Air Heating unit ACJB - Technical manual
13
FläktGroup DC_9170GB_20190117_R2
We reserve the right to make changes without prior notice
ELECTRIC HEATER 3 + 3 kW
Parameter
Function
Setting
Factory setting
1
Setpoint value supply air °C
10–30
20
2
Current temperature supply air °C
Display
3
Current temperature secondary air °C
Display
4
Summer mode 0=no 1-255=number of hrs before acti-
vation
0–255
0
5
Adjustment MIN speed in %
40–60
40
6
Adjustment MAX speed in %
40–100
100
7
Filter alarm 1=Yes 2=No
1–2
1
8
Plateau time in minutes before changing the fan speed
and heat output
0–255
30
9
Internal function
–
–
10
P-band multiplier
1–255
8
11
Int action time 1=5min
1–255
10
12
Current register value
Display
13
Current bit information
Display
WATER HEATER
Parameter
Function
Setting
Factory setting
1
Setpoint value supply air °C
10–30
20
2
Filter alarm 1=Yes 2=No
1–2
1
3
Adjustment MIN speed in %
40–100
40
4
Adjustment MAX speed in %
40–100
100
5
Current temperature supply air °C
Display
6
Current temperature extract air °C
Display
7
P-band multiplier
1–255
8
8
Int .action time 1=5 min.
1–255
10
9
P-band VA multiplier (not used)
1–255
8
10
Int. action time VA 1=5 min. (not used)
1–255
10
11
Range
0–200
100
12
Plateau time in minutes before changing the fan speed
and heat output
0–255
30
13
Summer mode (not used)
0–255
14
Control type electric/water (not used)
PARAMETER LISTS