High  Energy  Spark  Igniter  rod  should  be  fitted  such  that  the  tip  end  should  be  placed  at  a  distance  of  ~50  mm 
back from the stabilizer plate. High Tension Igniter should be placed closer to the stabilizer plate, at a distance of 
~10 mm. 

It should be noted that the rod tip positioning against the stabilizer plate in the pilot gas part assembly (pos. 1 
on Fig. 1) should be done outside the air tube only (do not install the rod in the gas head already mounted in 
the air tube). Only after proper rod positioning, should the rod be fixed by tightening the rod holding gland 
and the whole gas assembly with igniter rod inserted into the air tube pos. 4. 

The rods of both types of devices are held in the gas head by means of a fixing gland 1/2"BSP. 

The ignition device is not in gas pilot scope of supply. It is normally specified and ordered separately. 

5.  TECHNICAL DATA 

Fuel: two standard versions for Natural Gas (NG) and for Propane Gas or LPG (PG) - see gas characteristics in 

Appendix 1. In case of other fuel gas needed see p. 11 Ordering Information Special Pilots and Appendix 3. 

Outer diameter of the air tube 

48.0 mm 

Outer diameter of the mounting tube 

55.0 mm 

Outer diameter of the ignition rod 

16.0 mm 

Capacity range: 

Natural Gas 

20 ÷ 46 kW at 20 ÷ 80 kPa - see capacity vs. pressure graph in Appendix 1 

Propane Gas 

35 ÷ 74 kW at 20 ÷ 80 kPa - see capacity vs. pressure graph in Appendix 
1 - in case of other capacity range needed - see p. 11 for Special Pilots 

Air flow and pressure 

natural draught 

Gas connection 

1/2" BSP (inner thread) 

Operating temperature 

max. continuous 300°C, stabilizer, end of gas and air tube 500°C 

Igniter rod reference length range “L” 0.5 ÷ 2.0 m - longer upon request 

Pilot weight: P/N 

SP-48-NG/PG-ND- 0.5 

(length L=0.5 m): 3.00 kg, pilot weight adder: approx. 2,60 kg/m 

Material used for construction 

all parts: 304/316 SS and heat-resistant steel 310/330 SS 

Notes

1. If the above parameters are different than those required please contact Fireye 

2. For Imperial Units please refer to the Appendix 4 Unit Conversion Table 

3. Device complies with the requirements of the European Directive 2011/65/EU (RoHS 2) 

6.  OPERATIONAL SAFETY 

When operating and handling the pilot burner please follow the rules below: 

6.1 

Use pilot only for its intended purpose. 

 6.2 

At the time of installation, operation and maintenance follow the procedures described in the instructions 
and documentation of the pilot, ignition device and the main burner. 

6.3  

Check environmental conditions and ensure that the specified operating temperatures of pilot 
and igniter components will not be exceeded 

(

see p. 5 and igniter Manual). 

6.4  

Follow the warnings contained in the documentation. 

6.5  

Do not make any modifications or changes to the pilot construction. 

6.6 

Before starting, make sure that all parts of the pilot and electric ignition device are in good condition. 

6.7 

Circuits of power packs as well as igniter enclosures and junction boxes must be properly grounded. 

6.8 

Before igniting, check the tightness of gas tube connections. 

6.9 

During the observation of the pilot flame wear special goggles to protect the eyes from UV flame radiation. 

6.10  

Do not remove the protective ground when the ignition device is energized. 

6.11  

Before working on the ignition device, make sure that power is disconnected. 

6.12 

Before maintenance or repair works check if the gas shut-off valve is closed. 

6.13  

During installation, start-up or maintenance works on the pilot or burner/heater always wear protective 
clothing and use protective gloves

Содержание SureFire II SP-48-NG-ND

Страница 1: ...as or LPG gas is SP 48 PG ND xxx where xxx is the insertion length L from 0 5 to 2 0 metres see Appendix 1 the pilot capacity vs gas pressure graphs for Natural gas and Propane For other Fuel gas type...

Страница 2: ...e gas is supplied through the inlet 1 2 BSP to the gas head and to the gas tube and further to the orifice stabilizer assembly A small amount of gas leaves through the bleed orifice mounted in the gas...

Страница 3: ...ION SOURCES FOR GAS IGNITER LIGHT OFF SETTING METHOD Sources of ignition in the gas pilot SP 48 ND are electrical high energy spark igniters HESI or high tension igniters HTI equipped with the ignitio...

Страница 4: ...5 2 0 m longer upon request Pilot weight P N SP 48 NG PG ND 0 5 length L 0 5 m 3 00 kg pilot weight adder approx 2 60 kg m Material used for construction all parts 304 316 SS and heat resistant steel...

Страница 5: ...ng see Fig 2 If it is not possible to use one of mounting tubes proposed above a different type can be used bearing in mind that its inner diameter should be properly matched to the outer diameter of...

Страница 6: ...rmining the position of the complete pilot relative to the mounting tube the mounting tube clamping screws should be tightened to prevent the device from moving FIGURE 4 Gas head with ring gasket and...

Страница 7: ...if this happens adjust the air and gas or eventually the main burner air pressure in the windbox to stabilize the flame in the desired position and to stop the glow effect Flame should be as stable a...

Страница 8: ...e absence of the flame after trial for ignition the valves are closed and electrical igniter is switched off i Eventual repeating of trial for ignition sequence depends on the application Details of s...

Страница 9: ...e gas pilot does not operate correctly check the following a All manual gas valves on gas supply line were open and there is gas available b All valves in the supply line are functioning properly c Th...

Страница 10: ...enance of igniter contrary to the instructions in the user manual unauthorized igniter modifications or repairs made by unauthorized personnel use of components or spare parts other than original 11 6...

Страница 11: ...Fire IITM Pilot Mounting Tubes Spare Parts Part No Description SP 48 MTF Mounting Tube Flanged flange OD 80 length 120mm SP 48 MTW 150 Mounting Tube for Welding length 150 mm SP 48 MTW 600 Mounting Tu...

Страница 12: ...12 2020 Carrier APPENDIX No 1 The Pilot capacity vs gas pressure graphs standard version Remark The real measured capacity may differ by 5 depending on a particular pilot and measurement conditions...

Страница 13: ...lane Fig B Typical for refinery petrochem and industrial heaters shows position of SP 32 and SP 48 Gas Igniter operating as a continuous pilot on a sample main burner with gas spuds and central oil or...

Страница 14: ...nery gas Refinery Off Gas needs additional engineering and testing because their gas compositions and calorific values are different than these of NG PG and LPG taken for gas pilot design Moreover the...

Страница 15: ...x 35 315 cubic foot ft3 Air flow rate 1 cubic metre hour m3 h x 0 589 standard cubic foot min SCFM Weight 1 kilogram kg x 2 2046 pound lb Pressure 1 kilopascal kPa x 6 895 pound square inch gauge psig...

Страница 16: ...which is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIE...