup DC_9942GB_20180604_R0

Specifications are subject to alteration without notice

•  Use a screwdriver to do so. When connecting, ensure that no 

wire ends fan out. 

•  Seal the terminal box.

5.3.2.3 Cable routing 

Water must be prevented from reaching the cable gland along the 
cable. When routing the cable, make sure that the cable glands 
are located at the bottom. The cables must always be routed 
downward.

5.4 FACTORY SETTINGS 

Factory settings made for the device

Parameter

1~230 V

3~400 V

Mode parameter set 1

PWM control

PWM control

Mode parameter set 2

PWM control

PWM control

Fan/device address

01

01

Max. PWM / %

100

100

Min. PWM / %

10

5

Save set value to EEPROM

No

Yes

Set value requirement

Analog (linear)

Analog (linear)

Direction of action  

parameter set 1

Positive

Positive

Direction of action  

parameter set 1

Positive

Positive

5.5 CONNECTION DIAGRAM 

From this table you can see right connection diagram for specific fan.

Fan code

Motor code

Connection diagram

GMEC-3-bb-025-0500 APEC-2-12050-1-2-1

A

GMEC-3-bb-025-0700 APEC-2-12070-1-2-1

A

 

 

 

GMEC-3-bb-028-0500 APEC-2-13050-1-2-1

A

GMEC-3-bb-028-0800 APEC-2-11080-1-2-1

A

GMEC-3-bb-028-1100 APEC-2-11110-3-2-1

B

 

 

 

GMEC-3-bb-031-0500 APEC-2-14050-1-2-1

A

GMEC-3-bb-031-0700 APEC-2-13070-1-2-1

A

GMEC-3-bb-031-1200 APEC-2-12110-3-2-1

B

 

 

 

GMEC-3-bb-035-0700 APEC-2-14070-1-2-1

A

GMEC-3-bb-035-1300 APEC-2-11130-3-2-1

B

GMEC-3-bb-035-2200 APEC-2-12220-3-2-1

D

 

 

 

GMEC-3-bb-040-1300 APEC-2-12130-3-2-1

C

GMEC-3-bb-040-1900 APEC-2-11190-3-2-1

D

GMEC-3-bb-040-2900 APEC-2-11290-3-2-1

D

 

 

 

GMEC-3-bb-045-1300 APEC-2-13130-3-2-1

C

GMEC-3-bb-045-2200 APEC-2-11220-3-2-1

D

 

 

 

GMEC-3-bb-050-1800 APEC-2-11180-3-2-1

D

GMEC-3-bb-050-3400 APEC-2-11340-3-2-1

E

GMEC-3-bb-050-4500 APEC-2-11450-3-2-1

D

 

 

 

GMEC-3-00-056-3200 APEC-2-11320-3-2-1

E

GMEC-3-00-056-4900 APEC-2-11490-3-2-1

D

5.2.4 Residual current circuit breaker (RCCB) 

 Only universal residual current devices (type B or 
B+) are allowed. As with variable frequency drives, 
residual current devices cannot provide personal 
safety while operating the device. When the de-

vice’s power supply is switched on, pulsed charging currents 
from the capacitors in the integrated EMC filter can lead to the 
residual current devices tripping without delay. We recommend 
the use of residual current circuit breakers with a trip threshold of 
300 mA and delayed tripping (super-resistant, characteristic K). 

5.2.5 Leakage current 

 For asymmetrical power systems or if a phase 
fails, the leakage current can increase to a multiple 
of the nominal value. 

5.2.6 Locked-rotor protection 

 Due to the locked-rotor protection, the starting cur-
rent (LRA) is equal to or less than the nominal cur-
rent (FLA).

5.3 CONNECTIONS

5.3.1 Connection the cables to external terminal box

External terminal box doesn’t include in scope of delivery.
First connect the “PE” (protective earth) Connect the cables ac-
cording to your application. When doing so, observe Chapter 5.5 
Connection diagram.

5.3.2 Connection in motor terminal box 
5.3.2.1 PREPARING CABLES FOR CONNECTION 

Only strip the cable as far as necessary, ensuring that the cable 
gland is sealed and there is no strain on the connections. For 
tightening torques, see Chapter 5.5 Connection diagram. 

 NOTE 

Tightness and strain relief are dependent on the 
cable used. 
•  This must be checked by the user. 

5.3.2.2 CONNECTING WIRES TO TERMINALS 

WARNING Live terminals and connections even with device 

switched off  - Electric shock

 

•  Wait five minutes after disconnecting the voltage at all poles 

before opening the device.

•  Remove the cap from the cable gland. Only remove caps 

where cables are fed in.

•  Equip the cable glands with the seals provided in the terminal 

box.

•  Route the wire(s) (not included in scope of delivery) into the 

terminal box. ; First connect the “PE” (protective earth). 

•  Connect the wires to the corresponding terminals.

Содержание CENTRIFLOW 3D PLUG FAN GMEC

Страница 1: ...TRUCTIONS CENTRIFLOW 3D PLUG FAN GMEC CENTRIFLOW 3D PLUG FAN WITH EC MOTOR CONTENT PAGE 1 Introduction 2 2 Safety regulations and information 2 3 Intended use 4 4 Technical data 5 5 Connection and sta...

Страница 2: ...es a potentially hazardous situation which can result in mi nor or moderate injury or damage to property if the specified ac tions are not taken NOTE A potentially harmful situation can occur and if n...

Страница 3: ...on rotating parts Protect long hair with a cap WARNING Ejected parts If the motor is operated with attached fan blades missing protec tive devices may allow balancing weights or broken fan blades to b...

Страница 4: ...nsport and storage conditions and Chapter 4 1 Nominal data Operating the device with all protective devices Following the operating instructions IMPROPER USE In particular operating the device in the...

Страница 5: ...A Output 20 V DC max 50 mA Output for slave 0 10 V Input for sensor 0 10 V or 4 20mA External 24 V input parameter setting External 24 V input parameter setting External 24 V input parameter setting E...

Страница 6: ...Ssc value that is greater than or equal to 120 times the rated output of the arrangement 5 CONNECTION AND STARTUP 5 1 MECHANICAL CONNECTION WARNING Hot motor housing Risk of fire Ensure that no combu...

Страница 7: ...th motors included cables when routing these cables For permanently installed lines the bending radius must be at least four times the outside diameter of the cable For movable lines the bending radiu...

Страница 8: ...00 056 4900 APEC 2 11490 3 2 1 D 5 2 4 Residual current circuit breaker RCCB Only universal residual current devices type B or B are allowed As with variable frequency drives residual current devices...

Страница 9: ...Hz PE NC ALARM RELAY NC 2A 250 VAC MODBUS Potentiometer 10 k 0 1V stop 1 10V min max speed COM RSB RSA 10V 0 10V GND Blue EC motor 1 230V Black 1 Black 2 Black 3 Yellow Green White 1 White 2 Brown Wh...

Страница 10: ...relay floating status contact common con nection contact rating 250 VAC 2A AC1 min 10 mA reinforced insulation on supply side and basic insulation on control interface side GND Reference ground for co...

Страница 11: ...e g sensors SELV KL3 Ain2 I Analog input 2 measured value 4 20 mA Ri 100 k adjustable curve only usable as alternative to input Ain2U SELV KL3 Aout Analog output 0 10 VDC max 5 mA output of current m...

Страница 12: ...are functional Check the fan s air flow paths for foreign matter and remove any foreign matter found Apply the nominal supply voltage Start the device by changing the input signal 5 8 SWITCHING OFF TH...

Страница 13: ...by applying a control signal of 0 5 V to Din1 or by shorting Din1 to GND models with aluminum terminal box only Impermissible point of operation e g back pressure too high Correct the operating point...

Страница 14: ...uring cleaning Malfunction possible Do not clean the device using a high pressure cleaner Do not use acid alkali or solvent based cleaning agents Do not use any pointed or sharp edged objects for clea...

Страница 15: ......

Страница 16: ...ND RELIABILITY With more than a century of accumulated industry experience Fl ktGroup is in a unique position to deliver energy efficient components and solutions for inte grated performance reliabili...

Отзывы: