- 34 -
3.
Indoor unit installation
FSK-244-364-484HF
(1)
Install the main body
A. The existing ceiling (to be horizontal)
a. Please cut a quadrangular hole of 880X880mm in the ceiling according to the shape of the installation paper
board. (Refer to Chart3,4)
The center of the hole should be at the same position of that of the air conditioner body.
Determine the lengths and outlets of the connecting pipe, drain pipe and cables.
To balance the ceiling and to avoid vibration, please enforce the ceiling when necessary.
b. Please select the position of installation hooks according to the hook holes on the installation board.
Drill four holes of 12mm, 45~50mm deep at the selected positions on the ceiling. Then embed the
expansible hooks(fittings).
Face the concave side of the installation hooks toward the expansible hooks. Determine the length of the
installation hooks from the height of ceiling, then cut off the unnecessary part.
If the ceiling is extremely high, please determine the length of the installation hook according to facts.
The length could be calculated from Chart5:
Length=H-181+L(in general, L is half of the whole length of the installation hook)
c. Please adjust the hexangular nuts on the four installation hooks evenly, to ensure the balance of the body.
If the drainpipe is awry, leakage will be caused by the malfunction of the water-level switch.
Adjust the position to ensure the gaps between the body and the four sides of ceiling are even.The body's
lower part should sink into the ceiling for 10~12mm (Refer to chart5).
Locate the air conditioner firmly by wrenching the nuts after having adjusted the body's position well.
A
Drain side
Tubing side
680
(H
ook
-loc
at
ion)
780(Hook-location)
84
0(
Bod
y)
840(Body)
880
(C
eil
ing hole
)
880(Ceiling hole)
950(P
anel)
950(Panel)
Chart 3
Содержание FSK-124HF
Страница 9: ...Part 4 Velocity temperature distribution Discharge angle 60º Airflow velocity Temperature 8 ...
Страница 10: ...Part 5 Operation Range Ensure the operating temperature is in allowable range 9 ...
Страница 28: ...FSK 244HF Indoor Unit Outdoor Unit XT3 VALVE R T3 XT1 XT2 XS1 XP1 KM 1 FAN C AP2 C O M P C AP1 27 ...
Страница 42: ...Part 12 Exploded view 1 FSK 124HF Indoor unit 41 ...
Страница 45: ...2 FSK 184HF Indoor unit 44 ...
Страница 48: ...12 FSK 244HF Indoor unit 47 ...
Страница 51: ...13 FSK 364 484HF Indoor unit 50 ...
Страница 55: ... 54 54 ...