Firestorm Stoves 4.5KW Скачать руководство пользователя страница 2

Installation Instructions

 

 

 

 

The installer has a responsibility under the Health and Safety at Work Act 1974 to provide for the 
safety of persons carrying out the installation. Attention is drawn to the fact that fire cement is 
caustic and hands must be washed thoroughly after use. The appliance is heavy and care must be 
taken during handling. 

 

Although the appliance does not contain asbestos products, it is possible that asbestos may be 
disturbed in existing installations and every precaution must be taken. 
These instructions give a guide for the installation of the appliance but in no way absolves the 
installer from responsibilities to confirm to British Standards, in particular BS8303 and BS6461, 
relating to the installation of solid fuel appliances. All local regulations, including those referring to 
National and European standards need to be complied with when installing the appliance. 

 

 

 

 

Chimney & Flue

 

 

 

 

 

 

The successful operation of these appliances relies on the adequate performance of the chimney to 
which it is connected. The chimney must: 

Have an internal cross section of not less than 320 Cm.sq (200mm Dia.). (If a flue liner is 
used it should be not less than 150mm diameter and suitable for solid fuel and comply with 
2010 approved document J:2.6 ). 

Be a minimum 4.6m high from hearth level to pot. 

Be terminated at least 1m above roof level so that the chimney does not terminate in a 
pressure zone. 

Be free from cracks, severe bends, voids, and obstructions. 

Be connected to this one appliance only. 

New chimneys must be built in accordance with local building regulations. 

Existing chimneys must be tested in accordance with HETAS requirements. 

If the stove is installed as a freestanding appliance, it should not support any part of the 
chimney. 

Voids in the chimney should be avoided, as these will prevent a steady flue draught. 

The stove flue pipe should pass beyond the narrowing of the chimney. See Fig.1 

Consideration should be given to falling soot. For rear outlet stoves it may be necessary to 
provide soot catchment area in the form of a 90 degree tee with removable soot door at the 
rear connection. 

A flue/chimney access point may also be required so that the state of the chimney can be 
checked and any fallen soot removed. 

External flues must be insulated to prevent heat loss. 

o   

All stoves need air to breath, any stove with an output above 5 kW needs a permanent air 

supply into the room in which the stove is to be installed. 

This should be at least 550 mm" per kW output pf appliance. Please check current building 

regulations document j on the current ventilation requirement at the time of installation. 

Содержание 4.5KW

Страница 1: ...TION USER INSTRUCTIONS 10Kw 6 5Kw 4 5Kw Firestorm Stoves Welcome Court Unit 2 Bracewell Avenue Poulton Business Park Poulton Le Fylde Lancashire FY6 8JF Tel 01253885554 Fax 01253 885585 Web www firest...

Страница 2: ...with 2010 approved document J 2 6 o Be a minimum 4 6m high from hearth level to pot o Be terminated at least 1m above roof level so that the chimney does not terminate in a pressure zone o Be free fr...

Страница 3: ...ught test hole must be drilled in the flue pipe as close to the stove as possible and before any flue draught stabiliser Minimum The stove should be lit and allowed to warm the flue thoroughly The air...

Страница 4: ...only a guide as an apparently poor flue may improve once the stove is installed lit and the flue is warmed If once the stove is installed there is any doubt that the chimney is providing an adequate...

Страница 5: ...al should not exceed 80 C There should be sufficient space around the stove for service work Hearth The construction of the hearth must conform to Building Regulations must be firm non combustible and...

Страница 6: ...ore lighting the stove Once the stove is under fire check all seals for soundness and check that the flue is functioning correctly and that all products of combustion are vented safely to atmosphere v...

Страница 7: ...ood Peat Peat is a fuel conveniently available in some areas and should be burned in the same manner as wood Anthracite Smokeless a natural form of coal burns with great heat and is long lasting Ecoal...

Страница 8: ...and corrected If necessary seek expert advice The most common cause of fume emission is flueway or chimney blockage For your own safety these must be kept clean at all times CO Alarm Your installer s...

Страница 9: ...Components A Top or rear flue collar B Blanking plate C Removable handle D Baffle plate E Rear fire bricks F Side fire brick G Bottom grate H Secondary air control Air wash I Primary air control J Baf...

Страница 10: ...f gases and smoke which could ignite with a bang the moment air is reintroduced Tertiary Air Leaving the tertiary air inlets open reignites the un burnt gases within the firebox ensuring a cleaner bur...

Страница 11: ...bed but will not provide air for the volatile gases above the fire bed to combust resulting in a smoky inefficient fire Ash Removal Only remove small amounts of ash from the firebox When de ashing lea...

Страница 12: ...long period summertime for instance Remove all the ashes from the grate and ash pan and use a vacuum cleaner nozzle to clean ash from the base of the stove Remove the baffle plate and brush the flue...

Страница 13: ...ssion at 13 O2 0 60 Mean flue gas temperature C 249 Flue mass gas flow g s 2 7 Note Tests carried out at 12 Pa flue draught Performance results Ancit Mean Test duration h 2 00 Total Efficiency 78 1 No...

Страница 14: ...rovided air vent may be necessary for example small or tightly sealed rooms Air openings provided for this purpose must not be restricted It is important that flue ways are cleaned frequently and the...

Страница 15: ...panels rope seals glass seals bottom grate ash pan firebricks baffle plate How to proceed with a complaint If you have cause for dissatisfaction with your stove you should first contact your Firestor...

Страница 16: ...irestorm Stoves is Registered at the UK Patent Office 4010608 and is fully protected by Copyright and UK Design Right Firestorm stoves 19March 2009 Designed manufactured and distributed by Firestorm S...

Отзывы: