Stopping the Engine

1. Turn off and remove entire electrical loads. 
    Never start or stop the generator with 
    electrical devices plugged in or turned on.

    Let the generator run at no-load for two 
    minutes to stabilize internal temperatures 
    of the engine and generator.

2. Turn the fuel selector switch to 

OFF

 (

O

)position.

GAS

LPG

10. Allow generator to run at no load for few

  

minutes upon each initial start-up to permit 

    engine and generator to stablize.

Connecting Electrical Loads

This unit has been pretested and adjusted to 
handle its full capacity. Before starting the 
generator, disconnect all load. Apply load only 
after generator is running. Voltage is regulated 
via the engine speed adjusted at the factory for 
correct output. Readjusting will void warranty.

1.Let engine stabilize and warm up for a few 
   minutes after starting.
2.Ensure circuit breaker on control panel is in 
   on position.
3.Plug in and turn on the desired 120  Volt 
   AC, single phase, 60Hz electrical loads. It is 
   better to attach the item with largest load first.

CAUTION

When applying a load, do not exceed the maximum 
wattage rating of the generator when using one or 
more receptacles. Also, do not exceed the amperage 
rating of any one receptacle.
Do not apply heavy electrical load during break-in 
period (the first five hours of operations).

Connecting  a  generator  to  your  electric  utility 
company's power lines or to another power source 
may be against the law. In addition this action, if 
done  incorrectly,  could  damage  your  generator 
and  appliances  and  could  cause  serious  injury  or 
even death to you or a utility worker who may be 

working on nearby power lines. If you plan to run 
a  portable  electric  generator  during  an  outage, 
please  notify  your  electric  utility  company 
immediately and remember to plug your appliances 
directly  into  the  generator.  Do  not  plug  the 
generator  into  any  electric  outlet  in  your  home. 
Doing  so  could  create  a  connection  to  the  utility 
company  power  lines.  You  are  responsible  for 
ensuring that your generator's electricity does not 
feed back into the electric utility power lines. If the 
generator will be connected to a building electrical 
system,  consult  your  local  utility  company  or  a 
qualified  electrician.  Connections  must  isolate 
generator  power  from  utility  power  and  must 
comply with all applicable laws and codes.

 
    3. Fully close the LPG cylinder knob.

Содержание H05751

Страница 1: ...and level before performing any maintenance or service IMPORTANT Record product information to reference when ordering parts or obtaining warranty coverage Serial Number DUAL FUEL GENERATOR MODEL NUMB...

Страница 2: ......

Страница 3: ...tion Connecting to a Building s Electrical Maintenance And Storage 27 Maintenance Schedule 27 Engine Maintenance 28 Change Engine Oil 28 Air Filter Maintenance 28 Spark Plug Maintenance 29 Cleaning Fu...

Страница 4: ...mation The manufacturer cannot possibly anticipate every possible circumstance that might involve a hazard The warnings in this manual and the tags and decals affixed to the unit are therefore not all...

Страница 5: ...SAFETY PRECAUTIONS Page 02 WARNING POISONOUS GAS HAZARD WARNING WARNING English Customer Service 1 844 FIRMAN1...

Страница 6: ...de and downwind far away from windows doors and vents Direct exhaust away from occupied spaces INCORRECT USAGE Do not operate in any of the following locations Near any door window or vent Garage Base...

Страница 7: ...OR DRAINING GASOLINE Turn generator engine OFF and let it cool at least 2 minutes before removing fuel cap Loosen cap slowly to relieve pressure in tank Fill or drain fuel tank outdoors DO NOT overfi...

Страница 8: ...T handle generator or electrical cords while standing in water while barefoot or while hands or feet are wet DO NOT allow unqualified persons or children to operate or service generator WARNING Exhaus...

Страница 9: ...Gasoline can cause a fire or explosion if ignited Gasoline is a liquid fuel but it s vapors can ignite Gasoline is a skin irritant and needs to be cleaned up immediately if spilled on skin or clothes...

Страница 10: ...N LPG under pressure is highly flammable and can cause a fire or explosion if ignited LPG is heavier than air and can accumulate in confined spaces and low places in the event of a leak LPG has a dist...

Страница 11: ...he axle pin A through the wheel B 3 Slide the axle pin A through the mount point on the frame and flat washer D 4 Secure the wheel and axle pin with the cotter pin C 5 Repeat steps 2 4 to attach anoth...

Страница 12: ...d 1 Verify the positive battery cable red boot is securely tightened to the positive battery post Make sure boot is over battery post 2 Remove bolt M5X12 and M5 nut from black cable ring 3 Remove viny...

Страница 13: ...Filter 6 439cc FIRMAN OHV Engine 7 Recoil Starter 8 9 10 11 12 13 10 0 Flat Free Wheel Oil Filler Cap Battery Outlet Cover Control Panel Handle 14 LPG Hose Connector Inlet English Customer Service 1 8...

Страница 14: ...Starting the engine successfully during these 4 minutes will turn the indicator light GREEN MUST HAVE SOLID RED INDICATOR LIGHT TO BE ABLE TO START THE GENERATOR THE GENERATOR CANNOT BE STARTED DURIN...

Страница 15: ...This should stop the flow of electricity making the lamp shut off The GFCI s indicator light comes off RESET TEST TEST MONTHLY FOLLOW DIRECTIONS RESET BUTTON Receptacle Outlet LED Indicator Light TES...

Страница 16: ...llon 37 2 oz 1 1L Counter Clockwise Facing P T O Float Brushed Polyurethane Type Yes 5700 GASOLINE 5700 LPG FIRMAN Rated Fequency 60Hz Oil Type See Add Engine Oil Section Spark Plug AN IMPORTANT MESSA...

Страница 17: ...l activate a warning device or stop the engine If generator shuts off and the oil level is within specifications check to see if generator is sitting at an angle that forces oil to shift Place on an e...

Страница 18: ...lines tank cap and fittings frequently for cracks or leaks Replace if necessary DO NOT light a cigarette or smoke when filling the fuel tank 1 Clean area around fuel fill cap remove cap 2 Slowly add u...

Страница 19: ...ut and result in a hazardous condition Do not use tape or any type sealant to seal the LPG hose connections Always position the cylinder so the connection between the valve and the regulator won t cau...

Страница 20: ...lso result due to the increased enrichment of the air fuel ratio Other high altitude issues can include hard starting increased fuel consumption and spark plug fouling To alleviate high altitude issue...

Страница 21: ...any Use a ground fault circuit interrupter GFCI in any damp or highly conductive area such as metal decking or steel work DO NOT touch bare wires or receptacles DO NOT use generator with electrical co...

Страница 22: ...the weather Keep exhaust pipe clear of foreign objects Keep generator away from open flame Keep generator on a stable and level surface WARNING Surge Protection Voltage fluctuation may impair the prop...

Страница 23: ...un at no load for few minutes upon each initial start up to permit engine and generator to stablize StartingtheGenerator RecoilStart LPG 1 Before starting the generator check for loose or missing part...

Страница 24: ...EEN 6 Disconnect all electrical loads from the generator Never start or stop the generator with electrical devices plugged in or turned on 7 Move choke lever located on engine to START position NOTE D...

Страница 25: ...ctor switch is turned to the GAS position the indicator light will become RED up to 4 minutes before goes off Starting the engine successfully during these 4 minutes will turn the indicator light GREE...

Страница 26: ...g the engine successfully during these 4 minutes will turn the indicator light GREEN 6 Disconnect all electrical loads from the generator Never start or stop the generator with electrical devices plug...

Страница 27: ...do not exceed the maximum wattage rating of the generator when using one or more receptacles Also do not exceed the amperage rating of any one receptacle Do not apply heavy electrical load during bre...

Страница 28: ...STARTED DURING BATTERY POWER SAVING MODE UNLESS THE FUEL SELECTOR SWITCH IS TURNED TO THE OFF POSITION AND THEN TURNED BACK TO THE GAS OR LPG POSITION Unwanted Shutdown The generator cannot be started...

Страница 29: ...ufficient fuel flow to the engine This is not an indication of a problem with the generator but only a problem with the flow of gas from the LPG cylinder If generator performance seems to be deteriora...

Страница 30: ...ormance and extend the life of the generator See any authorized dealer for service The generator s warranty does not cover items that have been subjected to operator abuse or negligence To receive ful...

Страница 31: ...o cause skin cancer in certain laboratory animals Thoroughly wash exposed areas with soap and water a Drain oil by removing the drain plug and the oil filler cap while the engine is warm Change engine...

Страница 32: ...replacement parts Exhaust heat gases could ignite combustibles structures or damage fuel tank causing a fire resulting in death or serious injury and or property Contact with muffler area could cause...

Страница 33: ...and attach with the screws Spark arrester screen Flange Screw Battery Replacement 1 Remove the spark plug wire from spark plug 2 Remove the nut and bolt from the negative and positive posts 3 Loosen...

Страница 34: ...rator This product is equipped with an automatic battery charging circuit The battery will receive charging voltage when the engine is running The battery will maintain a proper charge if the unit is...

Страница 35: ...esh gasoline 7 Connect wire to spark plug 8 Replace spark plug 9 Drain gas tank and carburetor fill with fresh gasoline 10 Wait 5 minutes and re crank engine 11 Contact authorized service facility 12...

Страница 36: ...Page 33 PARTS DIAGRAM AND PART LIST H05751 PARTS DIAGRAM English Customer Service 1 844 FIRMAN1...

Страница 37: ...Page 34 439cc DUAL FUEL ENGINE PARTS DIAGRAM English Customer Service 1 844 FIRMAN1...

Страница 38: ...Lock Pin Front Cover Plate Frame Nut M8 Flange Bolt M8 35 1 1 5 1 1 1 1 1 1 1 1 1 2 1 2 1 1 3 4 8 4 2 2 2 1 1 5 4 1 19 1 2 1 1 1 2 2 2 1 1 1 4 1 1 4 4 4 1 2 1 1 1 1 1 7 1 1 1 1 1 1 1 1 2 2 2 1 1 8 2...

Страница 39: ...1 2 1 1 1 1 2 3 1 1 4 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 3 2 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 2 2 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 Crankcase Comp Locating Pins Oil Level Sensor Flg Bolt M6 12 Cams...

Страница 40: ...ranty Do Not Return the Unit to the Place of Purchase Contact the FIRMAN Service Center and FIRMAN will troubleshoot any issue via phone or e mail If the problem is not corrected by this method FIRMAN...

Страница 41: ...wear items accessory parts failures due to acts of God and other force majeure events beyond the manufacturer s control problems caused by parts that are not original FIRMAN parts WeareFIRMANPOWER And...

Страница 42: ...n emissions related parts is as follows 1 Any warranted part that is not scheduled for replacement as required maintenance in the owner s manual supplied is warranted for the warranty period stated ab...

Страница 43: ...esult in eligible warranty service being performed 1 Ignition system including Spark plug Ignition coil 2 Fuel metering system Fuel tank Fuel cap Fuel line and related fittings clamps Carburator assem...

Страница 44: ...P N 357745481 Rev 00 Firman Power Equipment Inc Peoria AZ 85381 www firmangenerators com 14131 N Rio Vista Blvd Suite 9...

Отзывы: