Integrated Fire Protection System
Mechanical Section - Dry-pipe Vacuum Sprinkler System - Electric Release
FM-060M-0-112B
1.3 Placing the system in service
1. Verify that all vacuum sprinklers are set and that
inspector's test valve and/or piping auxiliary drain valves
are
CLOSED
.
2. Verify that the system has been properly drained (see
warning note below).
CLOSE
main drain valve
(D3)
,
system drain valve
(G10)
and alarm line drain
valve
(B7)
. Verify that the manual emergency
release
(B10)
is
CLOSED
.
Warning !
It is very important to properly drain the piping
network in order to reduce the effect of corrosion.
3. Turn on the vacuum pump switch
(G16)
(see
section
D
VACUUM SUPPLY
).
The sign [
] will be displayed on the
FLX-PC
®
(G18)
when the pump is running and excess water in deluge
valve (
A1
) will be drained by vacuum pump (
G1
).
4. When vacuum pump
(G1)
stops, solenoid valve
(G2)
should close.
FLX-PC
®
(G18)
should display vacuum
level.
5.
OPEN
priming valve
(B1)
.
6. Reset the release control panel. Solenoid valve
(F1)
should close. Water pressure rises slowly on
gauge
(B11).
Silence the alarm.
7.
OPEN
flow test valve
(B6)
.
PARTIALLY OPEN
main water
supply valve
(D1)
.
Note:
Do not open main water supply valve
(D1)
until
gauge
(B11)
shows stabilized pressure.
8. When full flow develops from the flow test valve
(B6)
,
CLOSE
the flow test valve.
9.
FULLY OPEN
the main water supply valve
(D1)
. Reset
the release control panel.
10. Verify that the alarm test valve
(B5)
is
CLOSED
and that
all other valves are in their "normal" operating position
(refer to paragraph 2.2
NORMAL CONDITION
of the current
section for details).
11. Check and repair all leaks.
12. On new installation, system that has been placed out of
service, or where new equipment has been installed, trip
test the system to verify that all equipment functions
properly. Refer to paragraph 1.7.2
INSPECTIONS & TESTS
of the current section for instructions.
WARNING !
Performing a trip test will result in operation of
the deluge valve
(A1)
. Water will flow into the piping
network. Take necessary precautions to prevent damage.
13. After completing the trip test, perform paragraph 1.8
MAINTENANCE – SEMI-ANNUALLY
of the current section.
14. Notify the
AUTHORITY HAVING JURISDICTION
, remote
station alarm monitors, and those in the affected area
that the system is in service.
Warning !
Do not open main drain valve
(D3)
or alarm line
drain valve
(B7)
or the manual release valve
(B10)
while
system is in service. This will cause the system to trip.
Pressures settings
For complete pressures settings, see section
D
VACUUM
SUPPLY
.