5.1.

Pressure Connections

The instruments pressure ports are marked by 

+

 and 

symbols. The pressure applications need to be installed
according to the label.
• Differential pressure 

+

= higher pressure

measurement:

= lower pressure.

• Pressure measurement

+

 = pressure port

• Gauge measurement

 = negative pressure port

5.2.

Shock Pressure Moderation

During pulsating pressure on the plant mechanical wear
and disturbances in functional capability may occur. To
avoid this we recommend installing absorbers into the
pressure lines.

5.3.

Zero Point Adjustment

Usually adjustment of the instrument is not necessary for
it is factory calibrated. The output signal can be adjusted
with inbuilt zero point potentiometer.

Location of zero point potentiometer

Adjustment sequence

• Open housing cover.

• Connect current indicator (0-20 mA) to output signal

between terminals 11 and 12.

• Connect and switch on power supply.

• Measuring system depressurized: Output signal = 0

resp. (4) mA. Correct offset using zero point potentio-
meter N.

• Mount housing cover.

5.4.

Switching Point Adjustment

The instrument’s main board has two calibration poten-
tiometers and a coding switch to set switching points. Af-
ter removing housing cover they are freely acessible.

Adjustment sequence

• Switch on supply voltage.

• Open housing cover.

• Selector setting 1: Display indicates actual value.

• Selector setting 2: Display indicates switching point I.

• Selector setting 3: Display indicates switching point II.

• The respective setpoint values for contact 1 and con-

tact 2 can be set in display using potentiometers K1
and K2. 

• After adjustment is done turn selector to setting 1: ac-

tual value. 

• Setpoint values can be displayed any time by turning

selector to position 2 or 3.

Selector and Set-up Potentiometer

5.5.

Electrical Connection

3-wire connection 24 V DC

2-wire connection 24 V DC

For Gaseous Media

Adjustable attenuator
valve 

MZ41

During operating condition ad-
just needle valve that way,
that the indicator follows chan-
gements of pressure delayed.

MZ41

Mounting holes

Range adjustment: N = Zero point

Switching point 
potentiometer

Selector

Selector

Содержание DE61

Страница 1: ...instructions use of this pro duct for purposes for which it is not intended and or operation of this product outside the limits spe cified for any of its technical parameters can result in harm to per...

Страница 2: ...ssure safe shock and vibration resistant and long time stable The differential pressure acts on the sensor element and effects a measuring signal The electronic amplifier then generates an electrical...

Страница 3: ...mA Correct offset using zero point potentio meter N Mount housing cover 5 4 Switching Point Adjustment The instrument s main board has two calibration poten tiometers and a coding switch to set switch...

Страница 4: ...ust be read thoroughly to ensure that all of them work correctly when connected together 7 Transport The product must be protected against shock and vibra tion during transport It must therefore be pr...

Страница 5: ...Measuring indication 3 digit LC Display Switching point adjustment The digital display can be switched over between the differential pressure actual value and the switch point adjustments via selector...

Страница 6: ...6 12 Dimensions all units in mm unless stated otherwise Mounting holes 4 5 mm Cable gland M16 x 1 5...

Страница 7: ...0 Screw connection AI for 6 mm flexible tube 4 0 Screw connection AI for 8 mm flexible tube 4 1 Electrical Output Signal 0 20 mA linear 3 wire A 4 20 mA linear 2 wire only 24 V DC without contacts an...

Страница 8: ...ange without notice Changements techniques sous r serve Fischer Mess und Regeltechnik GmbH Bielefelder Str 37a D 32107 Bad Salzuflen Tel 49 5222 9740 Fax 49 5222 7170 eMail info fischermesstechnik de...

Отзывы: