Table function (n=7)
The table should comprise 7 value pairs. Of the input signal 0 … 10 V, the
range 2 … 8V should be used. The basic measuring range is 0 … 100 Pa. The
display should display in the start of the measuring range 10 Pa and at the end
of the measuring range 80 Pa.
0V
10V
Input signal
Display
2V
8V
0Pa
100Pa
E2
E3
E4
E5
E6
E7
E1
A1
A2
A3
A4
A5
A6
A7
10Pa
80Pa
Fig. 74:
Characteristic curve scale
E1= 2V
A1= 10,000 Pa
E2= 3V
A2= 20,000 Pa
E3= 4V
A3= 30,000 Pa
E4= 5V
A4= 40,000 Pa
E5= 6..2V A5= 40.750 Pa
E6= 7V
A6= 60,000 Pa
E7= 8V
A7= 80,000 Pa
Number of value pairs
n = 7
Input signal Start
Input signal End
Display range start
Display range end
Example:
E1 = 2 V
E7 = 8 V
A1 = 10 Pa
A7 = 80 Pa
deviating value
(see graphic tabel function)
Fig. 75:
Calculation of the characteristic curve