FPC-5V2
April 2019
2 |
P a g e
This Operation & User Manual provides information on the FPC-5V2 fire protection module
and how it is connected to the various
FirePro
Condensed Aerosol Generators.
Autonomous fire suppression unit
Primary power source: 3Vdc battery.
Battery monitoring feature with LED - indication.
Manual or Automatic battery status indication.
Single input detection loop.
Linear heat detector cable or a bimetallic sensor
c
onnections
Figure 1: FPC-5V2 module.
The
FirePro
fire protection module detects fire by using either a linear heat detector
cable or a bimetallic sensor and activates the condensed aerosol fire suppression
generators automatically in electrical cabinets and similar enclosures.
Figure 2: Fire detection devices.
Input detection terminal (J7 on the PCB) is available for connecting the linear heat
detector cable or a bimetallic sensor. Output terminal (J6 on the PCB) can be used to
connect the condensed aerosol fire suppression generator. Both J7 & J6 terminals
are not electrically polarized.
+
-
Figure 3: Interconnecting the fire detection devices.