background image

2

AGENCY ALARM PLACEMENT RECOMMENDA

TIONS

Invensys Controls Americas recommends complete coverage protection achieved by
installing a smoke alarm in every room of your home.

The National Fire Protection Association’s (NFPA) minimum 
requirement, as stated in Standard 72, Chapter 2, reads as follows:

“2-2.1.1.1 Smoke detectors shall be installed
outside of each separate sleeping area in the
immediate vicinity of the bedrooms and on
each additional story of the family living unit
including basements and excluding crawl
spaces and unfinished attics. In new construc-
tion a smoke detector also shall be 
installed in each sleeping room.”

Chapter 2 also reads as follows:

“2-2.2.1 In new construction, where more than one smoke detector is required by 2-
2.1, they shall be so arranged that operation of any smoke detector shall cause the
alarm in all smoke detectors within the dwelling to sound.”

“2.5.2.1 The required number of smoke detectors might not provide reliable early
warning protection for those areas separated by a door from the areas protected by
the required smoke detectors. For this reason it is recommended that the household-
er consider the use of additional smoke detectors for those areas for increased pro-
tection. The additional areas include the basement, bedrooms, dining room, furnace
room, utility room and hallways not protected by the required smoke detectors. The
installation of  smoke detectors in kitchens, attics (finished or unfinished), or garages
is not normally recommended, as these locations occasionally experience conditions
that can result in improper operation.”

This equipment should be installed in accordance with the National Fire Protection
Association’s Standard 72, NFPA, Batterymarch Park, Quincy, MA 02269.

THIS STANDARD MEANS YOU SHOULD INSTALL AND USE A SMOKE ALARM IN
EVERY ROOM AND AREA OF YOUR HOUSEHOLD OR 
BUILDING FOR BEST PROTECTION.

The NFPA, 1993 Edition, Appendix A further states:

“The required number of smoke detectors may not provide reliable early warning
protection for those areas separated by a door from the areas protected by the
required smoke detectors. For this reason, it is recommended that the house holder
consider the use of additional smoke detectors for those areas for increased protec-
tion. The additional areas include: basement, bedrooms, dining room, furnace room,
utility room, and hallways not protected by the required smoke detectors.”

Also, as required by the California State Fire Marshal:

“Early warning fire detection is best achieved by the installation of fire detection
equipment in all rooms and areas of the household as follows: a smoke detector
installed in each separate sleeping area (in the vicinity, but outside the bedrooms),
and heat or smoke detectors in the living rooms, dining rooms, bedrooms, kitchens,
hallways, attics, furnace rooms, closets, utility and storage rooms, basements and
attached garages.

Important Smoke Alarm Placement 
and Exception Information

• Install a smoke alarm as close to the center of the

ceiling as possible. If this is not practical, mount no
closer than 4 inches from a wall or corner. Also, if
local codes allow, install smoke alarms on walls,
between 4 and 12 inches from ceiling/wall
intersections.

• Install a minimum of two smoke alarms in every

home, no matter how small the home. New con-
struction codes require a minimum of two intercon-
nected smoke alarms in newly built homes.

• Install a smoke alarm in each room that is divided by a partial wall (either coming

down from the ceiling at least 24 inches, or coming up from the floor). 

• Install smoke alarms on peaked, cathedral, or gabled ceilings 3 feet from the

highest point (measured horizontally). 

Install a smoke alarm in lived-in attics or attics which house electrical equipment
like furnaces, air conditioners, or heaters.

SMOKE ALARM

COMBO SMOKE/CARBON MONOXIDE ALARM 

Key

CARBON MONOXIDE ALARM 

4 IN

(0.1m )

4 IN

(0.1m )

MINIMUM

12 IN

(0.3 m )

MAXIMUM

CEILING

SIDE

WALL

ACCEPTABLE HERE

NEVER HERE

TOP OF DETECTOR

ACCEPTABLE HERE

KITCHEN

DINING 
ROOM

BEDROOM

BEDROOM

BEDROOM

LIVING ROOM

BEDROOM

BEDROOM

LIVING
ROOM

DINING
ROOM

BASEMENT

HALL

/

TV ROOM

DINING 
ROOM

KITCHEN

BEDROOM

BEDROOM

BEDROOM

LIVING ROOM

For best protection, install a smoke alarm in EVERY room. 

In addition, we recom-

mend that all smoke alarms be interconnected.

Different Types of Smoke Alarms

Ionization alarms are generally more effective at detecting fast, flaming fires that
consume combustible materials rapidly and spread quickly. Sources of these fires
may include flammable liquids or paper burning in a waste container.
Photoelectric alarms are generally more effective at detecting slow, smoldering
fires that smolder for hours before bursting into flame. Sources of these fires may
include cigaretts burning in couches or bedding.  

However, both types of

alarms provide adequate detection of both types of fires.

If you desire the earliest detction of both smoldering fires and fast flaming fires,
you should install smoke alarms that combine both photoelectric and ionization
sensing technologies in one unit.

Содержание FADCM

Страница 1: ...uld this occur You must still test the alarm weekly to verify proper horn operation Trigger Alarm Locator TAL Most interconnect tests trigger all alarm horns simultaneously for the duration of the test This unique system alternates between a 10 second ALL ON cycle and a 50 second cycle where only the initiating alarm is sounding Alarm Controlled Interconnect Test In an interconnected system this f...

Страница 2: ...red by the California State Fire Marshal Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows a smoke detector installed in each separate sleeping area in the vicinity but outside the bedrooms and heat or smoke detectors in the living rooms dining rooms bedrooms kitchens hallways attics furnace rooms closet...

Страница 3: ...rms can only sound their alarms when they detect CO gas They do not sense heat flame or any gas other than carbon monoxide CO This alarm is designed to give audible warning that a dangerously high level of CO is present You must respond immediately to the CO alarm horn Smoke and CO alarms have limitations This alarm is not foolproof and is not war ranted to protect lives or property from fire Smok...

Страница 4: ...d 3 Interconnected AC Only and AC DC Alarms 1 Remove the mounting plate Hold the alarm and turn the mounting plate clockwise to separate it from the back of the alarm 2 Hold the mounting plate against the ceiling or wall in the desired position and use a pencil to trace the inside of the mounting slots 3 Use a 3 16 5mm drill bit to drill through the center of the outlines you made in Step 2 4 Inse...

Страница 5: ...OT PRESENT FOR ANY REASON AC POWERED SMOKE CO OR HEAT ALARMS WILL NOT OPERATE THIS ALARM SHOULD BE INSTALLED IN ACCORDANCE WITH THE NATIONAL FIRE PROTECTION ASSOCIATION S STANDARD 72 National Fire Protection Association One Batterymarch Park Quincy MA 02269 Connect CO and smoke alarms to a single dedicated AC branch circuit If local codes do not permit such a wiring configuration or connection be ...

Страница 6: ... a false alarm TO TEMPORARILY SILENCE AN ALARM NOTE These features temporarily quiet alarms but do not disable the sensor When you push the Smart Button during an alarm one of three things will happen 1 All interconnected alarms are silenced This means you pushed the button on the unit that actually triggered alarm Quick Quiet False Alarm Contro l 2 One unit still sounding an alarm the rest are si...

Страница 7: ...ving power and functioning properly 3 Alarm interconnect circuit problem Replace and retest 4 On DC battery powered interconnected alarms remove alarm from mounting bracket and check that the connector plug is securely attached 5 On an interconnected series with both AC and AC DC powered units wiring may have been improperly connected Have wiring checked by a licensed electrician Retest all alarms...

Страница 8: ...G AND MAINTENANCE Push the Smart Button to temporarily quiet the low battery signal for 10 hours The horn beeps once then two beeps then three beeps pauses and then sounds the full alarm when using the Smart Button to test The alarm is operating properly The Firex patented Horn Ramp Up feature lets you start the test sequence and move away from the unit before the full alarm horn sounds Alarm soun...

Страница 9: ...ds the CO poisoning because they stay in the home where CO is present As CO levels rise the symptoms become more extreme At low levels people will suffer headaches and mild nausea At higher levels unconsciousness heart failure and even death can occur The following symptoms are related to CARBON MONOX IDE POISONING and should be discussed with ALL members of the household Mild Exposure Slight head...

Страница 10: ...r this combination alarm Doing so will void your warranty If the alarm is not operating properly see Troubleshooting If you must return an alarm under warranty send the alarm in a well padded envelope with postage prepaid a note describing the nature of the difficulty and proof of date of purchase to In U S In Canada Invensys Controls Americas Invensys Controls Americas 28C Leigh Fisher Blvd Servi...

Отзывы: