Drainage pipe installation
110
Installation
6.3 Drainage test
6.3.1 Water leakage test
After finishing the construction of drainage pipe system, fill the pipe with water and keep it for 24 hours to
check whether there is leakage at joint section.
6.3.2 Water discharge test
1. Natural drainage mode(the indoor unit with outdoor drainage pump)
Infuse above 600ml water through water test hole slowly into the water collector, observe whether the
water can discharge through the transparent hard pipe at drainage outlet.
2. Pump drainage mode
2.1 Disconnect the plug of water level switch, remove the cover of water test hole and slowly infuse about
2000ml water through the water test hole, be sure that the water will not touch the motor of drainage
pump.
2.2 Power on and let the air conditioner operate for cooling. Check operation status of drainage pump, and
then connect the plug of water level switch, check the operation sound of water pump and observe
whether the water can discharge through the transparent hard pipe at drainage outlet. (In light of the
length of drainage pipe, water shall be discharged about 1 minute delayed)
2.3 Stop the operation of air conditioner, power off the power supply and put the cover of water test hole
back to the original place.
a. After stopped the air conditioner 3 minutes, check whether there is anything abnormal. If drainage pipes
have not been distributed properly, over back-flow water shall cause the flashing of alarm indicator at
remote-controlled receiving board and even water shall run over the water collector.
b. Continuously infusing water until water level alarmed, check whether the drainage pump could
discharge water at once. If water level does not decline under warning water level 3 minutes later, it
shall cause shutdown of unit. When this situation happens, the normal startup only can be recovered by
turning down power supply and eliminating accumulated water.
Note:
Drain plug at the main water-containing plate is used for eliminating accumulated water in
water-containing plate when maintaining air conditioner fault. During normal operation, the plug shall be
filled in to prevent leakage.
6.4 Insulation work of drainage pipe
Refer the introduction to the insulation engineering parts.
Содержание FSFIF-121AE2
Страница 12: ...Service Space 10 Indoor Units 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Страница 14: ...Air Velocity Distributions Reference Data 12 Indoor Units 30 36K Cooling Heating ...
Страница 15: ...Air Velocity Distributions Reference Data Indoor Units 13 48 60K Cooling Heating ...
Страница 20: ...Field Wiring 18 Indoor Units 9 Field Wiring ...
Страница 28: ...Static Pressure 26 Indoor Units 4 Static Pressure FSLIF 182AE2 FSLIF 242AE2 ...
Страница 29: ...Static Pressure Indoor Units 27 FSLIF 301AE2 FSLIF 362AE2 ...
Страница 30: ...Static Pressure 28 Indoor Units FSLIF 481AE0 FSLIF 602AE0 ...
Страница 35: ...Field Wiring Indoor Units 33 9 Field Wiring ...
Страница 37: ...Wiring Diagram Indoor Units 35 FSLIF 362AE2 ...
Страница 38: ...Wiring Diagram 36 Indoor Units ...
Страница 42: ...Service Space 40 Indoor Units 3 Service Space ...
Страница 51: ...Wiring Diagram Indoor Units 49 Field Wiring 9 ...
Страница 52: ...Wiring Diagram 50 Indoor Units 10 Wiring diagram FSPIF 181AE2 ...
Страница 53: ...Ceiling Floor Type Indoor Units 51 FSPIF 241AE2 FSPIF 301AE2 ...
Страница 54: ...Wiring Diagram 52 Indoor Units FSPIF 362AE2 FSPIF 480AE0 FSPIF 601AE0 ...
Страница 58: ...Service Space 56 Indoor Units 3 Service Space ...
Страница 62: ...60 Indoor Units 9 Field Wiring FSKIF 121AE2 EU FSKIF 184AE2 EU 12k unit Field Wiring ...
Страница 63: ...Indoor Units 61 10 Wiring diagram FSKIF 121AE2 EU FSKIF 184AE2 EU Wiring Diagram ...
Страница 67: ...Console Type 2 Dimensions 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 Indoor Units 63 ...
Страница 68: ...Console Type 3 Service Space 64 Indoor Units ...
Страница 73: ...Console Type 9 Field Wiring Indoor Units 69 FSFIF 121AE2 12 ...
Страница 74: ...Console Type 10 Wiring diagram 70 Indoor Units FSFIF 121AE2 ...
Страница 76: ...Outdoor Units 72 Outdoor Units ...
Страница 78: ...Dimensions 74 Outdoor Units Model KBtu h Unit mm W D H W1 A B 48 60 952 415 1333 1045 634 404 ...
Страница 84: ...Wiring diagram 80 Outdoor Units 7 Wiring diagram FSOIF 121AE2 FSOIF 183AE2 ...
Страница 85: ...Wiring diagram Outdoor Units 81 FSOIF 301AE2 FSOIF 243AE2 FSOIF 362AE2 3F ...
Страница 86: ...Wiring diagram 82 Outdoor Units FSOIF 482AE0 3F FSOIF 602AE0 3F ...
Страница 87: ...Wiring diagram Outdoor Units 83 ...
Страница 105: ...Installation 101 ...
Страница 110: ...Refrigerant pipe installation 106 Installation ...
Страница 132: ...Troubleshooting 128 Electrical Control System 2 1 5 Icon explanation on indoor display board Console ...
Страница 143: ...Troubleshooting Electrical Control System 139 2 4 4 2 E1 malfunction For current loop communication ...
Страница 145: ...Troubleshooting Electrical Control System 141 2 4 4 3 J4 malfunction J4 ...
Страница 148: ...Troubleshooting 144 Electrical Control System 2 4 4 6 F5 malfunction The same as E3 in indoor 2 4 4 7 J5 malfunction J5 ...
Страница 154: ...Troubleshooting 150 Electrical Control System 2 4 4 13 J0 malfunction J0 ...