The EP177 Programmer Module provides early spark termination for the spark ignition that is con-
nected to terminal 5. The EP177 also waits indefinitely for the M-D low fire start switch to close.
This programmer model also provides a number of operational characteristics that are selected via
the ED510 Keypad/Display rather than by dipswitch selection.
When in a modifiable selection, the RESET key is used to enter the modify mode, the SCRL key is
used to modify the value and the RESET key is used to save the value.
The following is a list of the programmable functions associated with the EP177 Programmer 
Module:

— Selectable purge (selectable from 30 seconds to 37 minutes – default setting is 30 seconds).
— Prove the operation of the 3-P Running Interlock Circuit at start.
— Terminal 6 operation - Interrupted / Intermittent operation of pilot valve – default is inter-

rupted.

— Prove the operation of the High Fire Purge Interlock (D-8).
— Prove the operation of the Low Fire Start Interlock (M-D).
— Purge Count method, UP or DOWN – default is down.
— Selectable Post Purge Timing of 1, 15, 30, 45 or 60 seconds – default is 15 seconds.

13(-*=-2+8,)463+6%11)6

1.

Insert the EP177 programmer module into the EB700 chassis and connect the ED510 Keypad/
Display.

2.

Open the operating control (L1-13) circuit. The EP177 cannot be modified unless the operating
control is open.

3.

The PROGRAM SETUP sub-menu will be used to display the programmable functions. Press

the SCRL key until the PROGRAM SETUP sub-menu is displayed. 

4.

Press the MODE key to enter the PROGRAM SETUP sub-menu. The SCRL key will advance

through the selections in the sub-menu. The first four items displayed in the sub-menu are PRO-

GRAMMER TYPE EP177, ENGR CODE, AMPLIFIER TYPE, and FFRT TIME 4 S. These
items are not programmable.

5.

Press the SCRL key and the next item displayed (and first programmable item) is PURGE
TIME followed by the current setting (default setting = 30 seconds). 

6.

Press and hold the RESET button for 1 second to enter the “Modify” mode (providing the con-
trol was not in a lockout condition). After a 2-3 second delay, the control will display SCRL TO
MODIFY on the top line of the display (replacing STANDBY). 

7.

Press the SCRL key to advance through the allowable selections. The selections will roll over

from the last selection to the first one. 

8.

Press and hold the RESET button for one second to choose and store in memory the appropriate
selection.

9.

The SCRL key will advance through the following selections. Follow steps 1 through 8 to mod-
ify the selections.

The program sequence timings of the EP177 are the same as the EP170 programmer.
The EP177 provides the following adjustments made via the ED510 keypad.
 PURGE TIME

30s, 1m, 3m, 5m, 7m, 9m, 10m, 12m, 15m, 16m, 18m, 20m, 22m, 25m, 
27m, 30m, 32m, 35m, 37m.

                                 default is 30s

Pre-purge time begins after the open damper proving switch (8) is detected closed.

PROVE 3-P OPEN             Y/N                          

default is N

The non-recycling interlocks wired between terminals 3 and P must be open at the start of a cycle.
TERMINAL 6 =                INTRP/INTMT

   

default is INTRP (interrupted)

Содержание EP160

Страница 1: ...ate a safety lockout if any of these circuits are open at the improper point in the control cycle The programmer module will de energize all fuel valve circuits within four 4 seconds max fol lowing a...

Страница 2: ...de is located on the back side of the board in the lower right hand corner The EP163 programmer requires the ED510 display for initial configuration programming 4463 07 Underwriters Laboratories Inc M...

Страница 3: ...VQ 7IG 7IG 7IG 8IVQ 7IG 7IG 4 7IG 8IVQ 7IG h 7IG 8IVQ 7IG 7IG 4 7IG 8IVQ 7IG h 7IG 8IVQ 7IG 7IG 4 4 4 7IG 8IVQ 7IG h 7IG 8IVQ 7IG 7IG 4YVKI XMQMRKW EVI EHNYWXEFPI 7II q MTW MXGLIW h 4YVKI 8MQMRK r 68...

Страница 4: ...32 0 7 037 1 6 2 4 6 3 0 3 18 7 48 7 18 7 496 7 1 8 6 1 2 0 7 4378 496 7 03 983 03 13 90 836 13836 6 9 8 7 037 47 8 7 88 2 7 00 7 88 2 7 6 2 8 EGXSV HIJEYPX ZEPYIW EVI WLS R 496 48 18 ERH 4SWX 4YVKI X...

Страница 5: ...2 0 32 0 7 037 1 6 2 4 6 3 0 3 18 7 48 7 496 7 1 8 6 1 2 0 7 4378 496 7 7 037 1 2 7 03 983 03 13 90 836 13836 6 9 8 48 7 47 8 7 88 2 7 00 7 88 2 7 6 2 8 EGXSV HIJEYPX ZEPYIW EVI WLS R 496 48 18 ERH 4S...

Страница 6: ...ing the dipswitches for a particular application should be made by a competent professional such as a Boiler Burner technician licensed by a state or other govern ment agency engineering personnel of...

Страница 7: ...en open at the start of purge before the Flame Monitor will drive the firing rate motor to the high fire position at which time the switch must then be proven closed If the D 8 inter lock circuit is c...

Страница 8: ...low switch to close and if not closed will go into lockout The EP programmers utilize the open damper switch interlock D 8 to determine the wait time for the air flow switch to close If at the start o...

Страница 9: ...40 seconds Prove the operation of the 3 P Running Interlock Circuit Prove the operation of the High Fire Purge Interlock D 8 Prove the operation of the Low Fire Start Interlock M D Selectable timings...

Страница 10: ...oth terminal 5 and 6 The control will begin MTFI as soon as flame is detected following 2 second check at the start of PTFI For example 3 seconds into PTFI flame signal detected terminal 7 is energize...

Страница 11: ...e programmable functions Press the SCRL key until the PROGRAM SETUP sub menu is displayed 4 Press the MODE key to enter the PROGRAM SETUP sub menu The SCRL key will advance through the selections in t...

Страница 12: ...ctions are 00 through 15 Default selection is 00 ACCEPT SETTINGS N Available selections are Yes Y and No N No is the default selection If selected Y the system will accept the current settings overrid...

Страница 13: ...the burner linkages pilot assembly etc Refer to Bulletin E 1101 for a complete description of the Check Run Switch SQQYRMGEXMSR RXIVJEGI ERH R8SYGL MVIPIWW 1SRMXSVMRK 7 WXIQ Programmer modules include...

Страница 14: ...6 13 97 31192 8 327 The protocol to be used is Modbus RTU This is implemented by the master PC PLC etc issuing a poll to the slave Flame Monitor and the slave responding with the appropriate message A...

Страница 15: ...RIW 8MQIV 8 TI 8 1 6 8MQI PEQI HHVIWW 0 1 PEQI 7MKREP 03 78 8 YVVIRX PSKMG QSHYPI 496 48 983 WII 8EFPI 24987 RTYX PMQMXW WXEXI 3984987 3YXTYX VIPE W WXEXI 7 71 27 7 WXIQ SR QMRYXIW 261 27 YVRIV SR QMR...

Страница 16: ...in purge a flame signal or meaningless Only the lower nibble of GSTAT has any value If this value is 0 then the TIMER value has no meaning The value in TIMER is a background minute timer in the Flame...

Страница 17: ...flame ceases or lockout occurs MPREPURGE1 is the period of time prior to PURGE where the control checks the status of the air flow interlocks or the high fire proving switch D 8 If either switch is fo...

Страница 18: ...7 34 2 07 0 1 03 398 0 1 7 2 0 48 0 1 8 1 PS 0 1 8 983 0 1 7 2 0 48 03 6 7 2 0 983 0 1 7 2 0 18 0 1 0 983 4 280 34 2 30 496 9 0 0 78 8 2 4 27 32 13 90 1 77 7 4 6 03 34 2 4 8 6 4 03 8 6 4 7 46 7796 4 0...

Страница 19: ...lf test diagnostics for 15 seconds 7XEVX 9T 2SVQEP GPI 4 4VSKVEQQIV Note For direct spark ignited oil burners substitute the words Main Oil Valve for Pilot Valve 1 Constant 120 VAC should be wired to...

Страница 20: ...ed after ten seconds the control will de energize Terminals 5 and 6 and lockout When flame is detected during this 10 second period the ED510 will display PTFI 20 FLAME SIGNAL 9 With flame proven at t...

Страница 21: ...nd the D 8 circuit is closed at the start of the purge period the control will hold for ten 10 seconds waiting for the D 8 circuit to open If after ten 10 seconds the D 8 circuit does not open the con...

Страница 22: ...GYMX 4PYK R PEQI QTPMJMIV PEQI 6SH 3RP 6 6 2 7 8 61 2 07 14368 28 SSH EVXL VSYRH MW WWIRXMEP MWGSRRIGX 1IERW RH 3ZIVPSEH 4VSXIGXMSR 308 2 2SXI LIR PEQI 6SH SV TLSXSGIPP MW YWIH YQTIV 7 8S XLI KVIIR KV...

Страница 23: ...23 MVMRK 0 1 132 836 XS E Q MVMRK 6EXI EQTIV 1SXSV 10 X 12 11 31 03 983 F 0 1 132 836 8 61 2 07 Q 13836 Q 3286300 6...

Страница 24: ...ells which is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARR...

Отзывы: