Fuse rating
Check fuse rating. If possible, refer to manufacturer's user guide. Otherwise
follow guidelines below:
3A or 5A fuse fitted: NO action.
13A fuse fitted: Then check power rating.
If power is less than 700 W then fit 3 Amp Fuse.
If power is more than 700 W then NO action.
Examples:
40W rating, requires 3A fuse.
1200W rating, requires 13A fuse.
If the equipment fails on any of the above points, then it must be taken out of
service, a "DO NOT USE" label applied and not used again until it has been
properly repaired and tested.
Under no circumstances must one proceed with the testing
stage, if a failure is found during the Formal Visual Inspection
stage.