GAS CONNECTION

Connection: 

1/2" NPT Minimum 5/8" dia. flex line.

 Supply pressure:

 6" to 9" W.C

Connection:

 1/2" NPT Minimum 5/8" dia. flex line. 

Supply Pressure:

 11" to 14" W.C. 

A regulator is required at the LP source to provide a maximum pressure of 14" W.C. to the 
cooktop regulator.

A manual shut-off valve (not supplied) must be installed in an accessible location in the 
gas line external to the appliance for the purpose of turning on or shutting off gas to the 
appliance. In Massachusetts, such shut-off valves should be approved by the Board of State 
Examiners of Plumbers & Gas Fitters. The shut-off valve must be located within 6 feet (1.8 
meters) of the appliance.
Ensure the gas supply is turned off at the wall valve before connecting the appliance. The 
gas supply connections should be made by a qualified technician and in accordance with 
local codes or ordinances. In the absence of a local code, the installation must conform to 
the latest edition of National Fuel Gas Code ANSI Z223.1. When within the Commonwealth of 
Massachusetts, this appliance must be installed by a licensed plumber or gas fitter.

To prepare the unit for connection to the gas supply

Thread the supplied 1/2" pipe nipple into the elbow on the end of the manifold. The elbow is 
located inside the chassis of the unit, on the end of the manifold, facing down. It is accessible 
through the square cutout in the left rear corner of the chassis bottom. Connect the outlet of 
the regulator to the exposed end of the nipple, connect the flex line from the gas supply to the 
inlet side of the regulator.

Fisher & Paykel recommends installing the manual shutoff valve in a location readily accessible 
by the customer, so that gas to the appliance can be shut off in an emergency situation. 
However, the appliance must not be modified in any way to accommodate such placement.
Pipe sealant must be used on all pipe threads.
The gas supply line must not protrude beyond the back of the appliance.
Ensure the gas supply is turned off at the wall valve before connecting the appliance. Leak-
testing of the appliance shall be conducted according to the manufacturer’s instructions. See 
instructions following. When checking the manifold gas pressure, the inlet pressure to the 
regulator should be at least 7.0" W.C. for natural gas or 12.0" for LP. 
The flex line for the gas supply must be metal and be approved for appliance use by a 
certifying agency (CSA, CGA, or UL). Never use a hose made of rubber or other synthetic 
material, as the heat may cause the hose to melt and develop leaks.
The arrow on the regulator indicating direction of gas flow should be pointing towards the 
unit.

Verify the type of gas supplied to the location. The cooktop is shipped from the factory set up and adjusted for Natural Gas or LP, depending on the specific model ordered. If the cooktop is not set 
for the gas supplied at the site, return to the dealer.

Pressure testing at test pressures in excess of 1/2 psig (3.5 kPa.): 

the cooktop and its individual shut-off valve must be disconnected from the gas supply piping system

Pressure testing at test pressures equal to or less than 1/2 psig (3.5 kPa.): 

The cooktop must be isolated from the building’s gas supply piping system by closing its individual manual shut-off valve

LP GAS CONNECTION

NATURAL GAS CONNECTION

base of product

1/2" coupling

1/2" close nipple

1/2" NPT to 3/8" 

flare adapter

to gas supply

1/2" x 5" close nipple

Regulator

Содержание CDV3-365

Страница 1: ...INSTALLATION GUIDE PROFESSIONAL CDV3 365H CDV3 365 CDV3 304H CDV3 304 GAS COOKTOPS US CA...

Страница 2: ...any electrical switch Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier cal...

Страница 3: ...avoid overheating z The cooktop must be grounded z Installation must comply with your local building and electricity regulations z Ensure the installer shows the customer where the gas supply shut of...

Страница 4: ...oduct to ensure there is no shipping damage If any damage is detected contact the dealer or retailer you bought the product from to report the damage z Fisher Paykel is not responsible for shipping da...

Страница 5: ...ht above countertop to top of grates 1 9 16 40 I Distance from right edge of chassis to centre of gas inlet 2 3 4 70 J Distance from rear edge of chassis to centre of gas inlet 1 5 16 33 K Distance fr...

Страница 6: ...from right edge of chassis to centre of gas inlet 2 3 4 70 J Distance from rear edge of chassis to centre of gas inlet 1 5 16 33 K Distance from right edge of chassis to centre of power cord 7 8 22 L...

Страница 7: ...ventilation hood required 30 762 F Min distance from rear edge of cutout to nearest combustible surface 2 51 CABINETRY DIMENSIONS 36 MODELS IN MM A Min height allowance 4 102 B Depth 19 3 4 502 C Wid...

Страница 8: ...defined in National Fuel Gas Code ANSI Z223 1 Current Edition Clearances from non combustible materials are not part of the ANSI Z21 1 scope and are not certified by UL Clearances of less than 6 152m...

Страница 9: ...ould be variable to reduce noise and loss of household air z Due to a high volume of ventilation air a source of make up air outside replacement air is recommended This is particularly important for t...

Страница 10: ...below Please verify your model s current draw by checking the rating label on the cooktop Required grounding method This appliance is factory equipped with a power supply cord with a three prong grou...

Страница 11: ...manual shutoff valve in a location readily accessible by the customer so that gas to the appliance can be shut off in an emergency situation However the appliance must not be modified in any way to ac...

Страница 12: ...z Check for a well defined blue flame without any yellow tipping z If any abnormality is evident check that the components of the burner assembly are located properly No air shutter adjustment is pos...

Страница 13: ...ight satisfactorily both individually and with other burners operating Flame adjustments made if required FINAL CHECKLIST GAS Connection 1 2 NPT with a minimum 5 8 diameter flex line Site gas supply i...

Страница 14: ...ge at any time The product specifications in this guide apply to the specific products and models described at the date of issue Under our policy of continuous product improvement these specifications...

Отзывы: