
30
237.
Temperature Sensor Error
The electronics have picked up a continuity problem, the same as fault code 10.
Primary Fault:
The sensor has failed either in the harness or the connection to the
thermistor.
Action:
Replace the thermistor (temperature sensor).
Secondary Source:
Motor Control module has failed to read the temperature. Check connections.
Action:
Replace Motor Control Module if the connections look fine and the fault still
occurs.
238.
Lid Lock Open Circuit
Check Harness to Lid Lock and connections at the Motor Control Module and lid lock ends.
Primary Fault:
Connector to the harness, either end could be at fault.
Action:
Replace Harness.
Secondary Source:
Lid Lock has failed to be activated.
Action:
Replace Lid Lock.
Tertiary Source:
Motor Control Module has not responded to the Lid Lock being activated.
Action:
Check the lid has a tang and is fitted correctly to activate the Lid Lock. If this
is all in order, the Motor Control Module must be at fault and needs to be
replaced.
239.
Lid Lock Short Circuit
Check Harness to Lid Lock and connections at the Motor Control Module and lid lock ends.
Primary Fault:
Connector to the harness, either end could be at fault.
Action:
Replace Harness.
Secondary Source:
Lid Lock has failed activated.
Action:
Replace Lid Lock.
Tertiary Source:
Motor Control Module has not responded to the Lid Lock being activated.
Action:
Check the lid has a tang and is fitted correctly to activate the Lid Lock. If this
is all in order, the Motor Control Module must be at fault and needs to be
replaced.
241.
Function Time Out
A fault has occurred with the Display Module.
Primary Fault:
Display Module has failed.
Action:
Replace Display Module.
Secondary Fault:
Motor Control Module has failed.
Action:
Replace Motor Control Module.
243.
Stepper Test Failure
The Motor Control Module has attempted a motor step test and found the motor has not stepped to the
correct position.
Primary Source:
Wiring.
Action:
Check the continuity of the Motor Harness and that the connectors are
correctly applied to the Motor and Motor Control Module.
Secondary Source:
Motor.
Action:
Check continuity of motor phases. Check the bridge terminal on the stator is
not open circuit or burnt. Replace Stator.
Tertiary Source:
Motor Control module.
Action:
Replace the Motor Control Module.
245.
Smart Pump Stall
This fault is normally as a result of the pump stalling during its normal operation.
Primary Source:
Pump stator winding open circuit.
Action:
Check the resistance of the pump stator. Resistance per Phase:
8.1Ω
+/- 10% (16.2Ω +/- 10% across any two phases).