Operation Manual of The Ducted Split
Type Air-Conditioning Units
FSL-1100B-H-3F
FSOL-1100B-3F
Please read this manual carefully before operation and installation
Страница 1: ...Operation Manual of The Ducted Split Type Air Conditioning Units FSL 1100B H 3F FSOL 1100B 3F Please read this manual carefully before operation and installation ...
Страница 2: ...e of guarantee must accord with the following items The first start up should be carried out by qualified service technicians appointed by the service center of FISHER The components of air conditioning units should only be provided by FISHER Company The specified time and frequency of the operation and maintenance items in this manual should be strictly executed Any violation of the precedent ite...
Страница 3: ...heater setting 16 5 12 Blow Function Setting 17 5 13 Quiet Function Setting 18 5 14 Debugging Functions 19 5 14 1 Ambient Temperature Sensor Setting 19 5 14 2 Three Grades of Speed for Indoor Fan 20 5 15 Other Functions 20 5 15 1 Lock Function 20 5 15 2 Memory Function 20 5 15 3 Gate control Display Function 20 5 15 4 Enquiry of Outdoor Ambient Temperature 21 5 15 5 Selection of Centigrade and Fah...
Страница 4: ...ge the air but this can affect the adjustment of air conditioning ATTENTION z Ensure the power supply correspond to the nameplate and check the security of the power source before installation z Make sure that the wires pipes and drain hose are properly connected before operation to avoid a fire or electric shock z Don t let children operate the ducted air conditioning unit z Turn off the power su...
Страница 5: ...2 6 The appliance shall be installed in accordance with national wiring regulations 7 The temperature of refrigerant circuit will be high please keep the interconnection cable away from the copper tube ...
Страница 6: ... LCD display No Description Instruction to Displaying Contents 1 Swing Swing function 2 Air Air exchange function 3 Sleep Sleeping states 4 Running Each kind of running mode of indoor unit auto mode 2 1 LCD Display of Wired Controller 2 2 Instruction to LCD Display ...
Страница 7: ...tate Indoor unit resumes original setting state after power failure and then power recovery 15 Twinkle Flicking when unit is on without operation of buttons 16 Save Energy saving state 17 Temperature Ambient setting temperature value 18 E Heater Mark that E heater is allowed to turned on 19 Blow Blow mark 20 Timer Timer displayed location 21 Quiet Quiet state two types quiet and auto quiet There i...
Страница 8: ...f cooling heating fan dry mode of indoor unit 5 Function Switchover among the functions of air sleep turbo save e heater blow quiet 7 Timer Timer setting 8 On off Turn on off indoor unit 4 Mode and 2 Memory function Press them for 5s under off state of the unit to enter cancel memory function If memory is set indoor unit after power failure and then power recovery will resume original setting stat...
Страница 9: ...press them at the same time for 5s in to lock state In this case any other buttons won t respond the press Repress them for 5s to quit lock state 4 Mode and 5 Function Enquiry and setting of address of wired controller Press them for 5s under unit off at the same time to set address Table 3 1 ...
Страница 10: ... then fix it in mounting hole with screws M4X25 4 Insert the 4 core twisted pair through rectangle hole into controller s slot and buckle the front panel and soleplate of controller together 5 At last fix the controller s front panel and soleplate with screws ST2 2X6 5 Caution During connection of wirings pay special attention to the following items to avoid interference of electromagnetism to uni...
Страница 11: ...should be kept 20cm in min 2 If the unit is installed at the place where there is interference of electromagnetism signal line and wiring communication of wired controller must be shielding twisted pair lines ...
Страница 12: ...it press Mode button to switch the operation modes as the following sequence Press or button for increase or decrease of setting temperature under on state of the unit If Press or button for increase or decrease of setting temperature under on state of the unit If press either of them continuously temperature will be increased or decreased by 1 every 0 5s In Cooling Dry Fan and Heating mode temper...
Страница 13: ...state of unit press Function button till the unit enters swing control function and then press Enter cancel button to turn on turbo control function During swing function press Function button till the unit enters swing control function and then press Enter cancel button to cancel swing control function Swing control function setting is shown in Fig 5 5 There is no this function for this unit 5 4 ...
Страница 14: ...Hour On Off xx Hour means time of timer on but time of timer off won t be displayed Timer off setting Under on state of the unit without timer setting if Timer button is pressed LCD will display xx Hour OFF blinking In this case press or button to adjust timer on and then press Timer to confirm If Mode button is pressed before pressing Timer button to confirm timer mode will be switched to timer o...
Страница 15: ...unit on Turn on air function Under on state of the unit press Function button into this function setting Air mark blinks AIR 1 displayed at the ambient temperature displayed location 888 is defaulted the last type of AIR will be displayed after adjustment Press or button to adjust air type Press Enter Cancel button to turn on off air function After turning on this function the air mark shows There...
Страница 16: ...king and then press Enter cancel button to turn off this function Air mark will subsequently disappear Air setting is shown as in fig 5 7 Fig 5 7 Air exchange device Note In air exchange mode press Function button or there is not any operation within 5s after the last button operation the system will quit from air exchange setting and current energy saving date won t be memorized Sleep on Press Fu...
Страница 17: ...eset temperature will be decreased by 1 and 1 in another 1 hour After that the unit will run at this temperature Turbo function The unit at high fun speed can realize quick cooling or heating so that room temperature can quickly approach setting temperature In cooling or heating mode press Function button till the unit enters turbo function and then press Enter cancel button to turn on turbo funct...
Страница 18: ...on button into energy saving function SAVE blinking Press or button to adjust lower limited value of setting temperature in cooing mode After that press Enter Cancel button to turn on energy saving function for cooling Energy Saving Setting for Heating Under on state and in heating mode of the unit press Function button into energy saving function SAVE blinking Press Mode button into energy saving...
Страница 19: ...alue in cooling mode is 16 and the upper limited value in heating mode is 30 5 After save setting if the setting temperature is out of the range in the mode the limited value will prevail There is no this function for this unit E heater In heating mode E heater is allowed to be turned on for improvement of efficiency If heating mode is turned on by button operation auxiliary electric heating funct...
Страница 20: ...er mark won t be displayed The setting is shown in Fig 5 11 2 There is not E heater for A2 and cassette unit Blow function After the unit is turned off water in evaporator of indoor unit will be automatically evaporated to avoid mildew In cooling and dry mode press Function button till the unit enters dry function BLOW blinking and then press Enter cancel button to turn on this function In blow mo...
Страница 21: ...unction consists of two kinds quiet and auto quiet Press Function button till the unit enters quiet function setting state Quiet or Auto Quiet mark blinks In this case press or button to switch between Quiet and Auto Quiet and then press Enter cancel button to turn on this function In quiet mode press Function button till the unit enters quiet function In this case Quiet or Auto Quiet icon blinks ...
Страница 22: ... raised but reduced If high fan speed is manually adjusted auto quiet mode will quit 4 There is not auto quiet function in fan or dry mode Quiet off is default after power failure and then power recovery 5 If quite function is set turbo function will be canceled Under off state of the unit press Function and Timer buttons continuously for 5s into debugging menu Press Mode button to adjust the sett...
Страница 23: ...startup of the unit without malfunction or under off state of the unit press and buttons at the same time for 5s till the wired controller enters lock state In this case LCD displays After that repress these two buttons at the same time for 5s to quit lock state Under lock state any other buttons won t give any response to the press Memory switchover Under off state of the unit press Mode and butt...
Страница 24: ...on operation after plugging out the card Under on or off state of the unit press Enter Cancel button for 5s outdoor ambient temperature will be displayed at temperature displaying area after a sound of click Pressing any button this enquiry state will quit If there is not any operation for 20s it will automatically quit Note 1 This function will be shielded after energization of 12hr for some mode...
Страница 25: ...y If there are multiple systems the system number of failed system will be displayed before the colon not for single system If malfunction occurs please turn off the unit and ask professionals for help As shown in Fig 6 1 it means high pressure protection of system 2 under unit on Note Only Big Wind Pipe series have multiple units Multi system is only for air cooled packaged unit Fig 6 1 Fig 5 1 ...
Страница 26: ...mmunication malfunction E9 Indoor fan motor protection F0 Indoor unit ambient sensor malfunction at air return opening F1 Evaporator sensor malfunction F2 Condenser sensor malfunction F3 Outdoor unit ambient temperature sensor mal F4 Discharge temperature sensor malfunction F5 Ambient sensor malfunction on Displayer or LED board EH Auxiliary electric heating malfunction C5 Wire jumper cap malfunct...
Страница 27: ...the unit will be run in the mode which you want Press this button once the mode will be changed in a regular as AUTO COOL DRY FAN HEAT AUTO COOL DRY FAN HEAT 3 button Press the or button to set your desired temperature The temperature range is from 16 to 30 It is not necessary at AUTO mode AND when you are setting the timing hours press the or button once the timing hours will increase or decrease...
Страница 28: ...ton under filcking status is above 5s the timer setting will quit If the timer has been set press this button once again to quit it 9 TURBO button Set turbo on or off the characters of turbo will appear of disappear by pressing this key under cooling or heating mode Once energized the unit will be defalted to be turbo off This function can not be set under auto dehumidify or fan mode and character...
Страница 29: ...t super high speed to cool or heat quickly so that the ambient temp approachs the preset temp as soon as possible About LOCK Press and simultaneously to lock or unlock the keyboard If the remote control is locked the icon will be displayed on the LCD in which case press any button the mark will flicker for three times If the keyboard is unlocked the mark will disappear About switch between Fahrenh...
Страница 30: ...ease take them out and do not let the leakage liquid damage the wireless remote control The operation should be in its receiving rang It should be placed where is 1m away from the TV set or stereo sound sets If the remote control cannot operate normally please take the batteries out and then reinsert it 30s later if it is also abnormal please replace the batteries If the main unit needs to be remo...
Страница 31: ...everyday so as to achieve fully automatic operation This WEEKLY TIMER adopts 485 modes to communicate with manual control of every duct type unit and it can control up to 16 units Adopting2 core twisted pair wire the longest communication distance of this TIMER is 1200m After connected to power the WEEKLY TIMER can display all connected units sequence of unit is determined by code switch of manual...
Страница 32: ...epared 1 Press or to select the unit that needed to be control It is available to control several units by Group Control 1 16 or control single unit by Single Control 2 When selected a certain or several units by Single Control or Group Control Timer setting and On off setting can be set Timer setting can set 4 on off times in a day in one week and on off setting can be done by pressing on off but...
Страница 33: ...Do not install the unit where it will be exposed to direct sunlight or other radiation heat source or the awning or a rainproof cloth should be utilized The inlet and outlet port should not be blocked Make sure the well air circulation Selection a location that is far away from combustible or explosive material dust fog or moist 10 2 Install the indoor unit 1 The dimensions of installation hole an...
Страница 34: ... Nut installation of suspender 1000 1 000 560 Fig 20 Schematic for the indoor unit 3 Drain hose For easy drainage of the condensation water the should be installed with a downward gradient To avoid the condensation the connection pipe joint should be insulated with thermal insulation material A water seal should be employed as shown in Fig 19 and the height of the water seal could be determined by...
Страница 35: ...ctrical Box part 6 Install the wired remote controller z A pit or a hole in the suitable position of the wall should be reserved for the connection signal cables z The connection wire between indoor unit and controller can be laid in the pit with 1 PVC pipe for direct installation Figure 22 For concealed installation 1 PVC can also be utilized Figure 23 z Both Cable of direct installation and the ...
Страница 36: ... wire controller User can select one from the two indoor room sensors on the basis of the engineering requirement Refer to the section of wire controller instructions for detailed operation Indoor Room Sensor B Indoor Room Sensor A 9 Checking of Outdoor Ambient Temperature The outdoor ambient temperature can be checked on the wire controller for the convenience of users before going out Refer to t...
Страница 37: ...n we should routinely check it every 1 2 months also ensure the test results complying with Table 2 The adjustment of the tightness of the belt is shown in Fig 25 Loosen screws fixing motor on the base move motor along the direction of arrow as shown in the picture then fix the screw again The tightness level of belt is tested by tensiometer as shown in Fig 26 when reaches the deviation length Dev...
Страница 38: ...e outdoor unit 1 Outline and dimension of the outdoor unit Nut 1 Setting lever Nut 2 Belt tensiometer 1772 A 880 840 C 2 B 2 844 2 Fig 27 Schematic of the Outdoor unit FSOL 1100B 3F Table 3 Outlines and dimension of the unit Unit mm Model A B C FG R 30 BNa M O 990 787 337 FG R 40 BNa M O 1290 1160 850 ...
Страница 39: ...36 2 Installation position 1200 1000 1000 1000 3000 Side with Electrical Box ...
Страница 40: ...M12 to tight the support fundus 3 Refrigerant pipe connection z The connection of the pipes should confirm to the following principles z Make sure to lessen the length of connecting pipe the height difference between the indoor and outdoor unit Note Do not loosen the cap of the pipes when connecting the pipes between the indoor unit and the outdoor unit Connecting the pipes as soon as possible aft...
Страница 41: ...n loosens the cores of the liquid valve and gas valve and clears the soap water with dry cloth z If the vacuum pumps and high pressure nitrogen are not available we can operate as following Remove the cores of the liquid valve and gas valve and loosen the cores of check valve on the gas valve and the gas will exhaust Keep exhausting for 15 seconds tightening the check valve as refrigerant gas comi...
Страница 42: ...a central switch which can cut all the power switch and air switch of the system The air switch should have hot and magnetic auto turn off function to protect the system from overloading or short power Please accord to electrical diagram on the unit when connecting the wires 1 Open indoor electric box and outdoor electric box respectively and put the wires cross the electric boxes Please choose th...
Страница 43: ...be copper inside while the working temp can not be over its standard one If the total length of the power cord is over 15m please increase the size by certain degree Please confirm the other wire according to the actual need ...
Страница 44: ...e rated voltage marked on the nameplate It may cause electric malfunction or damage the part Is the electric wiring and piping connection installed correctly and securely It may cause electric malfunction or damage the part Has the unit been connected to a secure earth connection It may cause electrical leakage Is the power cord specified It may cause electric malfunction or damage the part Has th...
Страница 45: ... Abnormal operation of the control system 1 Clean air filter 2 Move the obstacles 3 Close windows and doors 4 Contact the service center of FISHER 5 The performance of the unit is affected 6 Contact the service center of FISHER Cooling is not sufficient 1 Air filter is dirty 2 Air outlet port or intake port of indoor unit or outdoor unit is blocked 3 Too many persons or a heat source in the room 4...
Страница 46: ... so as to confirm the fluency flow of condensate 5 Running cautions of machine as operating season coming z Check if air intake and outlet port is blocked z Check if the earth connection of the machine is reliable z Check if the air filter is installed properly z After a long period of stop we should switch on the power supply for 8 hours to preheat the crankcase of compressor before operating the...
Страница 47: ...to change with the improvement of products in which case the values on nameplate shall prevail 4 In this table the outdoor side 18 15 DB temperature of low ambient cooling include two values the one in the bracket is the working condition of the appliance with function of low ambient cooling 18 is the working condition for the unit without low ambient cooling fuction 15 is the working condition fo...
Страница 48: ...DISPOSAL Do not dispose this product as unsorted municipal waste Collection of such waste separately for special treatment is necessary 66129906995 ...