4 | Commissioning
FISCHER Mess- und Regeltechnik GmbH
16/40
BA_EN_DE45_ATEX_LCD
4.3.1 Menu Level Switch points
Parameter name
Description
Value range
SP1 On
Switch point 1 On
MRS-50% … MRE+50%
SP1 Off
Switching point 1 off
MRS-50% … MRE+50%
SP1 Delay
Switching point 1 delay
0…1800 s
SP1 Function
Switching point 1 function
NO, NC
SP2 On
Switch point 2 On
MRS-50% … MRE+50%
SP2 Off
Switching point 2 off
MRS-50% … MRE+50%
SP2 Delay
Switching point 2 delay
0…1800 s
SP2 Function
Switching point 2 function
NO, NC
The two switch outputs are configured by four parameters respectively.
For the switch point 1 these are
•
SP1 On
•
SP1 Off
•
SP1 Delay
•
SP1 Function
Accordingly for switch point 2:
•
SP2 On
•
SP2 Off
•
SP2 Delay
•
SP2 Function
The function of the individual parameters is explained for both switch points us-
ing Switch point 1 as an example.
SP1 On
defines the activation point,
SP1 Off
the deactivation point of switch
output 1. The values are shown in the valid unit and set accordingly. The values
are shown in the valid unit and set accordingly. Both parameters can be set in-
dependently over the entire value range.
The value range ranges from MRS – 50% to MRE + 50%. MRS stands for
measuring range start and MRE for measuring range end.
Example:
Measurement range = 0 … 100 Pa
The value range for this measuring range is -50 Pa … +150 Pa.
Together, the two parameters
SP1 On
and
SP1 Off
determine the switch func-
tion of switch output 1:
• If
SP1 On
>
SP1 Off
, the output switches on, if the measured value ex-
ceeds SP1 On. It is only switched off again if the measured value SP1 Off is
undercut (hysteresis function).
• If
SP1 On
=
SP1 Off
, the output switches on if the measured value exceeds
SP1 On and off if the measured value undercuts the same value (SP1 Off).
• If
SP1 On
<
SP1 Off
, the output switches on, if the measured value lies
within these switch points: i.e:
SP1 On
< Measured value <
SP1 Off
(window function).
SP1 Delay
allows the reaction of the switch output to be delayed by between 0
and 1800 s. This parameter applies equally for switching on and off.
SP1 Function
changes the function of the switch output 1. It is possible here to
define whether the contact should work as a open contact (NO) or a break con-
tact (NC).