Electrical Control Function
Electrical Control System
123
1.3.6.3 Timer off. The machine will turn off automatically when reaching the setting time.
1.3.6.4 Timer on/off. The machine will turn on automatically when reaching the setting “on” time, and then
turn off automatically when reaching the setting “off” time.
1.3.6.5 Timer off/on. The machine will turn off automatically when reaching the setting “off” time, and then
turn on automatically when reaching the setting “on” time.
1.3.6.6 The timer function will not change the AC current operation mode. Suppose AC is off now, it will not
start up firstly after setting the “timer off” function. And when reaching the setting time, the timer LED will be
off and the AC running mode has not been changed.
1.3.6.7 The setting time is relative time.
1.3.7 Economy function
1.3.7.1 The sleep function is available in cooling, heating or auto mode.
1.3.7.2. Operation process in sleep mode is as follow:
When cooling, the setting temperature rises 1
℃
(be lower than 30
℃
) every one hour, 2 hours later the
setting temperature stops rising and the indoor fan is fixed at low speed.
When heating, the setting temperature decreases 1
℃
(be higher than 17
℃
) every one hour, 2 hours later
the setting temperature stops rising and indoor fan is fixed at low speed. (Anti-cold wind function has the
priority).
1.3.7.3 Operation time in sleep mode is 7 hours. After 7 hours the AC quits this mode but doesn’t turns off,
but for console, the unit will turn off.
1.3.7.4 Timer setting is available
1.3.8 Auto-Restart function
The indoor unit is equipped with auto-restart function, which is carried out through an auto-restart module. In
case of a sudden power failure, the module memorizes the setting conditions before the power failure. The
unit will resume the previous operation setting (not including economy function and
auxiliary functions
)
automatically after 3 minutes when power returns.
1.3.9 Drain pump control (For Cassette)
Adopt the water-level switch to control the action of drain pump.
Main action under different condition :( every 5 seconds the system will check the water level one time)
1. When the A/C operates with cooling (including auto cooling) and forced cooling mode, the pump will start
running immediately and continuously, till stop cooling.
2. Once the water level increase and up to the control point, LED will alarm and the drain pump open and
continue checking the water level. If the water level fall down and LED disalarmed (drain pump delay close 1
minute) and operate with the last mode. Otherwise the entire system stop operating ( including the pump)
and LED remain alarming after 3 minutes.
1.3.10 Follow me(Optional)
1) If the indoor PCB receives the signal which results from pressing the FOLLOW ME button on remote
Содержание FSFIF-121AE2
Страница 12: ...Service Space 10 Indoor Units 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Страница 14: ...Air Velocity Distributions Reference Data 12 Indoor Units 30 36K Cooling Heating ...
Страница 15: ...Air Velocity Distributions Reference Data Indoor Units 13 48 60K Cooling Heating ...
Страница 20: ...Field Wiring 18 Indoor Units 9 Field Wiring ...
Страница 28: ...Static Pressure 26 Indoor Units 4 Static Pressure FSLIF 182AE2 FSLIF 242AE2 ...
Страница 29: ...Static Pressure Indoor Units 27 FSLIF 301AE2 FSLIF 362AE2 ...
Страница 30: ...Static Pressure 28 Indoor Units FSLIF 481AE0 FSLIF 602AE0 ...
Страница 35: ...Field Wiring Indoor Units 33 9 Field Wiring ...
Страница 37: ...Wiring Diagram Indoor Units 35 FSLIF 362AE2 ...
Страница 38: ...Wiring Diagram 36 Indoor Units ...
Страница 42: ...Service Space 40 Indoor Units 3 Service Space ...
Страница 51: ...Wiring Diagram Indoor Units 49 Field Wiring 9 ...
Страница 52: ...Wiring Diagram 50 Indoor Units 10 Wiring diagram FSPIF 181AE2 ...
Страница 53: ...Ceiling Floor Type Indoor Units 51 FSPIF 241AE2 FSPIF 301AE2 ...
Страница 54: ...Wiring Diagram 52 Indoor Units FSPIF 362AE2 FSPIF 480AE0 FSPIF 601AE0 ...
Страница 58: ...Service Space 56 Indoor Units 3 Service Space ...
Страница 62: ...60 Indoor Units 9 Field Wiring FSKIF 121AE2 EU FSKIF 184AE2 EU 12k unit Field Wiring ...
Страница 63: ...Indoor Units 61 10 Wiring diagram FSKIF 121AE2 EU FSKIF 184AE2 EU Wiring Diagram ...
Страница 67: ...Console Type 2 Dimensions 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 Indoor Units 63 ...
Страница 68: ...Console Type 3 Service Space 64 Indoor Units ...
Страница 73: ...Console Type 9 Field Wiring Indoor Units 69 FSFIF 121AE2 12 ...
Страница 74: ...Console Type 10 Wiring diagram 70 Indoor Units FSFIF 121AE2 ...
Страница 76: ...Outdoor Units 72 Outdoor Units ...
Страница 78: ...Dimensions 74 Outdoor Units Model KBtu h Unit mm W D H W1 A B 48 60 952 415 1333 1045 634 404 ...
Страница 84: ...Wiring diagram 80 Outdoor Units 7 Wiring diagram FSOIF 121AE2 FSOIF 183AE2 ...
Страница 85: ...Wiring diagram Outdoor Units 81 FSOIF 301AE2 FSOIF 243AE2 FSOIF 362AE2 3F ...
Страница 86: ...Wiring diagram 82 Outdoor Units FSOIF 482AE0 3F FSOIF 602AE0 3F ...
Страница 87: ...Wiring diagram Outdoor Units 83 ...
Страница 105: ...Installation 101 ...
Страница 110: ...Refrigerant pipe installation 106 Installation ...
Страница 132: ...Troubleshooting 128 Electrical Control System 2 1 5 Icon explanation on indoor display board Console ...
Страница 143: ...Troubleshooting Electrical Control System 139 2 4 4 2 E1 malfunction For current loop communication ...
Страница 145: ...Troubleshooting Electrical Control System 141 2 4 4 3 J4 malfunction J4 ...
Страница 148: ...Troubleshooting 144 Electrical Control System 2 4 4 6 F5 malfunction The same as E3 in indoor 2 4 4 7 J5 malfunction J5 ...
Страница 154: ...Troubleshooting 150 Electrical Control System 2 4 4 13 J0 malfunction J0 ...