Installation of Valve Cluster Assemblies

HBC(X), PHBC(X), RHBC(X), CHBC(X):

 

Installation, Operation, and Maintenance Instructions

9

I

NSTALLATION OF 

V

ALVE 

C

LUSTER 

A

SSEMBLIES

Horizontal hydronic fan coil units may use either a two-way (Figure 3) or three-
way (Figure 4) motorized valve assembly. The following procedures describe 
each installation.

P

ROCEDURE 

1:  T

WO

-W

AY 

M

OTORIZED 

V

ALVE 

A

SSEMBLIES

1.

The two-way motorized valve assembly should be attached to the supply 
header which is the connection nearest the air outlet flange on the unit.

2.

Prior to soldering the joints, operate all the hand valves to ensure that the 
handles will fully open and close without interference to other valves, 
ceiling, wall, plenum or other accessories.

3.

All valves will operate at any angle with the exception of the motorized 
valve, which must never be installed with the power head below horizontal. 
The actuator box requires a 3/4-inch clearance for removal.

FIGURE 3. 

Two-Way Motorized Valve Assembly

P

ROCEDURE 

2:  T

HREE

-W

AY 

M

OTORIZED 

V

ALVE 

A

SSEMBLY

1.

The three-way valve assemblies will mount to the coil in only one position. 

2.

Prior to soldering the joints, operate all the hand valves to ensure that the 
handles will fully open and close without interference to other valves, 
ceiling, wall, plenum or other accessories.

3.

All valves will operate at any angle with the exception of the motorized 
valve, which must never be installed with the power head below horizontal. 
The actuator box requires a 3/4-inch clearance for removal.

FIGURE 4. 

Three-Way Motorized Valve Assembly

Содержание 450532L 5HBC32 LH

Страница 1: ...or local codes in any way These instructions must be left with the property owner SAFETY CONSIDERATIONS Improper installation adjustment alteration service maintenance or use can cause explosion fire...

Страница 2: ...death When fan coil is operating some components are operating at high speeds Personal injury can result from touching these items with any object All electrical and service access panels must be sec...

Страница 3: ...tion exists prior to energizing any power sources Always review the nameplate and wiring diagram on each unit for proper voltage and control configurations This information is determined from the comp...

Страница 4: ...be tilted toward the drain nipple to ensure proper drainage NOTES A field fabricated secondary drain pan with a drain pipe routed to the outside of the building may be required in installations over a...

Страница 5: ...Disconnect all power supplies before servicing lock out tag out to prevent accidental electrical shock Note there may be multiple power sources Use copper conductors only Install all parts and panels...

Страница 6: ...s Damage can occur in the form of excessive heat build up and interference to the operation and moving parts will result 10 All piping made in the field should be installed with consideration of addit...

Страница 7: ...return air space is large enough that a negative pressure is not present however a trapped condensate line is recommended in case a negative condition should occur the unit would drain properly PIPING...

Страница 8: ...8 HBC X PHBC X RHBC X CHBC X Installation Operation and Maintenance Instructions FIGURE 1 Determination of Right Hand Left Hand References FIGURE 2 Coil Assemblies Right Hand Shown 3 2 Row 3 1 4 1 3 R...

Страница 9: ...r valves ceiling wall plenum or other accessories 3 All valves will operate at any angle with the exception of the motorized valve which must never be installed with the power head below horizontal Th...

Страница 10: ...am that is supplied with the unit Failure to do so could result in damage to components and will void all warranties Prior to starting the unit 1 Ensure supply voltage matches nameplate data 2 Ensure...

Страница 11: ...e filter with the same type as originally furnished COIL Any dust or other contaminants which accumulate on the heat transfer surfaces interferes with the air flow and impairs heat transfer The coil m...

Отзывы: