- 37 -
2.
Install outdoor unit
3.
Refrigerant pipe connecting
(1) Maximum pipe length
Model
Max. Length
Max. Elevation
FSK-124-244-364-484HF 15m
5m
(2) Piping sizes
Model Liquid(mm/inch)
Gas(mm/inch)
FSK-124-184HF 6.35(1/4)
12.7(1/2)
FSK-244HF 9.52(3/8) 16.0(5/8)
FSK-364-484HF 12.7(1/2)
19.0(3/4)
(3) Piping connection
1). Measure the necessary length of the connecting pipe, and make it by the following way.
a.
Connect the indoor unit at first, then the outdoor unit.
Bend the tubing in proper way. Do not harm them.
CAUTIONS
& Daub the surfaces of the flare pipe and the joint nuts with frozen oil, and wrench it for 3~4 rounds
&With hands before fasten the flare nuts.
& Be sure to use two wrenches simultaneously when you connect or disconnect the pipes.
Tubing size
Torque
6.35 1420~1720N.cm(144~176kgf.cm)
9.52 3270~3990N.cm(333~407kgf.cm)
12.7 4950~6030N.cm(504~616kgf.cm)
16 6180~7540N.cm(630~770kgf.cm)
19 9720~11860N.cm(990~12106kgf.cm)
b.
The stop value of the outdoor unit should be closed absolutely (as original state). Every time you connect it,
first loosen the nuts at the part of stop value, then connect the flare pipe immediately (in 5 minutes). If the
nuts have been loosened for a long time, dusts and other impurities may enter the pipe system and may cause
malfunction later. So please expel the air out of the pipe with refrigerant before connection.
c.
Expel the air after connecting the refrigerant pipe with the indoor unit and the outdoor unit. Then fasten the
nuts at the repair-points.
2) Locate The Pipe
a. Drill a hole in the wall (suitable just for the size of the wall conduit), then set on the fittings such as the wall
conduit and its cover.
b. Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air in, which will
cause water leakage by condensation.
c. Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe allocation to do
no damage to the tubing.
3) Connect the pipes.
4) Then, open the stem of stop values of the outdoor unit to make the refrigerant pipe connecting the indoor unit
with the outdoor unit in fluent flow.
5) Be sure of no leakage by checking it with leak detector or soap water.
6) Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating sheath (fittings), and
bind it well with the tapes to prevent leakage.
Содержание FSK-124HF
Страница 9: ...Part 4 Velocity temperature distribution Discharge angle 60º Airflow velocity Temperature 8 ...
Страница 10: ...Part 5 Operation Range Ensure the operating temperature is in allowable range 9 ...
Страница 28: ...FSK 244HF Indoor Unit Outdoor Unit XT3 VALVE R T3 XT1 XT2 XS1 XP1 KM 1 FAN C AP2 C O M P C AP1 27 ...
Страница 42: ...Part 12 Exploded view 1 FSK 124HF Indoor unit 41 ...
Страница 45: ...2 FSK 184HF Indoor unit 44 ...
Страница 48: ...12 FSK 244HF Indoor unit 47 ...
Страница 51: ...13 FSK 364 484HF Indoor unit 50 ...
Страница 55: ... 54 54 ...