Page 11

NOTE:

Total power drawn from all receptacles must not exceed the name plate rating.

Engine Start Switch

 – Used to start engine

from  the  starter  motor(Electric  start  model
only).  To  start  engine,  press  and  hold  the 
switch  in  the  “

START

”(

ll

)  position,  the 

engine will crank and attempt to start. When 
the  engine  starts,  release  the  switch  to  the 

RUN

”(

l

) position.

Control Panel

English                                                                                                                                                  Customer Service: 1-844-FIRMAN1

1

Fuel Selector Switch

 – Used to select and 

turn on gasoline or LPG fuel source.

3-1 Data-Minder(Multi-Meter) – 

Push the 

SELECT

 

button to show the Voltage, Hertz 

and running hours.

5

6

120V, 30A Twist-Lock 

 (NEMA L5-30R) 

Maximum full load 30 Amp current may be 
drawn from this 120 Volt receptacle.

7

8

Indicator Light

When the fuel selector switch is turned to the 

GAS”

 or “

LPG”

 position, the indicator light will 

become 

RED

 up to 

4 minutes

(before goes off).

Starting  the  engine  successfully  during  these 

4 minutes

 will turn the indicator light 

GREEN

.

MUST HAVE 

SOLID RED INDICATOR LIGHT

 

TO BE ABLE TO START THE GENERATOR. THE 
GENERATOR CANNOT BE STARTED DURING 

BATTERY  POWER  SAVING  MODE

  UNLESS 

THE FUEL SELECTOR SWITCH IS TURNED TO 
THE  “

OFF

”  POSITION  AND  THEN  TURNED 

BACK TO THE “

GAS

” OR “

LPG

” POSITION.

See 

Indicator light

-

Battery power Saving 

Mode

 section for more information.

3

4

2

1

11

5

6

7

8

9

10

Ground  Fault  Circuit  Interrupter  conforms  to  UL  943, 
and  NEC  requirements.  This  device  protects 
you  against  hazardous  electrical  shock  that  may  be 
caused  if  your  body  becomes  a  path  through  which 
electricity  travels  to  reach  ground.  This  could  happen 
when  you  touch  an  appliance  or  cord  that  is  “  live  “ 
through faulty mechanism, damp or worn insulation, etc. 

120V, 20A Duplex GFCI (Ground Fault 
Circuit  Interrupter)

  –  (NEMA  5-20R)

This  receptacle  is  rated  so  that  a  total  of  20  amps 
may be drawn regardless of whether both halves or 
just one receptacle is used. 

Ground Terminal

 – Consult an electrician 

for local grounding regulations.

Содержание H05751

Страница 1: ...and level before performing any maintenance or service IMPORTANT Record product information to reference when ordering parts or obtaining warranty coverage Serial Number DUAL FUEL GENERATOR MODEL NUMB...

Страница 2: ......

Страница 3: ...tion Connecting to a Building s Electrical Maintenance And Storage 27 Maintenance Schedule 27 Engine Maintenance 28 Change Engine Oil 28 Air Filter Maintenance 28 Spark Plug Maintenance 29 Cleaning Fu...

Страница 4: ...mation The manufacturer cannot possibly anticipate every possible circumstance that might involve a hazard The warnings in this manual and the tags and decals affixed to the unit are therefore not all...

Страница 5: ...SAFETY PRECAUTIONS Page 02 WARNING POISONOUS GAS HAZARD WARNING WARNING English Customer Service 1 844 FIRMAN1...

Страница 6: ...de and downwind far away from windows doors and vents Direct exhaust away from occupied spaces INCORRECT USAGE Do not operate in any of the following locations Near any door window or vent Garage Base...

Страница 7: ...OR DRAINING GASOLINE Turn generator engine OFF and let it cool at least 2 minutes before removing fuel cap Loosen cap slowly to relieve pressure in tank Fill or drain fuel tank outdoors DO NOT overfi...

Страница 8: ...T handle generator or electrical cords while standing in water while barefoot or while hands or feet are wet DO NOT allow unqualified persons or children to operate or service generator WARNING Exhaus...

Страница 9: ...Gasoline can cause a fire or explosion if ignited Gasoline is a liquid fuel but it s vapors can ignite Gasoline is a skin irritant and needs to be cleaned up immediately if spilled on skin or clothes...

Страница 10: ...N LPG under pressure is highly flammable and can cause a fire or explosion if ignited LPG is heavier than air and can accumulate in confined spaces and low places in the event of a leak LPG has a dist...

Страница 11: ...he axle pin A through the wheel B 3 Slide the axle pin A through the mount point on the frame and flat washer D 4 Secure the wheel and axle pin with the cotter pin C 5 Repeat steps 2 4 to attach anoth...

Страница 12: ...d 1 Verify the positive battery cable red boot is securely tightened to the positive battery post Make sure boot is over battery post 2 Remove bolt M5X12 and M5 nut from black cable ring 3 Remove viny...

Страница 13: ...Filter 6 439cc FIRMAN OHV Engine 7 Recoil Starter 8 9 10 11 12 13 10 0 Flat Free Wheel Oil Filler Cap Battery Outlet Cover Control Panel Handle 14 LPG Hose Connector Inlet English Customer Service 1 8...

Страница 14: ...Starting the engine successfully during these 4 minutes will turn the indicator light GREEN MUST HAVE SOLID RED INDICATOR LIGHT TO BE ABLE TO START THE GENERATOR THE GENERATOR CANNOT BE STARTED DURIN...

Страница 15: ...This should stop the flow of electricity making the lamp shut off The GFCI s indicator light comes off RESET TEST TEST MONTHLY FOLLOW DIRECTIONS RESET BUTTON Receptacle Outlet LED Indicator Light TES...

Страница 16: ...llon 37 2 oz 1 1L Counter Clockwise Facing P T O Float Brushed Polyurethane Type Yes 5700 GASOLINE 5700 LPG FIRMAN Rated Fequency 60Hz Oil Type See Add Engine Oil Section Spark Plug AN IMPORTANT MESSA...

Страница 17: ...l activate a warning device or stop the engine If generator shuts off and the oil level is within specifications check to see if generator is sitting at an angle that forces oil to shift Place on an e...

Страница 18: ...lines tank cap and fittings frequently for cracks or leaks Replace if necessary DO NOT light a cigarette or smoke when filling the fuel tank 1 Clean area around fuel fill cap remove cap 2 Slowly add u...

Страница 19: ...ut and result in a hazardous condition Do not use tape or any type sealant to seal the LPG hose connections Always position the cylinder so the connection between the valve and the regulator won t cau...

Страница 20: ...lso result due to the increased enrichment of the air fuel ratio Other high altitude issues can include hard starting increased fuel consumption and spark plug fouling To alleviate high altitude issue...

Страница 21: ...any Use a ground fault circuit interrupter GFCI in any damp or highly conductive area such as metal decking or steel work DO NOT touch bare wires or receptacles DO NOT use generator with electrical co...

Страница 22: ...the weather Keep exhaust pipe clear of foreign objects Keep generator away from open flame Keep generator on a stable and level surface WARNING Surge Protection Voltage fluctuation may impair the prop...

Страница 23: ...un at no load for few minutes upon each initial start up to permit engine and generator to stablize StartingtheGenerator RecoilStart LPG 1 Before starting the generator check for loose or missing part...

Страница 24: ...EEN 6 Disconnect all electrical loads from the generator Never start or stop the generator with electrical devices plugged in or turned on 7 Move choke lever located on engine to START position NOTE D...

Страница 25: ...ctor switch is turned to the GAS position the indicator light will become RED up to 4 minutes before goes off Starting the engine successfully during these 4 minutes will turn the indicator light GREE...

Страница 26: ...g the engine successfully during these 4 minutes will turn the indicator light GREEN 6 Disconnect all electrical loads from the generator Never start or stop the generator with electrical devices plug...

Страница 27: ...do not exceed the maximum wattage rating of the generator when using one or more receptacles Also do not exceed the amperage rating of any one receptacle Do not apply heavy electrical load during bre...

Страница 28: ...STARTED DURING BATTERY POWER SAVING MODE UNLESS THE FUEL SELECTOR SWITCH IS TURNED TO THE OFF POSITION AND THEN TURNED BACK TO THE GAS OR LPG POSITION Unwanted Shutdown The generator cannot be started...

Страница 29: ...ufficient fuel flow to the engine This is not an indication of a problem with the generator but only a problem with the flow of gas from the LPG cylinder If generator performance seems to be deteriora...

Страница 30: ...ormance and extend the life of the generator See any authorized dealer for service The generator s warranty does not cover items that have been subjected to operator abuse or negligence To receive ful...

Страница 31: ...o cause skin cancer in certain laboratory animals Thoroughly wash exposed areas with soap and water a Drain oil by removing the drain plug and the oil filler cap while the engine is warm Change engine...

Страница 32: ...replacement parts Exhaust heat gases could ignite combustibles structures or damage fuel tank causing a fire resulting in death or serious injury and or property Contact with muffler area could cause...

Страница 33: ...and attach with the screws Spark arrester screen Flange Screw Battery Replacement 1 Remove the spark plug wire from spark plug 2 Remove the nut and bolt from the negative and positive posts 3 Loosen...

Страница 34: ...rator This product is equipped with an automatic battery charging circuit The battery will receive charging voltage when the engine is running The battery will maintain a proper charge if the unit is...

Страница 35: ...esh gasoline 7 Connect wire to spark plug 8 Replace spark plug 9 Drain gas tank and carburetor fill with fresh gasoline 10 Wait 5 minutes and re crank engine 11 Contact authorized service facility 12...

Страница 36: ...Page 33 PARTS DIAGRAM AND PART LIST H05751 PARTS DIAGRAM English Customer Service 1 844 FIRMAN1...

Страница 37: ...Page 34 439cc DUAL FUEL ENGINE PARTS DIAGRAM English Customer Service 1 844 FIRMAN1...

Страница 38: ...Lock Pin Front Cover Plate Frame Nut M8 Flange Bolt M8 35 1 1 5 1 1 1 1 1 1 1 1 1 2 1 2 1 1 3 4 8 4 2 2 2 1 1 5 4 1 19 1 2 1 1 1 2 2 2 1 1 1 4 1 1 4 4 4 1 2 1 1 1 1 1 7 1 1 1 1 1 1 1 1 2 2 2 1 1 8 2...

Страница 39: ...1 2 1 1 1 1 2 3 1 1 4 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 3 2 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 2 2 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 Crankcase Comp Locating Pins Oil Level Sensor Flg Bolt M6 12 Cams...

Страница 40: ...ranty Do Not Return the Unit to the Place of Purchase Contact the FIRMAN Service Center and FIRMAN will troubleshoot any issue via phone or e mail If the problem is not corrected by this method FIRMAN...

Страница 41: ...wear items accessory parts failures due to acts of God and other force majeure events beyond the manufacturer s control problems caused by parts that are not original FIRMAN parts WeareFIRMANPOWER And...

Страница 42: ...n emissions related parts is as follows 1 Any warranted part that is not scheduled for replacement as required maintenance in the owner s manual supplied is warranted for the warranty period stated ab...

Страница 43: ...esult in eligible warranty service being performed 1 Ignition system including Spark plug Ignition coil 2 Fuel metering system Fuel tank Fuel cap Fuel line and related fittings clamps Carburator assem...

Страница 44: ...P N 357745481 Rev 00 Firman Power Equipment Inc Peoria AZ 85381 www firmangenerators com 14131 N Rio Vista Blvd Suite 9...

Отзывы: