Inspection and Maintenance Section
FM-0723-0-7H
Installation
ICAF system shall be located, installed, or suitably protected
so as to not be subjected to mechanical, chemical, or other
damage that could render them inoperative. Foam
concentrates are subject to freezing or deterioration from
prolonged storage at high temperatures, the system shall
therefore be located in a room with ambient temperature from
40
°
F to 110
°
F (4
°
C to 43
°
C).
Although it is preferable to locate the system outside the
protected area, in the case where there is no other
alternative, provisions should be made to ensure that the
system is not going to be exposed to fire or mechanical
damage in a manner that would affect its operation.
System shall also be installed so that inspection, testing,
recharging, and other maintenance are facilitated and
interruption to protection is held to a minimum.
1. Install the ICAF
S
ystem unit, cylinders bank and foam
concentrate tank according to the technical data
supplied.
Note:
The drain collector shall be connected to an open
drain. Do not restrict or reduce drain piping.
2. Install the open nozzles piping network in accordance
with the ICAF System's Design Manual (FM-090M-0-01).
3. Install the releasing piping (if applicable), detection and
signaling circuits in accordance with applicable NFPA
standards.
4. Conform to local municipal or other codes regarding
installations of fire protection systems.
5. Perform preliminary inspection outlined below prior to
putting system in service.
6. Put the system into operation as outlined below.
7. Perform the annual inspection sequence and test each
detector and alarm unit.
8. If the system does not operate as it should, make the
necessary corrections according to manuals issued or
consult your distributor or
F
IRE
F
LEX
Systems Inc.
9. Make sure that the building owner or a delegated
representative has received instructions regarding the
operation of the system.
Inspections, Tests & Maintenance
Regular inspections, tests, and maintenance should be
performed at intervals specified in this document to verify that
the ICAF system is in good operating condition and that it
functions as intended. Components shall be restored to full
operational condition following inspection and testing.
The frequency of the inspections may vary due to
contaminated
water
supplies,
corrosive
or
humid
atmospheres as well as the condition of the air supply to the
system. In addition to the instructions herewith, local
Authority
Having
Jurisdiction
may
have
additional
maintenance, testing and inspection requirements which
must be followed.
Warning !
Any system maintenance which involves placing
a control valve or detection system out of service may
eliminate the fire protection capabilities of that system.
Prior to proceeding, notify all Authorities Having
Jurisdiction. Consideration should be given to the
employment of a fire patrol in the affected areas.
RESPONSIBILITY of the Owner:
1. The
responsibility
for
properly
maintaining
the
compressed air foam system shall be that of the owner
of the property.
2. Inspection,
testing,
and
maintenance
shall
be
implemented in accordance with procedures meeting or
exceeding those established in this document.
3. These tasks shall be performed by
F
IRE
F
LEX
's
authorized personnel who have developed competence
through training and experience.
4. It is the responsibility of the owner to promptly correct or
repair deficiencies, damaged parts, or impairments
found while performing the inspection, test, and
maintenance requirements of this document.
5. Corrections and repairs shall be performed by qualified
F
IRE
F
LEX
's authorized personnel.
6. The building owner shall not make changes in the
occupancy, the use or process, or the materials used or
stored in the building without evaluation of the fire
protection systems for their capability to protect the new
occupancy, use, or materials.
7. Where changes are identified, the owner shall promptly
take steps to evaluate the adequacy of the installed
system in order to protect the building or hazard in
question. Where the evaluation reveals a deficiency
causing a threat to life or property, the owner shall make
appropriate corrections.
Содержание ICAF System
Страница 1: ...Operation Maintenance Manual FM 0723 0 02 A ...
Страница 7: ...OWNER S OPERATION MAINTENANCE MANUAL ICAF Integrated Compressed Air Foam System FM 0723 0 5B ...
Страница 27: ...Page 4 of 4 ICAF Integrated Compressed Air Foam System System Trim Section FM 0723 0 10 A ...
Страница 41: ...Page 2 of 2 J ICAF Integrated Compressed Air Foam System User Notes FM 0723 0 16D User Notes ...