TYPICAL NXM2G INSTALLATION PROCEDURES

When installing the NXM2G, the following procedures must be followed:

Remove the bottom wiring cover. Select the required conduit size and connections 
for the field wiring to the boiler controls and temperature sensors.

Use suitable screwed fasteners such as self tapping screws. Only use the holes provided 
in the wiring compartment for mounting the NXM2G.

For top mounting, use only mounting screws and brackets provided.

Use conduits to run wires to connect the boiler thermostat/s or boiler control panel to the
NXM2G.

Conduits must be used to run the flow and return sensor wires to the NXM2G.

Use colored multi-core cable to make the various connections between the boiler 
and the NXM2G.

Remove the plug connectors from the wiring compartment. As in 

Figure 1

. using the 

cable anchor provided, use cable ties to secure cables in the wiring compartment.

Connect mains L, N and E (Ground) to the connector and plug into the NXM2G as in 

Figure 1

The L, N and E (Ground) must be on the same electrical phase as the boiler/burner’s 
electrical supply.

WARNING: 

Do not use the internal PCB area to secure the NXM2G – doing so will 

warranty 

void the 

TIP: 

Before installing the temperature sensors inside the conduits, mark 
either or both the flow or return sensor(s) with colored tape at both ends 
of the cable(s). This helps to ensure correct orientation when inserting 
the plugs into the NXM2G connectors. i.e. the supply (flow) sensor plugs 
into the supply (flow) connector on the NXM2G and the return sensor 

into the return connector on the NXM2G. 

plugs 

Содержание NXM2G-2

Страница 1: ...de based on temperature and time which are both adaptive The NXM2G will also inhibit the burner from firing on stage 2 if the boiler load demand is low thus ensuring the best efficiency for the curren...

Страница 2: ...is not compromised Moreover the boiler set point is always maintained Should the NXM2G unit fail or lose electrical supply the boiler control system wir ing remains as normal and the boiler will opera...

Страница 3: ...d devices NXM2G SPECIFICATIONS The right to make changes in specification or design at any time without prior notice is hereby reserved NXM2G System Model NXM2G 2 Supply Voltage 230V AC 60Hz Rated Cur...

Страница 4: ...r LTHW boilers fired with on off forced draft burners two stage high low burners modulating burners Atmospheric boilers fired with two stage burners modulating burners Wiring Diagrams FIGURE 3 Typical...

Страница 5: ...5 FIGURE 4 Typical Wiring for single stage forced draft burner FIGURE 5 Typical Wiring for 2 stage High Low force draft boiler 7 0 A max 3 7 0 A max 3 4 5...

Страница 6: ...n When choosing a place to locate the NXM2G ensure that 1 The position of the NXM2G does not obstruct the boiler access panels used for maintenance 2 The NXM2G LEDs can be viewed without restriction C...

Страница 7: ...onnections between the boiler and the NXM2G Remove the plug connectors from the wiring compartment As in Figure 1 using the cable anchor provided use cable ties to secure cables in the wiring compartm...

Страница 8: ...onnections this should be as close to the boiler as possible This may require the pipe work insulation to be removed Using appropriate banding clamp secure the sensors to the pipe Please note Do not o...

Страница 9: ...will allow the burner boiler to start without interruption i e not in save mode when the NXM2G is powered for the first time see Figure 6 5 Operate the boiler thermostat boiler firing to stop the boil...

Страница 10: ...10 NXM2G IN OPERATION FIGURE 6 NXM2G Operation Status LED s...

Страница 11: ...ring during first firing follow flowchart in Figure 7 2 3 Boiler Burner fires during first firing only and will not re fire thereafter follow flowchart in Figure 7 3 4 Boiler Burner fires in normal wa...

Страница 12: ...12 FIGURE 7 2 NXM2G Power supply correct red LED on however boiler will not fire during First Firing FIGURE 7 3 Boiler Burner fires during First firing only and will not re fire thereafter...

Страница 13: ...Boiler Burner fires in normal way without NXM2G operating in Save mode after first firing FIGURE 7 5 NXM2G Operates Boiler Burner but Thermostat on and Boiler firing LED s remain on when the boiler i...

Страница 14: ...any product or part thereof except lamps elec tronic tubes and photocells which is found defective in material or workmanship or which otherwise fails to conform to the description of the product on t...

Отзывы: