Page 1
INTRODUCTION - MODELS & FEATURES
FW-DACT:
A single board Digital Communicator that can connect via Contact Closure Inputs on a single ribbon cable
to a NAPCO Fire Alarm Control Panel (FACP) such as the FW-C2Z, FW-C4Z or FW-C4EZ. It can transmit
Common Alarm, Common Supervisory, and Common Trouble information on two telephone lines.
T
Communicates to a FACP via
Contact Closure Inputs
(FW-DACT).
T
User Configurable with
FW-PCTOOL Configuration Tool
. This includes a 4-Line LCD Display and Keypad in a rugged
metal enclosure, with a ribbon cable to connect to the Communicator.
T
Communicates to a
Central Monitoring Station
using
Ademco Contact ID
or
SIA DCS
Protocols.
T
The
FW-DACT
can transmit Common Alarm, Common Supervisory and Common Trouble information on two
telephone lines.
The
DACT
continuously supervises the state of each of two connected Telco Lines (at approximately 1 minute intervals)
by both a Line-DC level measurement, and by checking for a Dial-Tone. If either fails, a Line #1 or Line #2 Trouble event
will be reported. Once a Line has been restored, a Line Trouble Restored event will be reported. The product will
always
report events sorted in the order in which they are received / recognized. The products are capable of reporting multiple
events to a single Account number, within a single call session. Up to 4 retries, for a single message not yet reported,
will be made within a single call-attempt. A failure to communicate to either or both Accounts will generate a
corresponding event which will be queued for reporting.