4 | Start-up
FISCHER Mess- und Regeltechnik GmbH
14/28
BA_EN_DE85
4.3.1 Measuring range
1
1
rising
falling
2
2
asymmetric unidirectional
e.g. 0 ... x
symmetric bidirectional
e.g. -x ... +x
8
8
mbar
Pa / kPa
1
4
ON
5 6 7
3
2
8
Characteristic curve
Symmetry
Unit
Fig. 12:
Configure measuring range
For example:
A device with the Code D1 was ordered for the measuring range. On delivery,
the device is pre-set to the basic measuring range
-0.25 … +0.25 mbar
.
This leads to the following configuration options for this measuring range:
1
4
ON
5 6 7
3
2
8
1
4
ON
5 6 7
3
2
8
0 ... +0.25 mbar
0 ... +25 Pa
1
4
ON
5 6 7
3
2
8
1
4
ON
5 6 7
3
2
8
-0.25 ... +0.25 mbar
-25 ... +25 Pa
1
4
ON
5 6 7
3
2
8
4
1
ON
5 6 7
3
2
8
0 ... -0.25 mbar
0 ... -25 Pa
1
4
ON
5 6 7
3
2
8
1
4
ON
5 6 7
3
2
8
+0.25 ... -0.25 mbar
+25 ... -25 Pa
4.3.2 Output signal
• Damping affects the analogue output and display.
• In case of square rooting, the DIP switch 2 (symmetry) does not have a
function. The measuring range is permanently set to ‘asymmetric unidirec-
tional’ (0...x).
4 5 6
1
ON
2
8
7
3
Current / voltage
offset zero point
Characteristic curve
Square rooting
Damping
3
3
0 V / 0 mA
2 V / 4 mA
4
4
Current (mA)
Voltage (V)
5
5
rising
falling
6
6
Linear
Square rooted
7
7
1 sec
5 sec
Fig. 13:
Configure output signal