background image

Duct Unit Installation

DUCT SMOKE LOCATION PRE-REQUISITES:

This guideline contains general information on duct smoke detector installation, but does not preclude the NFPA documents listed.  Maple Chase
Company assumes no responsibility for improperly installed duct detectors.  To determine the correct installation position for a Firex Duct Smoke
Detector, the following factors must be considered.

1)  

A uniform non turbulent airflow of between 500 ft/min to 4000 ft/min. must be present in the HVAC duct.  To determine the duct
velocities examine the engineering specifications that define the expected velocities or use an Alnor model 6000P
velocity/meter (or equivalent).

2)  

In order to prevent stratification, duct smoke units, where possible, must be located a minimum of six duct widths down stream

from a source of turbulence i.e. elbows, deflector plates, filters, dampers, and inlets.

In installations where it is impossible to adhere to the six duct width requirement, units can be installed closer but as far from inlets, bends or
deflector plates as possible.  Should this situation arise, check velocity readings in the duct prior to the duct smoke unit installation.   Ensure the
duct smoke unit pressure differential complies with the unit specifications.  The pressure differential between the input sampling tube and
exhaust tube for the Firex series duct smoke unit should be greater than 0.01 inches of water and less than 1.2 inches of water.

3)  

Identify a location for the installation of the duct unit that will permit easy access for viewing and serviceability.

4)  

Install duct units in the return air side of an HVAC unit prior to the air being exhausted from the building or diluted with outside air.

5) 

When installing duct smoke units down stream of filters, fires occurring in the filters will be detected, but if the filters become blocked
insufficient air flow through the duct unit will prevent the correct operation of the duct detector.

6)  

Where possible, install duct detectors upstream of air humidifiers and downstream of dehumidifiers.

7)  

To prevent false alarms, the duct detector should not be mounted in areas of extreme high or low temperatures, in areas where high
humidity exists or in areas where the duct may contain gases or excess dust.

SAMPLING TUBE ASSEMBLY

:

Sampling tubes are to be ordered separately in one of the 3 standard lengths.

532

For duct widths of 

1.0’ TO 2.5’

533

For duct widths of

2.5’ TO 5.0’

534

For duct widths of

5.0’ TO 10.0’

The standard sampling tubes are steel tubes with air intake holes drilled down the entire length of the tube.  These tubes must be cut to length
and must span the entire width of the duct.  Sampling tubes over 3.0 feet must be supported on the opposite side of the duct.  To ensure the
correct operation of the sensing tube, the red end cap (red stopper in installation kit) must be inserted in the end of the air intake sampling tube.

Once the airflow direction has been determined, insert the inlet and exhaust tubes into the sampling tube connectors fitted to the back of the
duct smoke detector which are equipped with set screws.  These connectors will allow the tubes to be correctly orientated and secured by
tightening the set screw.  Ensure air intake sampling tube is positioned so that the inlet holes are facing the airflow.

2

6 Duct Widths

Minimum

Bend or Other
Obstruction

Insert Red Stopper
This End of Inlet Tube

Air Flow

Tube Support Hole Only for Ducts
Greater than 3 Feet Wide

Duct Width

Air Flow
Direction

Exhaust Tube
Installed Downstream of
Air Flow
Do Not Insert
Red Stopper

Set
Screw

Holes Face
Air Flow

Inlet Tube

2650 Duct Smoke
Detector

Содержание 2650-660

Страница 1: ...ARE SHOWN IN THE NON ENERGIZED CONDITION The trouble contact will not operate in the event of a smoke alarm The Firex Duct Detector models 2650 660 and 2650 661 will operate on one of the following input voltage sources 24VAC 24VDC 115VAC and 230VAC The duct smoke detector units are designed to operate in duct widths from 12 inches to 10 feet wide with an air velocity between 500 and 4000 feet per...

Страница 2: ...en installing duct smoke units down stream of filters fires occurring in the filters will be detected but if the filters become blocked insufficient air flow through the duct unit will prevent the correct operation of the duct detector 6 Where possible install duct detectors upstream of air humidifiers and downstream of dehumidifiers 7 To prevent false alarms the duct detector should not be mounte...

Страница 3: ...erential pressure between the inlet and exhaust tubes The differential pressure between the two tubes should be greater than 0 01 inches of water and less than 1 2 inches of water Model Number Detector Model Number S60A Ionization Detector Head 2850 250 S60A Photoelectric Detector Head 2850 350 POWER REQUIREMENTS QUIESCENT CURRENT ALARM CURRENT 24V AC 35 mA 24V AC 74mA 24V DC 15 mA 24V DC 48mA QUI...

Страница 4: ...Air Products and Controls Inc Spray the test gas directly at the detector head from a distance of 12 inches for at least 2 seconds CAUTION SPRAYING FROM A DISTANCE CLOSER THAN 12 INCHES CAN CAUSE DETECTOR CONTAMINATION After 15 to 20 seconds the detector head will go into alarm illuminating the detector head LED and causing the duct unit functions to operate relays will change state and the remote...

Страница 5: ...ad and connect one of the appropriate dedicated power sources to the applicable terminals See above Replace detector head and the unit will be energized The green LED will be illuminated When pressing the test reset button the red alarm LED will be illuminated In the event of a fire alarm certain equipment may have to be shut down A shut down will be achieved by interrupting the supply source to t...

Страница 6: ... 1 Firex Detector 2 EOL End of Line Fig 1 17 19 19 21 REMOTE ACCESSORY WIRING vvv vvv 21 20 13 19 vvv 18 14 YELLOW TROUBLE LED KEY OR PUSH BUTTON TEST RESET SWITCH RED ALARM LED AND OR HORN STROBE _ _ GREEN PILOT LED TROUBLE CONTACTS CANNOT BE CONNECTED TO FIRE ALARM PANEL WHEN USING THIS OPTION JUMPER TROUBLE TEST RESET ALARM PILOT 7 RED BLACK ...

Страница 7: ...7 18 19 20 21 ALL RELAYS OPERATE WITH SINGLE ALARM 30 DETECTORS MAX ALL RELAYS OPERATE WITH SINGLE ALARM INDIVIDUAL HORN STROBE OPERATE ON ALARMED DETECTOR ONLY 30 DETECTORS MAX ALL RELAYS OPERATE WITH SINGLE ALARM ALL HORN STROBES OPERATE WITH SINGLE ALARM 15 DETECTORS MAX COMMON TEST RESET 30 DETECTORS ONLY H NORMALLY OPEN RESET SWITCH H H H H H Unit 1 Unit 2 Unit 3 Unit 1 Unit 2 Unit 3 Unit 1 U...

Страница 8: ... Company 2820 Thatcher Road Downers Grove Illinois 60515 USA Telephone 1 630 719 5500 Facsimile 1 630 719 4400 Technical Service Telephone 1 800 445 8299 E mail mctechservices maplechase com www maplechase com TM ...

Отзывы: