EU Air Handling Unit

MAINTENANCE

EUQA Humidifier, for circulated water

Chart 1

Zone 1 is the safe zone, in which the water is soft or
demineralized.
Zone 2 is the lower part of the transition zone, in which
the water can be said to be of normal drinking quality.
Zone 3 is the upper part of the transition zone, in which
the water is relatively hard.
Zone 4 is the precipitation zone, in which the water is
very hard. The water must be subjected to partial softe-
ning, so that its quality will be within zone 2–3.
However, the softening treatment must not lower the
quality of the water to zone 1.

Example
Data from the municipal water authority:
pH = 7.6
Bicarbonate

70 mg/l

Calcium

30 mg/l

From Chart 1, the operating point is in zone 1 (safe
zone).

Water consumption

The water consumption consists of the water evaporated

and a certain amount of water bleed-off. This bleed-off

flow is necessary to reduce the consumption of salts in

the circulating water. If the concentration of salts is too

high, salts may be deposited on the humidifier fill, which

will have a detrimental effect on the performance of the

humidifier.

The chart above can be used to determine the appropria-

te bleed-off flow.

If the humidifier has been sized for running over a long

period at a high humidification rate

x above 8 grams per kg of air (90% humidifier) and

x above 5 grams per kg of air (60% humidifier) respec-

tively is recommended if the water tray is emptied and

flushed twice a day. (See: To set the timer for emptying

and flushing.)

Periods out of service

The controller of the humidifier switches to the empty-

ing mode whenever the fan is switched out.

Clean the water tray if the system is to be shut down

for an extended period, such as during the annual holiday

and long weekends.

If the humidifier is to be out of service for some time,

the humidifier fills should be removed, cleaned and sto-

red in a place where they will not sustain damage.

10

10 000

6000

2000

4000

1000

600

400
200

100

60
40

20

10

6
4

2

1

5

6

7

8

9

8,5

9,5

4

2

6

20 40 60 100

1000

10 000

Calcium Ca

2+ 

mg/l

pH-value

Max. pH of aluminium

Bikarbonate HCO

3

mg/l

Precipitation zone

Transition zone

Safe zone

Содержание EUQA

Страница 1: ...assified If the water is of zone 4 type it should be softened Level monitors fig 2 Level monitor A Closes the water supply valve when the water reaches max level A Setting A 25 mm from the upper edge of the water tray sizes 20 53 65 mm from the upper edge of the water tray sizes 60 84 Level monitor B Opens the drain valve for water bleed off Setting B The zone value obtained see page 5 determines ...

Страница 2: ...pening the drain valve approx half way 45 see Fig 3 The valve can be reclosed by pressing a reset button on the control unit When the water level has dropped below the lowest point of sensor B the drain valve should open fully If the water level continues to drop below the lowest point of sensor C water inlet valve should begin to open and after a preset period see Table 2 Fig 6 the drain valve sh...

Страница 3: ...5 12 M A1 15 B1 A2 18 16 Rel Power TR1 Fig 6 Table 3 Presetting time relay TR1 Seconds Range Time 0 1 s 0 10 10 s 10 red 20 30 s 20 black 30 30 s 30 black 40 100 s 4 red 50 100 s 5 red 60 100 s 6 red 70 100 s 7 red 80 100 s 8 red 90 100 s 9 red 100 100 s 10 red 120 300 s 12 black 180 300 s 18 black 240 300 s 24 black 300 300 s 30 black Q1 K1 R1 NR3 NR2 NR1 TR1 Fig 7 Components inside the control b...

Страница 4: ...ost easily by programming the opera tion times from 12 15 to 12 00 and from 12 10 to 12 12 on a daily basis Emptying and additional emptying will then occur from 12 00 to 12 10 and from 12 12 to 12 15 respectively Water quality Evaporation causes an increase in the concentration of minerals in the circulating water which necessitates continuous bleed off and make up with fresh water The bleed off ...

Страница 5: ... the time zone where it is to be used Display of special functions Manual operation Permanent ON OFF Symbols which indicate summer winter function Summer Winter The numbers under the display indicate days of the week 1 Monday 2 Tuesday etc Choice Yes means choice of programming Choice No means continue Day by day summary of the programmed connection times Example 5 Friday Duct status ON On OFF OFF...

Страница 6: ... If the concentration of salts is too high salts may be deposited on the humidifier fill which will have a detrimental effect on the performance of the humidifier The chart above can be used to determine the appropria te bleed off flow If the humidifier has been sized for running over a long period at a high humidification rate x above 8 grams per kg of air 90 humidifier and x above 5 grams per kg...

Страница 7: ...tom of the water tray E The fills are relatively delicate and should therefore be treated with great care Clean by spraying with a jet of clean water possibly containing some ULCZ 01 clea ning agent When replacing the humidifier fills see the appropriate instructions supplied with the new fills F Refit the components in the reverse order G Check the position of the side wall and close the inspecti...

Страница 8: ...operation when the tray is dry NR2 A B3 B2 16 B1 A1 A2 17 A2 A1 B1 B2 B3 B NR3 Maintains correct level 4 B1 A2 A1 TR1 Delayed closure SV1 TR1 15 16 18 R1 11 12 14 R1 21 22 24 R1 31 32 34 1 2 3 4 5 G G 7 8 6 Control box on outside Control box on inside 1 3 5 2 4 6 W U V 3 M 6 4 2 3 5 1 I I I K2 A1 A2 Contactor CP2 Humidity control Interlock Wiring diagram Service intervals Component Service work In...

Отзывы: