SETTINGS
OPTION SETTINGS
NOTE:
The list of available options and the settings associated with them will vary with each controller. Below are the
most common user defined settings that may appear.
1
AUDIBLE
Use arrows to enable or disable the audible alarm for selected option. Press to confirm.
1
COMMON ALARM
Use arrows to enable or disable the common alarm output for selected option.
Press to confirm.
Option Settings
EVENT LOG
The Event Log is a record of events (pressure recording, alarms, starts, etc...) that are stored in the memory of the
Mark II
xg
. The last 3000 events are kept in this memory. The events are stored in the order that they occur, with the
most recent being “first” (the last event that occurred will be event #1). The following keys are used to browse through
the event log:
Move forward through the events one at a time (1 - 2 - 3....etc)
Move backward through the events one at a time (55 - 54 - 53....etc)
Move forward through the events ten at a time (60 - 70 - 80....etc)
Move backward through the events ten at a time (91 - 81 - 71....etc)
Pressing and holding of the arrow keys will allow the scrolling to move faster.
Event Log
DATA HISTORY
The Data History is a record of important data and events that are kept throughout the life of the controller.
Use arrows to scroll through the information stored in the Data History log. The available information is:
Numbers of calls to start Number of actual starts Pump total run time Pump last run time Total controller power
on time Last pump start time/date Minimum system pressure Maximum system pressure Last phase failure
Last phase reversal Total Cycle Count Average Cycle Count/Hour Cycle Count Last Hour Average Cycle Count/Day
Cycle Count Last Day Average Cycle Count/Month Cycle Count Last Month Cycle Count/Set Interval
Data History
FACTORY
CONFIGURATION
MODEL
3
SERIAL NUMBER
Use arrows to enter the controller serial number. Press to confirm.
NOTE: This is a factory set parameter and under normal circumstances would never be changed.
3
MODEL
Use arrows to select required model number. Press to confirm.
NOTE: This is a factory set parameter and under normal circumstances would never be changed.
3
HP (HORSEPOWER)
Use arrows to select required motor horsepower. Press to confirm.
NOTE: This is a factory set parameter and under normal circumstances would never be changed.
3
VOLTAGE
Use arrows to select required voltage. Press to confirm.
NOTE: This is a factory set parameter and under normal circumstances would never be changed.
Configuration - Model