Firenzo CONTESSA Скачать руководство пользователя страница 6

 

CI-2013-05-14 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.1 Floor protector requirements 

This appliance has been tested as required under ADJ Page 37 Item 2.23a and maximum temperature rise 
recorded at 37°C. Only a hearth made of non-combustible board/sheet materials or tiles at least 12mm thick 
are required. 

The heater should always be installed on top of its leg base due to high temperaturessustained over long 
periods of use.  It is recommended that the appliance be secured to the floor protector to ensure stability with 
the brackets supplied. 

In situations where the stove is to be fitted into a brick or non-combustible recess, we recommend that the stove 
is installed with at least 100mm clearance to the wall, this will allow room air to circulate around the stove; also 
the maintenance of the outside stove is easier. When applied to masonry, a layer of wallpaper is normally 
classified as a non-combustible surface. 

5.2 On the floor 

National and Local Building Regulations must again be observed when considering the type, thickness and area 
of the hearth to be used in the installation. Max Hearth temperature under safety test was 37°C. One should of 
course always make certain that the underlying floor surface can bear the weight of the stove. 

5.3 Clearance to furniture and soft furnishings 

We recommend that the stove be installed 700 mm from furniture. Serious consideration should also be given to 
positioning of any furniture that could be adversely affected by heat. The clearances to combustible materials in 
front of the stove should be a minimum of 700 mm. When lit, a wood-burning stove gets hot and therefore 
adequate protect must be provided, particularly in situations where there is a safety risk to children or the infirm. 
A suitable safety guard around the stove should be considered. 

6. HETAS amendments 

6.1 More detailed advice about existing chimney usage 

NOTE: A chimney height of not less than 4.5 metres measured vertically from the outlet of the stove to the top of 
the chimney should be satisfactory. Alternatively the calculation procedure given in EN 13384-1 may be used as 
the basis for deciding whether a particular chimney design will provide sufficient draught. 

The outlet from the chimney should be above the roof of the building in accordance with the provisions of Building 
Regulations Approved Document J. 

If installation is into an existing chimney then it must be sound and have no cracks or other faults which might 
allow fumes into the house. Older properties, especially, may have chimney faults or the cross section may be 
too large i.e. more than 230 mm x 230 mm. Remedial action should be taken, if required, seeking expert advice, 
if necessary. If it is found necessary to line the chimney then a flue liner suitable for solid fuel must be used in 
accordance with Building Regulations Approved Document J. 

Any existing chimney must be clear of obstruction and have been swept clean immediately before installation of 
the stove. If the stove is fitted in place of an open fire then the chimney should be swept one month after 
installation to clear any soot falls which may have occurred due to the difference in combustion between the 
stove and the open fire. 

A = 150mm 
B = 345mm 
C = 220mm 

NB Clearances are measured from the 
edge of the top castings.

 

Содержание CONTESSA

Страница 1: ...1 CI 2013 05 14 Instructions for Installation Contessa Freestanding Woodburner Firenzo Woodfires UK Limited 98 Niven Street Napier 4142 New Zealand Website www firenzo co uk ...

Страница 2: ...s 3 3 1 Draught 3 3 2 The draught will be reduced when 3 3 3 A good draught is achieved when 4 Chimney sweep 5 Stove placement clearance and floor protector requirements 5 1 Floor protector requirements 5 2 On the floor 5 3 Clearance to furniture and soft furnishings 6 HETAS amendments 6 1 More detailed advice about existing chimney usage 6 2 Commissioning and handover 6 3 Extractor fan 6 4 Perman...

Страница 3: ...t 2 5 Metal parts When installing or servicing this stove care should be taken to avoid the possibility of personal injury 2 6 Note of references to the current UK regulations In all cases the installation must comply with current Building Regulations Local Authority Byelaws and other specifications or regulations as they affect the installation of the stove It should be noted that the Building Re...

Страница 4: ... and up to 50kW rated output burning any fuel 175mm diameter or rectangular square flues having the same cross sectional area and a minimum dimension not less than 150mm NOTES 1 Closed appliances include cookers stoves room heaters and boilers 2 Fuels such as bituminous coal untreated wood or compressed paper are not smokeless or low volatiles fuels 3 These appliances are known as exempted firepla...

Страница 5: ...The chimney is not tall enough with the result that it sits in the lee of the roof surface or tall trees These conditions are also associated with the greatest risk of smoke coming back down the chimney Air is entering the chimney in undesired places e g through cracked joints or leaks in the cleaning door or the flue pipe Unsealed unused fireplaces are connected to the chimney The flue pipe and c...

Страница 6: ... of 700 mm When lit a wood burning stove gets hot and therefore adequate protect must be provided particularly in situations where there is a safety risk to children or the infirm A suitable safety guard around the stove should be considered 6 HETAS amendments 6 1 More detailed advice about existing chimney usage NOTE A chimney height of not less than 4 5 metres measured vertically from the outlet...

Страница 7: ... to do should smoke or fumes be emitted from the stove The customer should be warned to use a fireguard to BS 8423 2002 Replaces BS 6539 in the presence of children aged and or infirm persons 6 3 Extractor fan There must not be an extractor fan fitted in the same room as the stove as this can cause the stove to emit smoke and fumes into the room 6 4 Permanent air vent The stove requires a permanen...

Страница 8: ...ent of the flue system to the spigot outlet 6 Assemble and install flue system accordingly to comply with all national and local regulations 7 Fit the air control knob place the flat on the knob to the flat on the shaft situated on the right hand side of the fire Press home firmly 8 Fit door knob with spacer as per drawing shown below 9 Commission stove to ensure correct operation and adequate flu...

Отзывы: