background image

 

 

 

INSTALLATION AND OPERATION INSTRUCTIONS

Jockey Pump Controllers - Models FTA560F,

FTA560E, FTA566E

Содержание FTA560E

Страница 1: ...1 INSTALLATION AND OPERATION INSTRUCTIONS Jockey Pump Controllers Models FTA560F FTA560E FTA566E ...

Страница 2: ...tem Pressure Connections 3 Making Electrical Connections 3 Methods of Starting Stopping 4 Control Buttons and Items on Keypad 5 Programmable Settings 6 Keypad Programming Procedure 7 Keypad Shortcuts 8 Visual Setup Instructions 9 10 Inspections of Controller and Operation 11 i ...

Страница 3: ...CONNECT SWITCH MUST BE IN THE OFF POSITION IN ORDER TO OPEN THE ENCLOSURE DOOR FIRETROL INC CANNOT BE LIABLE FOR ANY MISAPPLICATION OR INCORRECT INSTALLATION OF ITS PRODUCTS 1 WARNING This product can expose you to chemicals including DINP which is known to the State of California to cause cancer and DIDP which is known to the State of California to cause birth defects or other reproductive harm W...

Страница 4: ...uipment 2 Drill for drilling wall anchor holes 3 Hole conduit punch 4 Hand level 5 Tape measure 6 Four anchors with bolts and washers per enclosure Procedure Note Refer to the controller dimension drawing for necessary mounting dimensions The controller is wall mounted by using at least four 4 wall anchors 2 anchors for the top mounting brackets and 2 anchors for the bottom mounting brackets The b...

Страница 5: ...information Procedure All field connections remote alarm functions and AC wiring are brought into the enclosure through the top or bottom conduit entrances as indicated on the dimensional drawing Do not place conduit entrances in the sides of the enclosure 1 Using a hole conduit punch create a hole in the enclosure for the size conduit be ing used 2 Install necessary conduit 3 Pull all wires neces...

Страница 6: ...e STOP button will stop the motor for as long as the button is held pressed The motor will restart once button is released Bump For Rotation The combination of the Manual Start and the Manual Stop can be used to bump for rota tion If the rotation is incorrect turn OFF power with the door mounted disconnect Swap any two existing motor lead wires that are on the motor contactor in the controller Aut...

Страница 7: ...increasing or decreasing a parameter value shown on the screen The Left Right buttons are used to scroll through the five available programming settings 5 Enter Pushbutton Looks like a check mark inside of a gear This is used to access the pa rameters to program and to confirm programming changes The programming procedure is described below 6 ON OFF Pushbutton This is located on the lower right ha...

Страница 8: ... PSI BAR Kpa Feet H2O and Meter H2O The keypad display will show the pressure measured by the controller from the connected sensing line using that selected unit of pressure 4 Once the pump is running in automatic mode from the controller it will run for the pro grammed number of seconds after the Stop Pressure point has been reached This setting is adjustable from 0 to 9999 seconds A small red do...

Страница 9: ...n is kept pressed the faster the displayed number will change Once completed press Enter again Cu In will be shown D Press the right arrow pushbutton once Now Unit will be shown The default setting for the unit of pressure measurement is PSI If another unit of measurement is desired available choices listed above press the Enter button Then use the up or down or buttons to select the desired unit ...

Страница 10: ...n ON Delay Timer simultaneously press the Down arrow button and left arrow button OFF Delay Timer simultaneously press the Up arrow button and left arrow button Number of times pump has started simultaneously press the Up arrow button and right arrow button Pump Running Elapsed Time simultaneously press the down arrow button and right arrow button Stop Pressure Off Delay Timer of Starts Start Pres...

Страница 11: ...ity NEMA Type FLC Max Pres HP Ctr Volt Line Volt Phase H Model Mfg Date 7 6 Firetrol Models FTA560F FTA560E FTA566E 1 2 5 L1 L2 L3 T1 C1 T2 T3 AUTO HAND AUTO HAND AUTO HAND 5 sec AUTO HAND 4 3 AUTO HAND C1 T1 T2 T3 C1 T1 T2 T3 9 1 2 NPT ...

Страница 12: ...AUTO HAND AUTO HAND 2 sec OK 9 8 UNIT CUT OUT CUT IN ON TIMER OFF TIMER GREEN CUT IN CUT OUT 10 ...

Страница 13: ...heck for water leaks on pressure transducer and piping Inspect door for proper alignment and function of door locks Check tightness of all wiring connections Inspect the controller for proper grounding Inspect internal and external components for any damage Inspect motor starter power contacts Check tightness of all component mounting hardware OPERATIONAL INSPECTION YES NO Verify proper motor rota...

Страница 14: ...en taken to ensure accuracy and completeness herein Firetrol Inc assumes no responsibility and disclaims all liability for damages result ing from use of this information or for any errors or omissions Specifications and drawings are subject to change without notice 2021 Firetrol Inc All Rights Reserved Publication NS560 01 ...

Отзывы: