EU Air Handling Unit
MAINTENANCE
EUQA Humidifier, for circulated water
To shut down the humidifier
A. Switch off the power supply.
B. Stop any fans that might be running.
Cleaning or replacing the humidifier fills and
droplet eliminator
A. Switch off the humidifier.
B. Open the inspection door.
C. Remove the side wall as shown in Fig. 9.
D. Withdraw the droplet eliminators and the humidifier
fills straight out of the humidifier as shown in Fig. 9.
Important!
The innermost fills can be reached by carefully step-
ping on the edge of the water tray. Don't step on the
guide rails or on the bottom of the water tray.
E. The fills are relatively delicate and should therefore be
treated with great care. Clean by spraying with a jet of
clean water, possibly containing some ULCZ-01 clea-
ning agent. When replacing the humidifier fills, see
the appropriate instructions supplied with the new
fills.
F. Refit the components in the reverse order.
G. Check the position of the side wall and close the
inspection door.
To clean the water tray
A. Switch off the humidifier.
B. Remove the humidifier fills and the droplet elimina-
tors.
C. Manually open the drain valve to empty the water
tray.
Important!
Don't step on the bottom of the water tray or on the
guide rails.
D. The water tray is now accessible and can easily be cle-
aned by flushing with the hose supplied.
E. Refit the components in the reverse order.
F. Check the position of the side wall and close the
inspection door.