Installation and Maintenance Instructions
Operating and Care
Description
The cooling unit is a part of the air handling unit and
should be installed as a module in the EU air handling
unit.
The cooling unit operates independently and has its
own cubicle; however cooling capacity must be swit-
ched in according to signals from the air handling unit.
The cooling unit is designed for cooling the supply air in
the temperature range of b20 – +32 °C. It is
possible to lower the supply air temperature by 9 – 16 °C
depending on the selected capacity variant, air tempe-
ratures and air volume ratio: supply air/extract air.
Use
An electric equipment cubicle is installed in the service
section of the cooling unit. The cubicle contains mainly
the following items of equipment:
– Main switch
– Control circuit fuse
– Protective motor switch
– Control unit with display
Refrigerant tank
Component description
Control unit (RC1)
The control unit is located in the door of the cubicle.
See the description on page 9.
Control circuit fuse
To reset the miniature circuit breaker, pull the black
actuator button upward.
Main switch
Use the main switch for switching the cooling unit
on/off. Always switch off the main switch on the
cooling unit and lock it in position before beginning
work! Certain wiring terminals can be energized despi-
te the fact that the switch is switched off, for example
terminals for group alarm outputs.
EQKA Cooling unit
Warning!
The refrigerant tank is intended for
use as a ”passive” container only, i.e.
it must
NOT
be connected while the
unit is normally operating. (Applies
to units with refrigerant tank).
Important!
Always study the safety directions on
page 2 before beginning all work!
Warning!
The control circuit fuse does
NOT
switch off the voltage to the entire
cooling unit! Always open the main
switch on the cooling unit and lock it
in position!