![FIREWOLF FW-DACT Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/firewolf/fw-dact/fw-dact_installation-and-operation-manual_2292295012.webp)
Page 10
Periodic (24 hr) Test Event (Off Normal)
Test
New event
RP
01
Manually initiated dialer test
Test
New event
RX
00
DACT External Events (FW-DACT):
Event Description
Event Family
Qualifier
SIA Event Code
Parameter
Fire Alarm
Alarm
New event
FA
00
Fire Alarm restored
Alarm
Restore
FH
00
System Trouble detected
Trouble
New event
FT
00
System Trouble restored
Trouble
Restore
FJ
00
Supervisory condition
Supervisory
New event
SS
00
Supervisory restored
Supervisory
Restore
SR
00
COMPATIBLE FIRE ALARM CONTROL PANELS
NAPCO FW-DACT:
Compatible with
NAPCO FW-C2Z, FW-C4Z, FW-C4EZ
Fire Alarm Control Panels.
COMPATIBLE RECEIVERS
The
NAPCO FW-DACT
is compatible with the following
Digital Alarm Communicator Receivers (DACR)
...
DACR Receiver Model
Protocols
SurGard MLR2 Multi-Line Receiver (ULC, ULI Approved)
SIA-DCS and Ademco Contact ID
Osborne-Hoffman Quickalert! II Receiver (ULI Approved)
SIA-DCS and Ademco Contact ID
Osborne-Hoffman OH-2000 Receiver (ULI Approved)
SIA-DCS and Ademco Contact ID