10.3 Diagnostic Chart
10.3.1 After energizing, no indicator is lighted and the air conditioner can’t be operated.
After energizing, the air conditioner can’t be operated
22
Check if AC220V power supply outputs to Indoor PCB.
Yes
Yes
No
No
Yes
Yes
No
Check if AC220V exists at the primary coil of transformer.
Indoor PCB is defective
Check if AC14.5V exists at the secondary coil of transformer.
Take off the secondary plug of transformer, and then check if
AC14.5V exists at the secondary coil of transformer.
The transformer is defective.
Indoor PCB is defective
10.3.2 Resetting phenomenon often occurs during operation. (That is automatically entering to the status
when power is on.)
The reason is that the instantaneous voltage of main chip is less than 4.5V. Check according to the following procedure:
Yes
Resetting phenomenon often occurs during operation.
No
Yes
After changing Indoor PCB, check if the failure releases
.
No
After changing indoor fan motor, check if the failure releases
.
Indoor PCB is defective
Power supply circuit has problems.
Содержание FSMED-124HFPL
Страница 5: ...3 Dimensions 3 1 Indoor unit FSMED 74HFPL 3 2 Indoor unit FSMED 124HFPL 4 ...
Страница 6: ...3 3 Outdoor unit FSMED 74HFPL 3 4 Outdoor unit FSMED 124HFPL 530 315 290 750 110 62 590 285 5 ...
Страница 7: ...4 Refrigeration cycle diagram 5 Operation range 6 ...
Страница 13: ...8 2 Wiring diagram FSMED 74HFPL Indoor unit outdoor unit 12 ...
Страница 14: ...FSMED 124HFPL Indoor unit outdoor unit 13 ...